6.3.7
Manual call point
Manual call points are connected to the
connecting terminal "Manual call point"
(Fig. 59/12). If a manual call point is actu-
ated, the extinguishing process is released.
Normal state = switch open
Manual call point actuated = switch
closed
1 Lines to the system (connection "12")
2 Resistance R
K
= 470 Ω, 1/10 Watt
3 Resistance R
A
= 1,8 kΩ, 1/10 Watt
(delivered as such)
Several manual call points can be parallel connected (Fig. 60).
Extinguishing can be released by actuating a manual call point (
“Spare parts, accessories, consumables, and tools” on page 116
directly after the actuation and independently of the state of the automated fire
detectors.
Release of extinguishing by actuating a manual call point is suppressed if blocking is
in place.
The alarm message of the manual release must be reset manually using the upper
[Reset]