Manual Dry Contact Card PMC12 

5

EN 

 

2  Product Introduction 

 
Relay card for installation in Rittal PMC12 
single phase ups-system. The card can be 
used at article numbers DK7857.430, 
DK7857.431, DK7857.432, DK7857.433 and 
DK7857.434. 
At the article numbers DK7857.433 and 
DK7857.434 the card can be installed in slot 1 
or 2. 
 

3  Functional Descriptions 

 
The card will transmit the ups messages via 
potential free contacts. The available messages 
are: 
 

• 

UPS on Bypass mode.  

• 

Utility Normal (Normal close or open 
contact) 

• 

Inverter On  

• 

Battery Low  

• 

Battery Bad or Abnormal  

• 

UPS Alarm  

• 

Shutdown UPS  

 

3.1.  The pin assignments of the 10-Pin 

terminal (CN3):  

 

1  2  3  4  5  6  7  8  9 

10 

 
Pin 1: UPS on Bypass mode.  
Pin 2: Utility Normal (Normal close contact) 
Pin 3: Utility Normal (Normal open contact) 
Pin 4: Inverter On  
Pin 5: Battery Low  
Pin 6: Battery Bad or Abnormal  
Pin 7: UPS Alarm  
Pin 8: Common  
Pin 9: Shutdown UPS positive (+ ) signal  
Pin 10: Shutdown UPS negative (- ) signal 

 

3.2. 

 

Jumper settings and installation 

 

• 

The shutdown function will be activated, 
after a +6~+25Vdc is put between pin9 and 
pin10 for 5 seconds. 

• 

Installation Position: slot1(DK7857.430 – 
434) or slot 2 (DK7857.433 and 7857.434) 

• 

Flexible signal output for N.C.(Normal 
close) or N.O.(Normal open) contact by 
shorting pin1-2 or pin2-3 from JP1-5. 

• 

The shutdown function will be enabled in 1 
minute after blackout occurs if the pin1-2 of 
both CN1 and CN6 be shorted by cap. Or, 
the shutdown function can only be enabled 
by pin9-10 of CN3 if the pin2-3 of both CN1 
and CN6 be shorted by cap. 

 

CN1 

JP4 

JP5 

CN6 

JP1 

CN3 

Summary of Contents for RIMATRIX5 PMC12

Page 1: ...ard FRIEDHELM LOH GROUP R i t t a l GmbH Co KG Auf dem Stützelberg D 3 5 7 4 5 H e r b o r n Deutschland Germany Email Info rittal de http www rittal com Service Tel 49 0 2772 505 0 Service Fax 49 0 2772 505 2319 A 38333 07 IT 74eng ...

Page 2: ...Manual Dry Contact Card PMC12 2 Microsoft Windows is a registered trademark of Microsoft Corporation Acrobat Reader is a registered trademark of Adobe Systems Incorporated ...

Page 3: ...ctions 4 1 1 DOCUMENTATION NOTES 4 1 2 RETENTION OF THE DOCUMENTS 4 1 3 USED SYMBOLS 4 1 4 SAFETY INSTRUCTIONS 4 1 5 PROPER USE 4 2 Product Introduction 5 3 Functional Descriptions 5 3 1 PIN ASSIGNMENTS OF THE 10 PIN TERMINAL CN3 5 3 2 JUMPER SETTINGS AND INSTALLATION 5 ...

Page 4: ... Other tasks associated with the UPS such as the assembly and installation of system components with tested standard connectors and the operation and configuration of the PMC12 UPS System may be performed only by instructed personnel 2 Observe the valid regulations for the electrical installation for the country in which the unit is installed and operated and the national regulations for accident ...

Page 5: ... on Bypass mode Pin 2 Utility Normal Normal close contact Pin 3 Utility Normal Normal open contact Pin 4 Inverter On Pin 5 Battery Low Pin 6 Battery Bad or Abnormal Pin 7 UPS Alarm Pin 8 Common Pin 9 Shutdown UPS positive signal Pin 10 Shutdown UPS negative signal 3 2 Jumper settings and installation The shutdown function will be activated after a 6 25Vdc is put between pin9 and pin10 for 5 second...

Reviews: