Dok‑Commander

®

 

Installation/Service/Owner's Manual

 Rite‑Hite

®

6 Publication:

 AMEN00070 2020-01-30

INSTALLATION

 DANGER

When working with electrical or electronic 

controls, make sure that power source  

has been locked out and tagged according  

to approved local electrical codes.
Post safety warnings and barricade work area,  

at dock level and at ground level, to prevent 

unauthorized use of dock position.

A qualified electrician should install wiring in 

accordance with local electrical codes.

NOTICE

Mounting surfaces vary Use mounting hardware  

(supplied by others) with necessary strength for 

secure attachment of assembly to door frame or 

inside face of building wall

NOTICE

The safest location for conduit is at the bottom of the 

control box Failure to install conduit at the bottom of 

the control box may void the warranty
Be extremely careful when drilling conduit holes into 

control box Drilling too deeply or allowing debris to 

fall into electrical components may cause severe 

equipment damage or component failure 

DO NOT

 turn control box upside down when drilling 

holes Holes on top of control box may allow dust  

and moisture to enter control box 

If rigid conduit is installed, bonding must be 

maintained between conduit connections by using 

ground bushings and a jumper wire

All field wiring to be minimum 60°/75°C copper wire, 

insulated sufficiently for highest voltage that will be 

encountered

NOTE:

Cover screw torque is 10in-lbs [113 Nm] for all 

applications

Standard Applications

1  Install the control box on a wall adjacent to the 

overhead door at approximately 48in – 50in  

[1219mm – 1270mm] above the floor level Make sure 

to mount where control box is clear of obstructions

2  Drill a hole for the power supply conduit (supplied 

by others) in the bottom of the control box All holes 

drilled through the control box must be through the 

bottom of the box to maintain NEMA4X rating

Temperature Controlled Applications

In addition to the standard application instructions follow 

these guidelines:
• 

If conduit could fill with water, install a drip leg 

 

(supplied by others)

•  Seal the conduit in any location where the conduit 

transitions temperature zones that may produce 

condensation

•  Install spacers (supplied by others) between the 

enclosure and the wall to provide temperature insulation 

and air flow.

Summary of Contents for Dok-Commander

Page 1: ...atic 13 Wiring Corner Vu Leveler Vu 17 Wiring Pedestrian Vu 18 Wiring Approach Vu 20 Wiring Outside Light Box 21 Wiring Safe T Pit Sensor 22 OPERATION Best Practice Sequence 24 Supply Chain Integrity...

Page 2: ...8307956 8443474 8464384 8464846 8465245 8497761 8499897 8544130 8547234 8590087 8590673 8616826 8657551 8662535 8678736 8690087 8905198 9010501 9096170 9096397 9126775 9139384 9145273 9150367 9174811...

Page 3: ...gram P M P As part of this service your local Rite Hite representative will do all routine maintenance lubrication and adjustments 6 Dock equipment that is structurally damaged shall be removed from s...

Page 4: ...OTE A note is used to inform you of important installation operation or maintenance information Lockout Procedure Barricade work area and post safety warnings Power supply and control must Be disconne...

Page 5: ...Rite Hite Installation Service Owner s Manual Dok Commander Publication AMEN00070 2020 01 30 5 FEATURES D C B A A Control Box B Outside Lights C Inside Sign D Outside Sign Figure 1...

Page 6: ...down when drilling holes Holes on top of control box may allow dust and moisture to enter control box If rigid conduit is installed bonding must be maintained between conduit connections by using grou...

Page 7: ...Rite Hite Installation Service Owner s Manual Dok Commander Publication AMEN00070 2020 01 30 7 ELECTRICAL 115V Schematic Dok Comm_115V_Schematic 1 200121 pdf...

Page 8: ...Dok Commander Installation Service Owner s Manual Rite Hite 8 Publication AMEN00070 2020 01 30 ELECTRICAL 115V Schematic Continued Dok Comm_115V_Schematic 2 200121 pdf...

Page 9: ...Rite Hite Installation Service Owner s Manual Dok Commander Publication AMEN00070 2020 01 30 9 ELECTRICAL 115V Schematic Continued Dok Comm_115V_Schematic 3 pdf...

