Rish EM 3490 SS Installation & Operating Instruction Download Page 1

                    Single Phase Energy Meter

Installation  & Operating Instructions

EM 

3490 SS

1.  Introduction

Ultra high brightness LED display.

Down

Up

2.  Measurement Reading Screen

In normal operation the user is presented with active  energy measurement screen.  

Screen 1 : Active Energy  (kWh)

When x1000 LED glows the energy is displayed in mega watt.

Section

Contents

1.

Introduction

2.

Measurement Reading Screen 

4. 

Programming

4.1 Password Protection
4.2 Menu selection

4.2.1   System Parameter selection screen

4.2.2   Communication Parameter selection screen

4.2.3   Reset Parameter selection screen

4.2.4   Relay Output parameter selection screen

4.2.5   Quit screen

4.2.1.1   Potential transformer Primary value
4.2.1.2   Potential transformer secondary value
4.2.1.3   Current  transformer Primary value
4.2.1.4   Energy Display on modbus
4.2.1.5   Energy Digit Rollover(reset) count

4.2.2.1   Address Setting
4.2.2.2   RS 485 Baud rate
4.2.2.3   RS 485 Parity selection

10. 

Specification

Installation

8.1  EMC Installation Requirements
8.2  Case Dimensions and Panel Cut-out
8.3  Wiring 
8.4  Auxiliary Supply
8.5  Fusing
8.6  Earth / Ground Connections

9. 

11. 

Connection for Optional Pulse output / RS 485 

8. 

Phaser Diagram

4.2.3.1   Resetting Parameter 

4.2.4.1  Pulse Duration (width) selection

15000251_Rev.C - 12/ 08

7. 

6. 

RS 485 (Modbus) Output

5. 

Relay Output (Optional).

4.2.4.2  Pulse rate divisor

The instrument is  a panel mounted 96 x 96mm DIN Quadratic energy 

meter. It accumulates Active energy, in single phase network.

The instrument also measures AC Voltage, AC Current, Frequency, 

Power, Power factor, Phase Angle, Apparent Energy which can be accessed via 
Modbus. All voltage & Current measurements are True RMS upto 15th harmonic.

Meter can be configured & Programmed at site 
for the following :
PT Primary, PT Secondary, CT Primary, Modbus 
Settings & Pulse output settings.

The front panel has two push buttons through 
which the user can reset the energy & configure 
the product.
The front panel has Impulse red led, flashing at 
rate proportional to measured power.
Its impulse rate is 3600impulses/kWh.
 

6.1 User assignable Modbus Register

 Network Wiring

5.1 Pulse Output 

1

x1000 

3600 Imp/KWh

kWh

x1000 

kWh

VON IREV

3.  Phase Indications

“LED Von glowing”

Voltage Phase present

x1000 

kWh

VON IREV

“LED Von off”

Voltage phase absent

x1000 

kWh

VON IREV

Measured Parameters

System Voltage

System Current
Frequency

Active  Energy  

Units of measurement

Volts

Amps

Hz

 Wh

TABLE 1:

Apparent Energy  

Active Power 
Reactive Power 
Apparent Power  
Power Factor 
Phase Angle 

Kwatts

KVAr
KVA

Degree

VAh

Display Parameter

Active  Energy  (8 digit counter)

kWh

Modbus Parameter

Active energy is displayed in 8 digit counter with auto ranging feature. Below given table
describes auto ranging with minimum resolution of energy measured in perticular range.

Display Format

X1000 LED

Minimum resolution

99.999999
999.99999
9999.9999
99999.999
999999.99
9999999.9
99999999
999999.99
9999999.9

99999999

OFF
OFF
OFF

OFF
OFF
OFF

OFF

ON
ON

ON

1 miliWatt

10 miliWatt

100 miliWatt
1 Watt

10 Watt
100 Watt

1 kiloWatt
10 kiloWatt
100 kiloWatt

1 MegaWatt

Maximum Active energy count reached is 99999999 MegaWatt after this counter 

rollovers to zero and measurement starts from first range.

3.

Phase Indications

Impulse led on front panel can be used to cross check the energy calibration on site.  

Its nominal impulse rate is 3600 impulses / kWh.

