3.
Dispose of the old tank in a proper and professional manner.
The fastening material is not included in the scope of delivery of the new
tank to be installed. Keep the fastening material if the new tank is not installed
directly after the removal of the old tank.
4.
L
WARNING! Danger of a faulty release!
Ensure that the blocking switch is set to "Agent disconnect [blocked]" before
installing a new tank.
5.
Install the new tank in the reverse order.
10.2.23 Concluding the inspection
● Put the system in service again according to the installation instructions in this
operating instruction.
● Check whether installation, as before, corresponds to the operation and installa-
tion conditions described in this operating instruction. In doing so, also check for
any possible openings in the cabinet which could perhaps obstruct successful
extinguishing.
10.3
Repairs after a release
10.3.1
Safety instructions for the tank change
L
WARNING
Danger for insufficiently qualified personnel!
Insufficiently qualified personnel is incapable of assessing the risk involved when
changing the tank and may cause severe or fatal injuries to themselves or others.
● The removal of an empty tank after a release and the installation of a new full
tank may only be performed by trained personnel using the materials and tools
intended for the task.
L
WARNING
Risk of death due to electric shock!
An imminent risk of death or severe physical injury due to electric shock exists if
live components are touched.
● Allow only qualified electricians to work on electrical components and the elec-
trical connection.
● Disconnect the system from the power supply:
– Remove the mains lead.
– Remove all electrical connections.
Repairs
Operating Instructions / DET-AC III Slave / 916007 / 05-2016 / en_US
70