Page 10: ...Dok Commander Installation Service Owner s Manual Rite Hite 10 Publication AMEN00070 2020 01 30 ELECTRICAL 230V Schematic Dok Comm_230V_Schematic 1 200121 pdf...

Page 11: ...Rite Hite Installation Service Owner s Manual Dok Commander Publication AMEN00070 2020 01 30 11 ELECTRICAL 230V Schematic Continued Dok Comm_230V_Schematic 2 200121 pdf...

Page 12: ...Dok Commander Installation Service Owner s Manual Rite Hite 12 Publication AMEN00070 2020 01 30 ELECTRICAL 230V Schematic Continued Dok Comm_230V_Schematic 3 pdf...

Page 13: ...Rite Hite Installation Service Owner s Manual Dok Commander Publication AMEN00070 2020 01 30 13 ELECTRICAL 3 Phase Schematic Dok Comm_3PH_Schematic 1 200121 pdf...

Page 14: ...Dok Commander Installation Service Owner s Manual Rite Hite 14 Publication AMEN00070 2020 01 30 ELECTRICAL 3 Phase Schematic Continued Dok Comm_3PH_Schematic 2 200121 pdf...

Page 15: ...Rite Hite Installation Service Owner s Manual Dok Commander Publication AMEN00070 2020 01 30 15 ELECTRICAL 3 Phase Schematic Continued Dok Comm_3PH_Schematic 3 pdf...

Page 16: ...Dok Commander Installation Service Owner s Manual Rite Hite 16 Publication AMEN00070 2020 01 30 ELECTRICAL 3 Phase Schematic Continued Dok Comm_3PH_Schematic 4 pdf...

Page 17: ...Rite Hite Installation Service Owner s Manual Dok Commander Publication AMEN00070 2020 01 30 17 ELECTRICAL Wiring Corner Vu Leveler Vu RIte Vu Schematic 200121 pdf Figure 2...

Page 18: ...Dok Commander Installation Service Owner s Manual Rite Hite 18 Publication AMEN00070 2020 01 30 ELECTRICAL Wiring Pedestrian Vu Leveler Stored to Unlock Restraint RIte Vu Schematic 200121 pdf Figure 3...

Page 19: ...te Installation Service Owner s Manual Dok Commander Publication AMEN00070 2020 01 30 19 ELECTRICAL Wiring Pedestrian Vu Continued Leveler Stored to Close Overhead Door RIte Vu Schematic 200121 pdf Fi...

Page 20: ...Dok Commander Installation Service Owner s Manual Rite Hite 20 Publication AMEN00070 2020 01 30 ELECTRICAL Wiring Approach Vu Appr Vu_Approach Vu for Manuals 170520 pdf Figure 5...

Page 21: ...side Light Box To Controls Red Lamp Green Lamp Light Box Cover 40 Wire 12 VDC Red Light OSR Term for Gen2 OSR Term for URC 40 Term for SDL Green Light 41 Wire 12 VDC Green Light OSG Term for Gen2 OSG...

Page 22: ...D13 LD11 LD39 LD20 LD40 LD37 LD42 LD48 LD10 LD49 LD46 LD44 LD43 LD41 LD38 OSG OSR LVLRCNTR MWLACTR MWLALM UDITCOUT GLTITL CVURD CVUGN LVURD LVUGN PVUALM PVULT AUTOITC UDITCIN KYDHORNOVRD CTRLPWR OSLTI...

Page 23: ...M COM COM PVUDET PVUEN SW2 SW1 LD35 SD K1 K2 DIAG SW2 SW6 RES O L FACTORY JUMPERS 18GA WH BL J14 1 J14 2 J14 3 J14 5 RESET LD51 PROG LD7 J2 12VDC DETAIL A RESTRAINT POWER CKT BD LOWER RIGHT CORNER 12V...

Page 24: ...o green 3 Dock operator opens the overhead door Leveler controls are now active 4 Dock operator lowers leveler into trailer 5 Truck is ready to be loaded 6 When loading operation is complete operator...

Page 25: ...backed into loading dock and is parked firmly against dock bumpers Hook rotates from STORED position to entrap R I G If horn sounds go to FAULT State from LOCKING State if not go to Restraint LOCKED...

