RIVC000001   Pag. 11  

 

REV. 00  11/10/10 

UK

7.

Switching on/off
When the machine is energised, the display will read OFF and show the coldroom temperature 
alternately.  To switch the Blocksystem on (off), hold down the “ON/OFF” key on the front of the machine 
for more than 5 seconds. 

7.

Coldroom temperature adjustment
The temperature ranges within which the Blocksystem can operate are as follows: 

Minimum 

Maximum

High Temperature  (HBP) 

+2

+10

Medium Temperature 

(MBP) 

-5

+5

Low Temperature  (LBP) 

-25

-15

The temperature adjustment setpoint can be accessed directly for display or adjustment purposes. 

Press and release SETPOINT: the display will read “SEt” (the procedure is slightly different if there

are alarms in progress; see the machine status display paragraph)

Press SETPOINT: the green SET LED will switch on and the Setpoint value will be displayed

Press UP or DOWN to set the new value

Press SETPOINT or ON/OFF (or wait for the 5-second timeout) to confirm the value (the SET LED

will switch off and the display will read “SEt”)

Press ON/OFF (or wait for the 5-second timeout) to return to the normal display mode

7.

How to vary parameters
Blocksystem operation is governed by parameters that have been stored in the memory of the electronic 
control unit by the manufacturer (see the parameters table).  These factory settings should not be varied 
unless strictly necessary, and in all cases such operations are only to be carried out by qualified staff. 

Parameters are not only divided by function, they are also divided according to their security/accessibility 
levels: 

Level 0 

Setpoint parameters 

direct access (see paragraph 7.3) 

Level 1 

frequently used parameters 

access without password (see paragraph 7.5) 

Level 2      configuration parameters         access with password (see paragraph 7.7) 
Parameters can be varied as follows: 

ƒ

From the keyboard

ƒ

Via LAN network (Master/Slave)

ƒ

Via Supervision network

7.

How to vary level 1 parameters

ƒ

Hold down SET for 5 seconds until the display reads “reg” (adjustment parameters)

ƒ

Press UP or DOWN until the required menu appears on the display

ƒ

Press SET to access the menu; the code number for the first parameter in the selected menu will
appear

ƒ

Press UP or DOWN until the required parameter appears

ƒ

Press SET to view the value of the parameter

ƒ

Press UP or DOWN to set the required value

ƒ

Press SET to confirm the value and return to the parameters list; press ON/OFF to confirm the
value and return to the menu list

ƒ

Press ON/OFF to pass from the parameters list to the menu list

ƒ

Press ON/OFF again to exit the editing procedure,

If no key is pressed for more than 15 seconds, any value shown on the display will be stored in the 
memory for the relevant parameter and there will be a forced exit from the parameters variation 
procedure.

 

7.

Machine status display

ƒ

Press and release SET: the display will read “SEt” or “AAL” if there are any alarms in progress

ƒ

Press UP or DOWN until the required status is displayed

AAL 

alarms in progress (if present) 

SEt setpoint 

Summary of Contents for RIVC000001

Page 1: ...Mod AN203T 2F Production code FAL016G012 DI 06 2022 ...

Page 2: ...RIVC000001 REV 00 11 10 10 UK RIVC000001 USE AND MAINTENANCE HANDBOOK ...

Page 3: ... is in progress LIT A serious alarm is in progress and alarm relay activated BLINKING A non serious alarm is in progress or a serious alarm has been silenced alarm relay deactivated SETPOINT key SETPOINT REDUCED SET green LED LIT The setpoint is displayed BLINKING The reduced set is activated ENTER key This is used to set the setpoint to access the programming menu and to view the machine status i...

Page 4: ...ations are only to be carried out by qualified staff Parameters are not only divided by function they are also divided according to their security accessibility levels Level 0 Setpoint parameters direct access see paragraph 7 3 Level 1 frequently used parameters access without password see paragraph 7 5 Level 2 configuration parameters access with password see paragraph 7 7 Parameters can be varie...

Page 5: ...time The time starting from the moment of deactivation for which it is not possible to restart the compressor 0 60 min dbi 1 Delay between switch on times The time starting from the moment of previous activation for which the compressor cannot be restarted 0 60 min OdO 1 Outputs delay at power on compressor fans defrosting This is used to delay the enabling of adjustments after the instrument has ...

Page 6: ...fter a high or low temperature alarm condition 1 0 90 0 C F HAL 1 Maximum alarm threshold Above this value absolute or referred to the setpoint an alarm is triggered If the reference is relative the unmarked value is added to the setpoint 50 0 199 0 C F LAL 1 Minimum alarm threshold Below this value absolute or referred to the setpoint an alarm is triggered If the reference is relative the unmarke...

Page 7: ...mperature above which defrosting is ended If at the start of a defrosting cycle the temperature is greater than that set no defrosting will be carried out In the event of a probe 2 malfunction the defrosting cycle will in any case terminate after reaching a time limit 50 0 199 0 C F Note To release the keypad hold down SET and ON OFF together for at least 5 seconds Note The LAn network parameter o...

Page 8: ...ng element Application 5 5 C 25 15 C 2 10 C 5 5 C 25 15 C Menu Code no CPP 1 CPP 2 CPP 3 CPP 4 CPP 5 REG SEt 2 0 18 0 5 0 2 0 18 0 REG diF 2 0 2 0 2 0 2 0 2 0 REG HSE 5 0 15 0 10 0 5 0 15 0 REG LSE 5 0 25 0 2 0 5 0 25 0 DEF dtY 1 1 0 0 0 DEF dEt 15 15 15 30 30 DEF dSt 10 0 15 0 10 0 15 0 15 0 Fan FSt 8 0 5 0 50 0 8 0 5 0 Fan Fdt 1 2 0 1 2 Fan dt 2 2 0 2 2 Fan dFd 1 1 0 1 1 Follow the instructions ...

Page 9: ...tch alarm adjustment is disabled permanently yes yes at switch on LO low temperature alarm yes yes automatic when the condition ceases HI high temperature alarm yes yes automatic when the condition ceases EE data saving alarm default parameters are loaded yes yes at power on or after the parameter has been stored to memory Ec condenser cleaning alarm blink no automatic when the condition ceases Er...

Page 10: ...ly there is an EMERGENCY SYSTEM that can be used to maintain the unit in operation until it can be replaced To use this system proceed as follows 1 Cut off power to the Blocksystem 2 Remove all jumpers between the L terminals and the common contacts of the card relays terminals 25 28 33 36 38 3 As shown in the diagram connect a thermostat between the L terminal the NO terminals terminals 32 37 and...

Reviews: