Rittal roof-mounted fan

3.  Mounting

3.1  Choosing the installation site

 

When choosing the installation site for the enclosure, please 

observe the following:

 

The site for the enclosure, and hence the position of the 

roof-mounted fan, must be carefully selected so as to ensure 

good ventilation.

 

The site must be free from excessive dirt and moisture.

 

Roof-mounted fans must always be installed on horizontal 

panels (roof).

 

The ambient temperature must be lower than the admissible 

enclosure interior temperature.

 

The mains connection data as stated on the rating plate of 

the unit must be guaranteed.

3.2  Notes on installation

3.2.1  General

 

Check the packaging carefully for signs of damage. 

Any packaging damage may be the cause of a subsequent 

functional failure.

Note:

 

The inlet filter must ensure an adequate air exchange.

 

The enclosure must be sealed on all sides (IP 54). If the 

enclosure has a leak, unfiltered, contaminated air may enter 

the enclosure.

 

The fan motor is a rotating component that may transfer 

vibrations and oscillations.

 

Appropriate measures to decouple vibration must be taken in 

advance by the company responsible for the overall plant or 

system.

 

During transportation, the roof-mounted fan must be secured 

in accordance with section 3.3.2 or section 3.3.3 to prevent 

damage.

3.2.2  Layout of the electronic components in the enclo-

sure

 

Take note of the air flows from the internal fans of installed 

electronic components.

 

When installing the roof-mounted fan, it is important to ensure 

that the airflows of fans and built-in electronic components do 

not adversely influence one another (air short-circuit).

 

The corresponding minimum distances between the fan and 

component must be observed in order to ensure unhindered 

air circulation.

3.2.3  General

 

Carefully deburr the cut-out to prevent injuries caused by 

sharp edges.

 

The position of the roof-mounted fan in the mounting cut-out 

is freely selectable. It should be based on the position of the 

electrical connection inside the enclosure.

 

No filter mats are needed in order to achieve protection 

category IP 21.

 

Check that the clips are completely snapped into place to 

ensure that the roof-mounted fan is securely held in the 

mounting cut-out.

 

The filter mats may be removed to achieve a higher air 

throughput. In this case, the protection category will be 

reduced to IP 21 and UL Type 1.

 

Use only original Rittal filters which bear the Rittal logo to be 

sure of the protection category, air throughout and approvals.

 

The protection category of the roof-mounted fan can be 

raised to IP 55. To this end, the pleated filters must be 

replaced with Rittal filter mats SK 3174100. The side with the 

Rittal logo must face towards the fan (see section 3.3.4).

 

Note: This reduces the air throughput. For details, please 

refer to the performance diagrams which can be found on the 

Rittal website.

 

You should inspect the filter regularly depending on the 

amount of dust. Recommended: Replace after 2,000 operat-

ing hours at the latest, and as and when necessary.

 

The orientation of the cover on the base tray is freely selecta-

ble.

Summary of Contents for SK 3138000

Page 1: ...Assembly and installation instructions Roof mounted fan SK 3138000 SK 3139100 SK 3139110 SK 3140100 SK 3140110 SK 3140140 SK 3140500 SK 3140510 ...

Page 2: ...ype 12 9 3 3 3 Additional installation steps Installation from inside IP 54 UL Type 12 10 3 3 4 Additional installation steps Enhanced protection category IP 55 UL Type 12 10 3 3 5 Additional installation steps Protection category IP 21 UL Type 1 and higher air throughput 11 4 Electrical connection 12 4 1 Connecting the power supply 12 4 1 1 Notes on electrical installation 12 4 1 2 Connection dat...

Page 3: ...out by authorised specialist personnel Children and persons with limited cognitive coordinative abili ties must not operate maintain or clean the unit or be allowed to use it as a toy Spending long periods in the airflow may irritate the eyes and muscles If extinguisher gas is used in the enclosure the roof mounted fan must be incorporated into the fire protection concept 1 Safety instructions 1 1...

Page 4: ...ttal roof mounted fan Key 1 Cover 2 Fan plate with fan 3 Inflow nozzle for air routing 4 Base tray with pleated filter 5 Electrical connector 2 1 4 5 3 Fig 1 Components 2 Product description 2 1 Components ...

Page 5: ...lter 4x pre installed Assembly and installation instructions Montage und Installationsanleitung Assembly and installation instructions Notice de montage et d installation Dachlüfter Roof mounted fan Ventilateur de toit 1x Connector 1x Tab 1 Scope of supply 2 2 Scope of supply 2 Product description ...

Page 6: ...mbient air enters the enclosure via an air inlet grille in the lower section and is drawn upwards through the enclosure by the roof mounted fan The warmed air is then returned to the outside via the fan It is not possible to change the air flow direction 2 3 2 Safety devices The fan is equipped with a thermal winding protection for protec tion against overload 2 3 3 Filter mats The roof mounted fa...

Page 7: ...When installing the roof mounted fan it is important to ensure that the airflows of fans and built in electronic components do not adversely influence one another air short circuit The corresponding minimum distances between the fan and component must be observed in order to ensure unhindered air circulation 3 2 3 General Carefully deburr the cut out to prevent injuries caused by sharp edges The p...

