Technical Informations
UPS-Manual
25
EN
Model
1KVA
2KVA
3KVA
Battery System
Type
12V/7,2Ah
12V/7,2Ah
12V/9Ah
Numbers of Batteries
3
6
6
Backup Time(20%)
>66min.
>66min.
>59min.
Backup Time(40%)
>27min.
>28min.
>19min.
Backup Time(60%)
>14min.
>14min.
>12min.
Backup Time(80%)
>10min.
>10min.
>8min.
Backup Time(100%)
>7min.
>7min.
>5min.
Recharging Time
4 Hours to 90%
Charging Current (Max.)
1,1A
2,16A
2,7A
Charging Voltage
41,0Vdc±0,5V
82,0Vdc±0,5V
82,0Vdc±0,5V
Hot Swappable Battery
Yes
Internal battery
Yes
DC leakage current
≤
≤
≤
≤
30µA (
±
10µA) with no AC applied and the unit in the off position
Battery type
Sealed, non-spillage, maintenance-free, lead acid
Transfer Time
AC to DC
Zero
Inverter to Bypass
2,5ms(Typical)
Zero
DC Start
Yes
Self Diagnostics
By button of the panel or Software Control
Front Panel
LED
Load Level/Battery Level/ Battery Mode/ Normal Mode/Bypass Mode/ Self-Test/
Weak/Bad Battery/Site Wiring Fault/ Fault/ Overload/Programmable
Outlet1//Programmable Outlet2
Key
ON Button/ OFF Button/ (Test/Alarm Reset Button)
Protection
(AC Mode )
<105% continuous
>106% ~ 120% for 30 seconds transfer to bypass
>121% ~ 150% for 10 seconds transfer to bypass
>150% for immediately transfer to bypass
Buzzer continuously alarms.
Overload
(Battery Mode)
<105% continuous
>106% ~ 120% for 30 seconds shuts down
>121% ~ 150% for 10 seconds shuts down
>150% for immediately shuts down
Buzzer continuously alarms.