5 Assembly and siting
EN
30
Rittal Liquid Cooling Package
At the fuse box, re-connect the thermally activated
switch for the (pair of) fans of which one fan has
been replaced.
Activate the newly installed fan in the software (see
section 8.2.4 "LCP configuration").
5.4
Install the optional display (3311.030)
In its delivered state, there is already a suitable open-
ing provided in the front door of the Liquid Cooling
Package for installing the optional display. This open-
ing is sealed from the inside by a trim panel.
Open the front door of the Liquid Cooling Package.
Loosen the attachments of the trim panel.
Remove the trim panel to the outside of the door.
Insert the fastening clamps with screws (fig. 35,
item 2) on the left and right of the display.
Fig. 35:
Preparing the graphic display
Key
1
Display with touch function
2
Fastening clamps
3
Connectors for display (4- and 12-pole)
4
Connection cable
Insert the connection cable (fig. 35, item 4) into the
bottom of the display (fig. 35, item 3).
Push the display into the cut-out from the outside un-
til it is in contact with the door (fig. 36, item 1) of the
Liquid Cooling Package at the front.
Tighten the two assembly screws (fig. 36, item 2)
from the inside.
Fig. 36:
Securing the graphic display
Key
1
Inner view of door, LCP Inline
2
Assembly screws
3
Strain relief, connection cable
4
Connection socket in LCP Inline
Connect the connection cable of the display to the
corresponding socket in the Liquid Cooling
Package (fig. 36, item 4).
Attach the strain relief (fig. 36, item 3) to the connec-
tion cable to prevent accidental damage to the ca-
ble e.g. when opening the door.
After connection, the following display will appear:
Fig. 37:
Display after connecting
You must select which version of the control unit is in-
stalled in your Liquid Cooling Package.
Open the front door of the Liquid Cooling Package.
Select the point "CMCII" if a device with a grey front
panel marked "CMC-TC" is installed.
Select the point "CMCIII" if a device with a grey front
panel marked "CMC III PU" is installed, as shown in
fig. 28.
2
4
2
3
1
Note:
If the control unit is incorrectly entered, oper-
ation via the display will not be possible. The
display will first need to be reset by the Rittal
service department.
4
2
2
1
3