Maintenance, repair

 

 

 
Assembly and operating instructions Tangential fans 

 
 

EN 

professionally connected and operating 
properly.

 

Connection data complies with the 
specifications on the type plate. 

 

Start-up: 

Switch fan on in accordance with switched 
state and local conditions. 

Check: Smoothness of motor operation, 

Direction of rotation/direction of 
conveyance when looking at the motor 
(see also Fig. 1, 2) 

 

 

Figure 1: Direction of rotation: right 

 

 

Figure 2: Direction of rotation: left

 

9  Maintenance, repair 

 

Wear safety shoes and gloves for handling! 

 

Due to the selection of bearings with "lifetime 
lubrication" (special grease), the cross flow fan 
is maintenance-free. Once the grease 
consumption period has expired (for standard 
applications, approx. 20-30,000 hrs., for direct 
current motors with collector, approx. 5-10,000 
hrs.), it is necessary to replace the bearings. 

 

Take note of abnormal operating noise! 

 

Replace the bearings at the end of the grease-
consumption period, or if they should become 
damaged. Ask for our Maintenance Guide or 
contact our Repair Department (special tools 
may be required!). 

 

Replace bearings only with original parts. 

 

In the event of any other damage (e.g. motor 
damage or damage to the fan cylinder), please 
contact our Repair Department. 

 

On 1~ motors, condenser rating can decrease 
with time. Life expectancy approx. 30,000 hrs. 
per DIN EN 60252. 

 

Outdoor fans: If a fan is stationary for long 
periods in a humid atmosphere, it should be 
switched ON for minimum of two hours 
every month to remove any moisture that 
may have condensed within the motor. 

 

Allow maintenance work to be carried out by 
trained specialists only. 

 

For all repair and maintenance work: 

Observe  the safety and labour regulations 
(DIN EN 50 110, IEC 364). 

Fan cylinder has come to a standstill! 

Open the electrical circuit and secure 
against being switched back on. 

No maintenance work at running fan! 

 

After dismantling and reinstalling an impeller, 
the entire rotating unit must be rebalanced in 
accordance with DIN ISO 1940,-1. 

 

Keep the airways of the fan free-  danger 
because of objects dropping out! 

 

Do not bend fan cylinder or blades! 

10  Cleaning 

 

 

Regular inspection, and cleaning is necessary 
to prevent 

imbalance due to ingress of dirt. 

 

Clean the fans`s flow area. 

 

Keep fan air way open; clean the fan cylinder 
with a brush when necessary. 

 

Watch out for vibration free motion. 

 

Maintenance interval in accordance with the 
degree of contamination of the impeller! 

 

You can clean the entire fan with a moist cloth. 

Summary of Contents for 3144.000

Page 1: ...Tangential fans for 482 6 mm 19 Assembly and operating instructions 3144 000 3145 000 ...

Page 2: ...cation 3 2 Safety instructions 3 3 Note on the ErP directive 3 4 Transport storage 3 5 Mounting 4 6 Electrical connection 4 7 Operating conditions 4 8 Start up 4 9 Maintenance repair 5 10 Cleaning 5 11 Disposal recycling 6 12 Dimensions 7 ...

Page 3: ... motor circuit wiring diagram a tripping device is required For motors without a temperature monitor a motor cut out switch is to be used for P1 750 W P2 500 W Blocking or braking the fan by say pushing objects into it is forbidden This leads to heated surfaces and damage to the impeller It is not possible to exclude a residual risk due to incorrect use malfunction or force majeure The designer or...

Page 4: ...d Attention Connection directly to the mains supply results in a damage of the motor Electrical connections must not be short circuited since there is danger of de magnetization Do not touch the connection ends of the motor when it has been switched off and is coming to a stop Electrical shock due to the effect of the generator 7 Operating conditions Do not operate the fan in an explosive atmosphe...

Page 5: ...t of any other damage e g motor damage or damage to the fan cylinder please contact our Repair Department On 1 motors condenser rating can decrease with time Life expectancy approx 30 000 hrs per DIN EN 60252 Outdoor fans If a fan is stationary for long periods in a humid atmosphere it should be switched ON for minimum of two hours every month to remove any moisture that may have condensed within ...

Page 6: ...e ventilator is running If water enters the motor Dry off the motor winding before using it again Replace motor ball bearings Wet cleaning under voltage may lead to an electric hock danger to life 11 Disposal recycling Our products are manufactured in compliance with valid international standards and regulations If you have any questions about how to use our products or if you are planning special...

Page 7: ...Dimensions 12 Dimensions ...

Page 8: ......

Reviews: