5 Assembly and siting
EN
24
Rittal Liquid Cooling Package
5.2.4
Dismantle the server enclosure door
Before baying a Liquid Cooling Package, at least one
of the two server enclosure doors must be dismantled
so that the attachment points for the baying connec-
tors are accessible and are not covered by a door
edge.
Proceed as follows to dismantle a server enclosure
door:
Remove the sealing bungs from the four door hinges
with an appropriate tool (e.g. screwdriver).
Release and open the server enclosure door.
Loosen the hinge bolts from the four door hinges by
raising them with an appropriate tool (e.g. screw-
driver). Pull the bolts out of the hinge pin holding fix-
ture as far as they will go (see fig. 23, step A).
Begin with the lowest door hinge.
Fig. 23:
Removing a door hinge
Key
1
Door hinge
2
Hinge pin holding fixture
3
Hinge joint
4
Server enclosure door
Remove the server enclosure door (fig. 23, step B).
5.2.5
Fit the rear adaptor on the LCP Inline
In order to achieve an even finish for the LCP Inline
and the server enclosure fronts at the rear, a corre-
sponding enclosure extension may be installed on the
LCP Inline (see section 15 "Accessories").
Dismantle the rear door of the LCP Inline in the same
way as the server enclosure (see section 5.2.4 "Dis-
mantle the server enclosure door").
Dismantle the hinge pin holding fixtures (fig. 24,
item 1) and corresponding fixing components
(fig. 24, item 2) from the LCP Inline and reassemble
at the rear of the adaptor in the same way.
Fig. 24:
Assembly components on the Liquid Cooling
Package – rear view
Key
1
Hinge pin holding fixture
2
Fixing component
Attach the adaptor (fig. 25, item 2) to the rear open-
ing of the LCP Inline using four of the supplied
screws (fig. 25, item 1) each on the left and right.
Note:
It is only necessary to dismantle a server en-
closure door when the Liquid Cooling
Package is to be bayed onto a previously
erected server enclosure.
Otherwise, this work is not necessary.
If the Liquid Cooling Package is to be in-
stalled together with a new server enclosure,
proceed according to the enclosure's as-
sembly instructions and bay the Liquid
Cooling Package onto the server enclosure
before assembling the server enclosure
doors.
1
2
1
3
A
A
B
4
Note:
Support the server enclosure door so that it
will not fall as the door hinges are loosened.
If necessary, work with a second person.
2
1