Page 8: ...8 Rittal roof mounted fan 3 Mounting 2 258 2 258 2 1 CLICK CLICK 3 3 Installing the roof mounted fan 3 3 1 Installation IP 21 ...

Page 9: ...9 Rittal roof mounted fan 7 TX25 4 3 TX25 3 3 2 Additional installation steps Installation from outside IP 54 UL Type 12 5 6 TX25 MA max 2 Nm 4x 3 Mounting 3 3 Installing the roof mounted fan ...

Page 10: ... 3 Additional installation steps Installation from inside IP 54 UL Type 12 3 TX25 5a 3 3 4 Additional installation steps Enhanced protection category IP 55 UL Type 12 5b MA max 2 Nm 4x 3 Mounting 3 3 Installing the roof mounted fan ...

Page 11: ...11 Rittal roof mounted fan 5a 3 3 5 Additional installation steps Protection category IP 21 UL Type 1 and higher air throughput 6 3 Mounting 3 3 Installing the roof mounted fan ...

Page 12: ... be taken at the supply end by the switch gear manufacturer or operator to ensure effective protection against lightning and overvoltage The units are classified as overvoltage category III The mains voltage must not exceed a tolerance of 10 4 1 4 PE conductor connection The PE conductor must be connected to the PE conductor system of the overall system 4 1 5 Installing the power supply Remove the...

Page 13: ...he power supply SK 3139100 SK 3139110 SK 3140100 SK 3140110 SK 3140140 SK 3140500 SK 3140510 L N PE 1 2 3 4 Fig 2 Connection diagrams Fig 3 Connector and strain relief max 9 mm Strain relief 4 Electrical connection 4 1 Connecting the power supply ...

Page 14: ...he terminal with the screwdriver and insert the connection cable as shown in the connection diagram Remove the screwdriver To operate without a pilot wire the jumper should be left in the connection terminal The unit will then be operated at maximum speed 10 V 0 10 V PWM 0 10 V PWM GND 0 10 V PWM GND 10 V 0 10 V PWM GND 0 10 V PWM Fig 4 Pilot wire 1 Max speed as delivered with jumper between the 1...

Page 15: ...r The life expectancy is at least 50 000 operating hours L10 40 C The roof mounted fan is therefore largely maintenance free From time to time the components may need to be cleaned using a vacuum cleaner or compressed air if they become visibly dirty Any stubborn oily stains may be removed using a nonflam mable detergent such as degreaser Never use flammable liquids for cleaning the unit Sequence ...

Page 16: ...5 759 759 700 749 841 841 Air throughput with filter mats and inlet filter 1 x SK 3243200 with chopped fibre filter m h 360 383 383 557 572 572 550 565 690 690 1 x SK 3243200 with pleated filter m h 425 460 460 698 730 730 690 720 847 847 Fan Radial capacitor motor Radial rotary current motor Radial EC motor Electromagnetic compatibility Immunity to interference For industrial areas to EN 61000 6 ...

Page 17: ...ter class in accordance with Packs of Model No DIN EN 779 ISO 16890 SK 3138000 SK 3139100 SK 3139110 SK 3140100 SK 3140110 SK 3140140 SK 3140500 SK 3140510 M5 ePM10 50 12 pc s SK 3174120 Tab 4 Pleated filter Chopped fibre filter To fit Model No Filter class in accordance with Packs of Model No DIN EN 779 ISO 16890 SK 3138000 SK 3139100 SK 3139110 SK 3140100 SK 3140110 SK 3140140 SK 3140500 SK 3140...

Page 18: ...odel No Packs of Model No SK 3139100 SK 3139110 SK 3140100 SK 3140110 SK 3140140 SK 3140500 SK 3140510 1 pc s SK 3118000 Tab 8 Hygrostat Speed control To fit Model No Packs of Model No SK 3139100 SK 3139110 SK 3140100 SK 3140110 1 pc s SK 3120200 Tab 9 Speed control Sensor for speed control To fit Model No Packs of Model No SK 3140500 SK 3140510 1 pc s SK 3235450 Tab 10 Sensor for speed control Co...

Page 19: ...l us Service HUB China RITTAL Electro Mechanical Technology Co Ltd No 1658 Minyi Road Songjiang District Shanghai 201612 Phone 86 21 5115 7799 213 Fax 86 21 5115 7788 E mail service rittal cn Service HUB India RITTAL India Pvt Ltd Nos 23 24 KIADB Industrial Area Veerapura Doddaballapur 561 203 Bengaluru District Phone 91 80 22890792 Fax 91 80 7623 343 E mail service rittal india com 11 Customer se...

Page 20: ...20 Rittal roof mounted fan ...

Page 21: ...21 Rittal roof mounted fan Notes ...

Page 22: ...ftware Services www rittal com contact You can find the contact details of all Rittal companies throughout the world here RITTAL GmbH Co KG Auf dem Stuetzelberg 35745 Herborn Germany Phone 49 2772 505 0 E mail info rittal de www rittal com 03 2022 D 0000 00000432 04 EN ...

Reviews: