Rittal 7320.790 Assembly And Operating Instructions Manual Download Page 4

3

 Device description

 

 

 
Automatic Door Control Unit 

 

EN

3

 

Device description 

3.1

 

Components and function description 

The following components belong to the complete 
Automatic Door Control system: 
 

Designation Order 

number 

Automatic Door Control Unit 

7320790 

Up to four Automatic Door Kits 

7320.792, or 7320.795, 
or 
7320.796  

Up to four Automatic Door keys 

7320.793 

Up to four TS 8 comfort handles 
with door opener function 

7320.794 

230 V / 24 V power pack with 
connection cable 

7320.725 
7200.210 

Fastening components in the 19" 
frame  

7320.440 

Fastening components in the 
enclosure frame  

7320.450 

 
The Automatic Door Control Unit performs the 
automatic opening of the rack doors should the 
cooling system of the racks fail or the rack doors 
need to be opened because of a smoke alarm and 
fire extinguishing so that the extinguishing gas 
entering the room can penetrate the racks. 
The Control Unit can activate as many as four 
Automatic Door Kits for the control of a maximum of 
four doors where the CMC-TC system can always 
control two doors using one CMC-TC channel. In 
addition, four normally-closed contacts are provided 
that can be assigned individually and connected to 
their manually initiating keys or other adequate 
switching elements. The Automatic Door Control Unit 
receives an identification so it can be automatically 
detected and set up by the CMC-TC system. 
The Automatic Door Kit provides the magnetic locking 
of the rack doors that is activated by the Automatic 
Door Control Unit. 
The holding magnets of the Automatic Door Kit in 
their active state are supplied with 24 V power. When 
the command for opening the door is issued, the 
Automatic Door Control Unit deactivates the magnets 
and the installed gas pressure dampers open the 
rack doors.  

3.1.1

 

Automatic Door Control Unit 

All inputs and outputs of the Automatic Door Control 
Unit are located on the rear. 
 
 
 
 
 
 
 
 
 
 
 

Legend 

-

 

I/O Door 1/2 or 3/4: 
Two RJ12 sockets for connection to an I/O unit 
of a CMC-TC system.  
The input 1/2 and input 3/4 activates Doors 1 
and 2, and Doors 3 and 4, respectively.  
The CMC-TC Processing Unit II can be used to 
define the appropriate combinations that cause 
the doors to be opened in an alarm situation.  
The Automatic Door Unit can be activated by a 
CMC-TC I/O unit in conjunction with a PU II or 
alternatively by a Basic CMC. 

-

 

Doors 1, 2, 3, 4: 

Four terminals for up to four door locks 
(Automatic Door Kits) 
The following assignment is recommended:  

Door 1: Rack 1 front door 
Door 2: Rack 1 rear door 
Door 3: Rack 2 front door 
Door 4: Rack 2 rear door 

-

 

Access – Input 1, 2, 3, 4: 

Four connections for Access Input components. 
A channel for the manual door opening is 
provided for each door. Automatic Door keys or 
TS 8 comfort handles with door opener function 
are connected to open the doors manually. 

-

 

Power: 
Connection for the 24 V power supply. 

Fig. 1:  Automatic Door Control Unit – rear trim panel 

Summary of Contents for 7320.790

Page 1: ...Assembly and operating instructions Automatic Door Control Unit 7320 790 A4069307IT74 ...

Page 2: ...er use 4 3 3 Dimensions 4 3 4 Scope of delivery 4 4 Assembly and installation 4 4 1 Assembly procedure 4 4 2 Installation 5 4 3 Installation procedure 5 4 3 1 Automatic Door Control Unit wiring 5 4 3 2 Installation guidelines 7 5 Commissioning and configuration 7 6 Operation 8 6 1 Display elements 8 6 2 Error messages 8 7 Fault and remedial action 8 8 Inspection and maintenance 8 8 1 Inspection 8 ...

Page 3: ...lso made to the operating and installation instructions for the CMC TC Processing Unit II and to the operating and installation instructions for the products listed in Section 3 1 All documents are contained on the CD ROM that accompanies the Processing Unit II The appropriate current version can be downloaded as PDF file from the RITTAL homepage http www rittal com 2 Safety instructions 2 1 Gener...

Page 4: ...ected and set up by the CMC TC system The Automatic Door Kit provides the magnetic locking of the rack doors that is activated by the Automatic Door Control Unit The holding magnets of the Automatic Door Kit in their active state are supplied with 24 V power When the command for opening the door is issued the Automatic Door Control Unit deactivates the magnets and the installed gas pressure damper...

Page 5: ...r Only the RITTAL Automatic Door Kit product may be activated 3 3 Dimensions W x H x D 136 mm x 44 mm x 129 mm 3 4 Scope of delivery 1 x Automatic Door Control Unit 1 x Assembly installation and operating instructions 2 x Nylon tape fastening 2 x RJ12 connection cable 4 Assembly and installation The Automatic Door Control Unit is installed in a RITTAL TS 8 rack in accordance with the procedure des...

Page 6: ...the CMC TC I O unit Connect the inputs from Door 1 2 and Door 3 4 with any free port of the CMC TC I O unit as shown in Fig 5 Use the provided RJ12 cable for this purpose Door 1 2 to Port 1 Door 3 4 to Port 2 Connection of the Automatic Door Control Unit to a Basic CMC or an LCP Plus Control Unit Connect the inputs from Door 1 2 and Door 3 4 with any free port on the Basic CMC as shown in Fig 6 Us...

Page 7: ...We recommend that the keys are placed where they are easily accessible provided there is no danger of them being activated inadvertently The maximum cable lengths must not be exceeded Connection of the 24 V power supply Note We recommend that the doors are monitored with access sensors 7320 530 because the Automatic Door Control Unit does not provide this function Fig 8 Connection of Automatic Doo...

Page 8: ...en Use the alarm configuring of the PU II or the Basic CMC to ensure that in this case all required protective measures are initiated for the installed server systems 4th Rack doors must not remain closed in a fault situation The connected controller must be configured so that the relevant alarms are signalled and manual intervention is possible To ensure the continuing correct functioning of the ...

Page 9: ...nd remedial action Malfunction Remedy Check the miniature fuses in the Automatic Door Control Unit Check the power supply of the Automatic Door Control Unit Check alarm messages and Combinations Doors cannot be closed Check the plugs at the Access Units inputs and the Doors outputs Doors remain closed in the Open system status Check the cabling in particular the connection cable from the Processin...

Page 10: ...n with Rittal up to 50 m UL approval CU to Basic CMC 10 m after consultation with Rittal up to 50 m UL approval CU to LCP Plus 10 m after consultation with Rittal up to 50 m UL approval 1 Not required because 24 V DC safety extra low voltage 11 Spare parts Miniature fuses type 5 x 20 mm 1 5 A slow The product will be replaced in case of an Automatic Door Control Unit defect 12 Wiring diagrams A Wo...

Page 11: ...tschrank Systeme Industrial Enclosures Coffrets et armoires électriques Kastsystemen Apparatskåpssystem Armadi per quadri di comando Sistemas de armarios Elektronik Aufbau Systeme Electronic Packaging Electronique Electronic Packaging Systems Electronic Packaging Contenitori per elettronica Sistemas para la electrónica Communication Systems Communication Systems Armoires outdoor Outdoor behuizinge...