Rishabh Rish Eine Operating Manual Download Page 10

9

 

X

1000

L1

L2

L3

V

 

X

1000

L1

L2

L3

V

RMS 

TRUE

Pressing the “    ” key accepts the present value  and advances 

to the “Auto scroll” selection menu(See Section 3.1.6) for 3V. 

In case of Eine  V it will exit from set up menu. 

Pressing the “     ” key will enter the “Potential transformer 
Secondary Value Most significant digit  Selection. 

Pressing the “     ” key will scroll the value of the most significant digit. 

position and advances the cursor to the next Less significant digit.

When the least significant digit has been set, pressing  the “    ” key will advance to the  

 “Potential transformer secondary value confirmation” screen.For Eine 3V minimum PT secondary 

Pressing the “    ” key accepts the present value at the cursor 

can set is 100V(L-L).For Eine  V If Pt secondary is less than 57.5 V(L-N) then meter shows 

  “Err” and PT secondary is set to 57.5 V(L-N). 

  

Note: For Eine V decimal point is fixed at third digit position.

Potential Transformer Secondary Value Confirmation

This screen will only appear following an edit of the Potential 
Transformer Secondary Value.
If the set value is to be corrected, pressing the “     ” key will 
return to the “Potential Transformer Secondary Value Edit” stage. 
Pressing the “     ” key sets the value  and then advance to the 

“Auto scroll” Selection menu in case of Eine  -3V and in case of

Eine -1V it will exit from set up menu.

 

X

1000

L1

L2

L3

V

 

X

1000

L1

L2

L3

V

RMS 

TRUE

L1

L2

L3

L1

L2

L3

 

X

1000

A

 

X

1000

A

3.1.5 Current Transformer Secondary Value (for 3A & A)

This  screen is used to set Current transformer secondary 
value. "1"for CT secondary 1A and "5" for CT secondary 5A. 
pressing "  " down key accepts the present value and 
advances to the Auto Scroll  option in case of Eine -3A and 
for Eine -A it will exit from setup and goes to measurement 
screen.

Summary of Contents for Rish Eine

Page 1: ...DMAN 00IM 0637 Rev_B 12 2017 OPERATING MANUAL Rish Eine Size 48 x 96 Size 96 x 96...

Page 2: ...ment Reading Screens 3 4 Installation 4 1 EMC Installation Requirements 4 2 Case Dimensions and Panel Cut out 4 3 Wiring Programming 3 1 Set Up Screens 4 4 Auxiliary Supply 4 5 Fusing 4 6 Earth Ground...

Page 3: ...00 L1 L2 L3 V X1000 L1 L2 L3 V RMS TRUE X1000 L1 L2 L3 V X1000 L1 L2 L3 A 2 Eine 3A RMS TRUE X1000 L1 L2 L3 V RISH Ein X1000 V 3 Eine V RMS TRUE X1000 L1 L2 L3 V X1000 A 4 Eine A RMS TRUE phase or sin...

Page 4: ...l with Eine 3A models Measured Parameters Unit of measurement 2 Measurement Reading Screen In normal operation the user is presented with the measurement reading screens These screens may be scrolled...

Page 5: ...L3 V X1000 L1 L2 L3 V X1000 L1 L2 L3 V value displayed after Sys flashing on Display RMS TRUE RMS TRUE X1000 L1 L2 L3 V X1000 L1 L2 L3 A B Screens of EINE 3A Models Screen 1 L1 Current Screen 2 System...

Page 6: ...ed to set the system type System type 3 for 3 phase 3 wire 4 for 3 phase 4 wire system advances to the system type confirmation menu Pressing the down key accepts the present value and case of 3A valu...

Page 7: ...tion 3 1 4 for Eine 3V and V Pressing the key will enter the Potential transformer Primary Value Multiplier Selection Eine 3V Initially the multiplier must be selected Pressing the Key will move the d...

Page 8: ...decimal point position and enters into Current Transformer Primary value edit to with Annunciation of x1000 It indicates the value in kA X1000 L1 L2 L3 V X1000 L1 L2 L3 V RMS TRUE X1000 L1 L2 L3 V X1...

Page 9: ...present to identify the scaling of the number until the cursor position coincides with the steady decimal point position At this stage the decimal point will be flashing Current Transformer Primary Va...

Page 10: ...hen meter shows Err and PT secondary is set to 57 5 V L N Note For Eine V decimal point is fixed at third digit position Potential Transformer Secondary Value Confirmation This screen will only appear...

Page 11: ...Eine A and goes to measurement screen 3 1 6 Selection of Auto Scrolling or fixed Screen only for 3V 3A Pressing the key will enter into Screen selection Confirmation screen Pressing the key will scro...

Page 12: ...ounting Swivel screw As the front of the enclosure conforms to IP 50 additional protection to the panel may be obtained by the use of an optional panel The EINE V A should be mounted in a reasonably s...

Page 13: ...uppression components such as ferrite absorbers line filters etc in the event that RF fields cause problems Note It is good practice to install sensitive electronic instruments that are performing cri...

Page 14: ...ons and Panel Cut Out 4 2 1 for 96X96 models 92mm 0 8 92mm 0 8 Panel Cutout Front Display Area 96mm 96 mm 27 mm 6 mm 35 mm MAX PANEL THICKNESS 0 18 5mm 4 2 2 for 48X96 models Mounting Position Install...

Page 15: ...cal regulations 2 2 Terminal for inputs will accept up to 4mm 12 AWG or 2 5mm 12AWG Standard Note 1 It is recommended to use wire with lug for connection with meter 2 For disconnecting the device a sw...

Page 16: ...PHASE 3 WIRE UNBALANCED LOAD DIGITAL PANEL METER External Aux N L N AUX SUPPLY 13 14 L N AUX SUPPLY 13 14 L N AUX SUPPLY 13 14 Connections For EINE V 96X96 SINGLE PHASE 2 WIRE DIGITAL PANEL METER Ext...

Page 17: ...DIGITAL METERING SYSTEM WITH EXTERNAL AUX 3 PHASE 3 WIRE UNBALANCED LOAD DIGITAL METERING SYSTEM WITH EXTERNAL AUX Connections for EINE 3A 48 x 96mm L1 L2 1 3 L O A D 6 7 9 10 L3 3 PHASE 4 WIRE UNBAL...

Page 18: ...Applicable for single phase only System PT Primary values 3 V 100VL L to 999kV L L Programmable onsite V 57 5VL N to 999kV L N Programmable onsite 0 4 VA approx per phase for 600VLN Connections For EI...

Page 19: ...nt Voltage 2 X Rated Value for 1 Second repeated 4 X Rated Value for 1 Second repeated 10 times at 10 second interval 5 times at 5 min interval Operating Measuring Ranges Voltage Range 10 120 of Rated...

Page 20: ...st Safety 2 III Pollution Degree Installation Category High Voltage Test 2 2 kV AC 50 Hz for 1 minute 10V m min Level 3 industrial low level Electromagnetic radiation environment Current Range 10 100...

Page 21: ...er installations and is intended to describe the correct method of installation for this product However Manufacturer has no control over the field condition which influence product installation Incid...