![Rittal 3363 Series Assembly And Operating Instructions Manual Download Page 24](http://html.mh-extra.com/html/rittal/3363-series/3363-series_assembly-and-operating-instructions-manual_1465064024.webp)
24
Rittal air/water heat exchanger assembly instructions
9 Technical specifications
EN
9
Technical specifications
Fig. 31:
Rating plate (Technical specifications)
– Observe the mains connection data (voltage
and frequency) as per the rating plate.
– Observe the pre-fuse as per the specifications
on the rating plate.
Unit
Model No.
Basic controller, RAL 7035
–
3363.100
3363.104
3364.100
3364.104
e-Comfort controller, RAL 7035
–
3363.500
3363.504
3364.500
3364.504
Rated voltage
Volt
Hz
230, 1~,
50/60
Rated current
A
0.18/0.18
Pre-fuse T
A
4.0
Motor circuit-breaker
A
–
–
–
–
Transformer circuit-breaker
A
–
–
–
–
Miniature circuit-breaker or gG slow fuse (T)
–
䡲
䡲
䡲
䡲
Total cooling power Pc
to DIN 3168
L35 W10 400 l/h
kW
0.5
1.0
0.95
Power consumption Pel
to DIN 3168
kW
0.037/0.038
Water connection
–
1
/
2
˝ hose nozzle or G
3
/
8
˝ external thread
Air throughput per fan
(unimpeded air flow)
m
3
/h
290/345
Permissible pressure
bar
1…10
Operating temperature range
°C
+1…+70
Setting range
°C
+20…+55
Noise level
dB (A)
42
44
Protection category to IEC 60 529
–
IP 55
Dimensions (W x H x D)
mm
280 x 550 x 120
Weight
kg
8
9