![Rittal 3237 Series Assembly And Operating Instructions Manual Download Page 14](http://html.mh-extra.com/html/rittal/3237-series/3237-series_assembly-and-operating-instructions-manual_1465028014.webp)
14
Rittal fan-and-filter unit assembly and operating instructions
Technical specifications
EN
Unit
Model No.
Fan-and-filter unit
RAL 7035
3243.100 3243.110 3244.100 3244.110 3244.140 3245.500 3245.510
Fan-and-filter unit
RAL 9005
3243.108 3243.118 3244.108 3244.118 –
3245.508 3245.518
EMC fan-and-filter unit
RAL 7035
3243.600 –
3244.600 –
–
3245.600 –
Rated operating voltage
V
Hz
230, 1~,
50/60
115, 1~,
50/60
230, 1~,
50/60
115, 1~,
50/60
400, 3~,
50/60
460, 3~,
60
200…240
1~,
50/60
100…130
1~,
50/60
Rated current max.
A
0.37/0.39 0.78/0.8
0.43/0.6
0.9/1.25
0.17/0.21 1.33
2.1
Power consumption
W
70/87
75/90
95/135
100/145
93/140
165
165
Pre-fuse T
A
4
6
4
6
Motor
circuit
breaker
4
6
Dimensions
Width (B1) x height (H1)
mm
323 x 323
Required mounting cut-out
(B2 x H2)
mm
292 x 292
Depth (T1)
mm
25
Max. installation depth (T2) mm
118.5
130.5
130.5
Air throughput, unimped-
ed airflow with standard
fleece filter mat
m³/h
540/590
700/770
890
Air throughput, unimpeded
airflow with pleated filter
m³/h
625/716
855/905
1125
Air throughput with outlet
filter, including standard
fleece filter mat
m³/h
1 x 3243.20x: 405/460 1 x 3243.20x: 485/520
1 x 3243.20x: 630
2 x 3243.20x: 475/520 2 x 3243.20x: 570/630
2 x 3243.20x: 770
Air throughput with outlet
filter including pleated filter
m³/h
1 x 3243.20x: 550/630 1 x 3243.20x: 700/730
1 x 3243.20x: 930
2 x 3243.20x: 600/683 2 x 3243.20x: 800/840
2 x 3243.20x: 1060
Outlet filter RAL 7035
3243.200
Outlet filter RAL 9005
3243.208
EMC outlet filter
RAL 7035
3243.060
Fan
Diagonal, capacitor motor
Diagonal,
rotary
current
motor
Diagonal, EC motor
Noise pressure level
dB (A)
59/61
65/66
67/70
72
Operating temperature
°C
-30…+55
Storage temperature
°C
-30…+70
Protection category (to
IEC 60 529)
IP 54 standard
IP 55 with pleated filter
IP 56 with hose-proof hood
IP 51 standard
IP 52 with pleated filter
IP 56 with hose-proof
hood
Tab. 6:
Technical specifications
Technical modifications reserved.