Page 26: ...nside light turns red and horn sounds press LOCK button to secure R I G WARNING Visually confirm Dok Lok barrier obstructs R I G of trailer being serviced before operating dock leveler Green Alerts op...

Page 27: ...NLOCKING State Hook cannot rotate to STORED position Hook could be caught on R I G or another part of trailer Verify trailer is parked firmly against dock bumpers If not press LOCK to entrap R I G hav...

Page 28: ...ange Procedure Reasons for program change Restraint change Adding or removing green light interlock with either the leveler or overhead door Adding or removing Control Power Keyed Horn Override Coded...

Page 29: ...uid Stop cycling once Dok Lok barrier travels up and down without hesitation 5 To exit FILL MODE Press DIAGNOSTIC button or Press no buttons for 5 minutes or Cycle power Fill Mode Input Outputs Chart...

Page 30: ...Dok Commander Installation Service Owner s Manual Rite Hite 30 Publication AMEN00070 2020 01 30 PARTS Dok Commander Bottom Left Side Right Side...

Page 31: ...Rite Hite Installation Service Owner s Manual Dok Commander Publication AMEN00070 2020 01 30 31 PARTS Dok Commander Continued Dok Comm_Enclosure_Assembly 2020 01 21 pdf...

Page 32: ...ap 145118 Motor Overload Relay 127199 QTY DESCRIPTION PART 217 1 Transformer 500VA 230 460V 146025 Transformer 500VA 575V 146026 Transformer 1000VA 230 460V 146027 Transformer 1000VA 575V 146028 Trans...

Page 33: ...0V 3PH incoming power 103229 QTY DESCRIPTION PART 507 2 2A fuse CC Dual element time delay 500VA transformer and 575V incoming power 66019 2 5A fuse CC Dual element time delay 500VA transformer and 46...

Page 34: ...142101 703 6 Screw round head 6 32 0 25 length 133366 704 6 Lock washer 6 51826 705 7 Standoff Male Female 6 32 0 75 length 142100 706 4 Standoff Male Female 6 32 1 625 length 142101 707 7 Screw round...

Page 35: ...62THK Rubber 145920 7 4 Nut 1 14UNS Plastic 145776 8 1 Ped VU Enclosure Sensor Light BLUE Left 150027 9 1 Ped VU Enclosure Sensor Light BLUE Right 150028 10 2 Ped VU LED Light Assembly 150026 11 1 Ped...

Page 36: ...2 5 4 5 5 3 3 3 4 5 4 2 3 5 6 9 2 4 4 6 3 6 5 6 2 15 1 1 2 5 4 5 5 3 3 3 4 5 1 Pedestrian Vu 2 15 1 5 4 5 4 7 8 2 15 1 1 2 5 4 5 5 3 3 3 4 5 7 8 8 7 QTY DESCRIPTION PART 1 2 Mounting Bracket Assembly...

Page 37: ...2 SCR 250 20X 625 CAP FLAT SST 150717 5 1 APPROACH VU CABLE ASSY 18 2 PVC RCPT 92L 150795 6 1 APPROACH VU WARNING SIGN 150669 7 1 TRUCK SENSOR RAVE CBL 26FT 150688 8 1 TRUCK SENSOR BRACKET 6 188L 1506...

Page 38: ...9623 2 2 CAMERA WEATHERPROOF INP 12VDC LENS 120DEG WH IP68 149622 3 1 JUNCTION BOX 4X4X2 N4 2HOLE 540DIA 156252 4 2 CORD GRIP 11 25 CORD DOME BK 25NPT 156649 5 1 BRACKET EXTENDED Lok Vu 156240 6 12 SC...

Page 39: ...TAINER 66067 11 1 TERMINAL END BARRIER 65599 12 4 TERMINAL MARKER 65601 13 2 TERMINAL BLOCK CENTER JUMPER 2P W4 113590 14 4 TERMINAL BLOSK 600V 30A 22 10AWG IEC 65476 15 1 TIMER RELAY 05S 60HR INPUT 1...

Page 40: ...e or normal wear and tear of the Product iii failure to follow Rite Hite s instructions for installation failure to operate the Product within the Product s rated capacities and or specified design pa...

Reviews: