7. Configuration

7.1  Via Telnet

The menu “General configuration / SMS configuration” lets you enter the following
values needed for the ISDN unit.

ISDN MSN:

The MSN (multiple subscriber number) is assigned by the network provider.
Also the country code and the local area code must be entered (separated by “/”).
Example: +49/2772/570126

ISDN Command:

Before an SMS can be sent over the fixed network, the ISDN unit must be registered
at an SMS centre. (This is necessary only when an SMS command is to be sent to
the ISDN unit. 

Receiving SMS “alarm” messages does not require registration

). )

The Deutsche Telekom SMS Centre requires an SMS containing the text “ANMELD”
to be sent to the number 8888.
Enter 

“8888 ANMELD”

 in the field “ISDN Command”. The ISDN unit then sends this

message to the SMS centre.
The command “8888 ABMELD” cancels the registration.

SMS Unit Message:

When this option is enabled, unit messages are also sent as SMSs (e.g. timeout,
configuration change, etc.). This SMS is sent to all target numbers.

SMS Phone Number:

Here you can enter the target call numbers that are to receive SMS messages sent
by the ISDN unit.
Prefixing the target call number by “F” (the letter F followed by a space) causes the
SMS to be sent over the fixed network.

Example: F 027725052578

When the target call number is entered 

without

 the prefix 

“F”

 the SMS will be sent

to an SMS centre in accordance with the respective mobile network protocol.

Example: 027725052578

The costs differ depending on whether an SMS is sent over the fixed network
or via mobile network operators.

Summary of Contents for CMC-TC ISDN Unit 7320.830

Page 1: ... clarity these operating instructions cannot contain all detailed information nor can they take into account every conceivable case of installation operation and maintenance Specifications subject to alterations at any time The German wording shall apply in cases of doubt Accessories Processing Unit ISDN Unit 7320 830 PU 7320 100 from software version 1 21 Connection cable RJ 12 RJ 12 enclosed RJ4...

Page 2: ...t to multi point configuration ISDN S0 Bus These minimum requirements must also be fulfilled when the ISDN unit is connected to a private branch exchange Important information IMPORTANT Only one of the tools ISDN unit GSM unit or display unit may be connected to a PU IMPORTANT When the ISDN unit is used the front interface RS 232 on the processing unit is deactivated e g Hyperterminal access The s...

Page 3: ...tive that the CMC TC ISDN unit does not come into direct contact with water e g dew oil or aggressive substances The unit must not be operated in environments with flammable gases or vapours The unit must be installed in an enclosure to protect it from water and dust There must be no voltage across the CMC TC system when the CMC TC ISDN unit is connected to the PU The CMC TC ISDN unit must be prop...

Page 4: ...ter activation the ISDN unit still has no ISDN access no terminal endpoint identifier TEI assigned brief flash The ISDN socket is in the non operative state TEI assigned Layer 1 of the ISDN socket is deactivated slowly flashing s ON s OFF The ISDN socket is activated but the ISDN unit has not connected Layer 1 activated Layer 2 pending slowly flashing s ON s OFF The ISDN socket is activated but th...

Page 5: ...ned for connection to an ISDN socket 3 The 24 V DC voltage connector is designed for future developments of the CMC TC system and is not needed for running the processing unit 5 Specifications Max power consumption 80 mA Max connecting lead length 4 m processing unit to ISDN unit Rated voltage 24 V DC with supply link from the processing unit Shock resistance 1 g Operating temperature range 5 C to...

Page 6: ... to the processing unit Mandatory data ISDN MSN The MSN multiple subscriber number is assigned by the network provider Also the country code and the local area code must be entered separated by Example 49 2772 570126 ISDN Command Before an SMS can be sent over the fixed network the ISDN unit must be registered at an SMS centre This is necessary only when an SMS command is to be sent to the ISDN un...

Page 7: ...ected from processing unit Receive SMS SMS is being received Every sensor and every output can be assigned a list of target call numbers that an SMS is sent to every status change leads to an SMS message This list can be created via the menu item Sensor Units Unit xyz Sensor abc Send SMS Here you can enter a string consisting of a list of call numbers separated by the character e g 1 4 sends an SM...

Page 8: ...he syntax is correct the corresponding action initiated The system also checks whether the sender s phone number is on the list of target call numbers The action is initiated only when this is the case The ISDN connection to the switching centre is constantly checked In the event of an error the status LED lights up red ...

Page 9: ...he number 8888 Enter 8888 ANMELD in the field ISDN Command The ISDN unit then sends this message to the SMS centre The command 8888 ABMELD cancels the registration SMS Unit Message When this option is enabled unit messages are also sent as SMSs e g timeout configuration change etc This SMS is sent to all target numbers SMS Phone Number Here you can enter the target call numbers that are to receive...

Page 10: ...ing statuses ISDN unit found ISDN unit was found ISDN unit ok ISDN unit was recognised and initialised ISDN network is OK MSN missing An MSN has not been entered see section First start up ISDN no Line There is no ISDN network available e g ISDN cable not connected No SMS unit found No SMS unit connected SMS unit timeout SMS unit disconnected from processing unit Receive SMS SMS is being received ...

Page 11: ...be configured to send one or more SMS messages when its status changes The relevant menu item is Send SMS The above example specifies that an SMS is to be sent to the target call numbers 1 and 3 The target call numbers must be separated with the character and must not contain spaces ...

Page 12: ...e menu SMS Configuration lets you configure the system as described in the last section via your web browser as well The line SMS Info shows the current status see section Via Telnet Fig 4 Web browser configuration of ISDN unit ...

Page 13: ...Fig 5 Web browser configuration of sensors This browser window lets you configure the target call number s an SMS is to be sent to on a status change the input format is 1 2 3 4 for all four target call numbers ...

Page 14: ...us report e g Alarm too high low etc Example 28 02 2002 14 33 CMC TC Development Enclosure 1 01 Temperature sensor too high This SMS is sent to one or more target call numbers These can be for mobile phones or any fixed network subscribers When no SMS terminal has been registered at the fixed network socket a special service D1 Service provides a digital voice to read out the SMS by telephone Plea...

Page 15: ...le phone in T D1 network contract with service provider Mobile phone in Vodafone D2 network Mobile phone in e Plus network Mobile phone in O2 network Fixed network access registered at Deutsche Telekom AG SMS terminal ISDN unit at Deutsche Telekom Use default SMS centre 491710760000 Enter T D1 SMS Centre 491710760000 in mobile phone Only voice mail is possible At present only voice mail is possibl...

Page 16: ...lock or delay Unit 1 4 door 1 or 2 the unit number the separator and the door number must be written together Command DOOR Commands are case insensitive Single words can be separated with spaces with the exception of unit door b Outputs universal output power switch The CMC TC outputs can be activated and deactivated with the functions on and off Example SMS structure the following command switche...

Page 17: ...Function on or AUTO Climate unit 1 4 Command FAN Commands are case insensitive Single words can be separated with spaces Note For safety reasons the fan can not be deactivated by SMS d Resetting the alarm The command CLEAR can be used to confirm a pending alarm Commands are case insensitive Address Rittal GmbH Co KG Auf dem Stützelberg D 35726 Herborn Tel 49 2772 505 0 Fax 49 0 2772 505 2319 eMail...

Reviews: