10 Technical specifications
14
Rittal fan-and-filter unit assembly and operating instructions
EN
Unit
Model No. SK
Fan-and-filter unit,
RAL 7035
–
3240.100
3240.110
3240.124
3241.100
3241.110
3241.124
EMC fan-and-filter
unit,
RAL 7035
–
3240.600
–
–
3241.600
–
–
Rated operating
voltage
V
Hz
230, 1~,
50/60
115, 1~,
50/60
24 (DC)
230, 1~,
50/60
115, 1~,
50/60
24 (DC)
Rated current max.
A
0.19/0.18
0.38/0.36
0.07
0.27/0.28
0.54/0.52
0.2
Power
consumption
W
33/33
10
42/46
43/46
25
Pre-fuse T
A
2
4
2
4
2
Dimensions
B1/H1
mm
255 x 255
B2/H2
mm
224 x 224
T1
mm
25
T2
(max. installation
depth)
mm
107
Air throughput,
unimpeded air flow
m³/h
180/160
180
230/250
230
Air throughput with
outlet filter
including standard
filter mat
m³/h
1 x 3240.200: 138/121
1 x 3240.200: 183/205
2 x 3240.200: 165/140
2 x 3240.200: 203/230
1 x 3243.200: 165/140
1 x 3243.200: 203/230
Outlet filter
–
3240.200
EMC
outlet filter
–
3240.060
Fan
–
Diagonal, self-starting
shaded pole motor
Diagonal,
DC motor
Diagonal, self-starting
shaded pole motor
Diagonal,
DC motor
Noise pressure
level
dB (A) 51/46
51
54/56
54
Operating
temperature
°C
–30 to +55
Storage
temperature
°C
–30 to +70
Protection category
(to EN 60 529)
–
IP 54 standard
IP 55 with additional fine filter mat or hose-proof hood
IP 56 with hose-proof hood
Tab. 4: Technical specifications
We reserve the right to make technical modifications.