2

VON IREV

3600 Imp/KWh

3600 Imp/KWh

3600 Imp/KWh

“LED IREV glowing”

Current out of phase w.r.t voltage .

x1000 

kWh

VON IREV

“LED IREV off”

Current in phase w.r.t voltage

x1000 

kWh

VON IREV

3600 Imp/KWh

3600 Imp/KWh

 
 

                   

 

 
 

SEL

 (Select) 

 

: UP KEY 

: DOWN  KEY 

 

 

(Select Relay Parameter)

 

 

quit 

(Exit Menu)

 

Exit 

from setup Parameter to Main

 

Display 

        

rESEt

 

(

Reset

 

Parameter)

 

 

non

 

(

No

 

Parameter), 

 

E

 (Energy), 

 

 

 

 

 

 

“Down” key

SEriAL 

 

(

Serial Communication

)

 

 

Add

 

(Modbus Address) 

br

 

         (Baud Rate)

 

Pr

 

         (Parity Bits)

 

 

cd 

 (PassWord)

 

SEL

 

(

Select System

 

Parameter)

(Sec 4.2.2)

 

         

 

 

 

         

UP 

(

PT Primary

         

US 

(

PT Secondary

 

 

 

A

 

(Sec 4.2.1.1)

 Setup Parameter Screen

(Sec 4.2.5)

Parameter

(Sec 4.2.2.1)

(Sec 4.2.2.2)

(Sec 4.2.2.3)

(Sec 4.2.3)

  SYS 

(Sec 4.2.1)

SEL 

SEL 

(Sec 4.2.4)

rELAY

SEL 

dur

 

( Relay Pulse Duration)

 

rAt

 

         (Pulse Rate Divisor)

 

 

 

 

(Sec 4.2.4.1)

(Sec 4.2.4.2)

AP

(CT Primary)

(Sec 4.2.1.3)

(Sec 4.2.1.2)

(Sec 4.2.3.1)

Summary of Contents for EM 3490 SS

Page 1: ...rtional to measured power Its impulse rate is 3600impulses kWh 6 1 User assignable Modbus Register Network Wiring 5 1 Pulse Output 1 x1000 3600 Imp KWh kWh x1000 kWh VON IREV 3 Phase Indications LED Von glowing Voltage Phase present x1000 kWh VON IREV LED Von off Voltage phase absent x1000 kWh VON IREV Measured Parameters System Voltage System Current Frequency Active Energy Units of measurement V...

Page 2: ...er see section 4 2 3 1 Option selection screen see section 4 2 4 This menu screen is used to select the different communication parameters like Address selection RS485 Parity selection Pressing the Up key allows the user to set different Pressing the down key will advance to Reset parameter Communication parameters see section 4 2 3 RS485 baud rate Screen Pressing the Up key will allow the user to...

Page 3: ...gy at the moment of resetting energy will become zero Reset Energy Confirmation Pressing the Down key will re enter the Reset option mode Pressing Up key will jump back to the menu selection screen see section 4 2 6 4 2 4 Relay output menu 4 2 4 1 Pulse Duration Selection This screen applies only to the Pulsed output mode of the relay This screen allows the user to set Relay energisation time in m...

Page 4: ...gh Byte Data Register2 Low Byte AE Hex CRC Low Data register 2 Low Byte Least significant 8 bits of Data register 2 of the parameter requested Table 4 3 X register addresses measured parameters Address Register Parameter No Parameter Modbus Start Address Hex High Byte Low Byte High Byte High Byte 30001 1 Volts 1 00 0 30007 4 Current 1 00 6 30013 7 W1 00 C 30019 10 VA1 00 12 30025 13 VAR1 00 18 300...

Page 5: ...egister 0x200 to 0x213 see Table 10 Address Register Parameter Number Assignable Register 02 High Byte Low Byte Table 10 User Assignable mapping register 4X registers Example Assigning parameter to user assignable registers To access the voltage 3X address 0x0000 and Power Factor 3X address 0x001E through user assignable register assign these addresses to 4x register Table 10 0x0200 and 0x0201 res...

Page 6: ...connections should be grounded in accordance with local regulations 8 3 Wiring Input connections are made directly to screw type terminals with indirect wire pressure Numbering is clearly marked in the plastic moulding Choice of cable should meet local regulations Terminal for both Current and Voltage 2 inputs will accept upto 3mm x 2 diameter cables Note It is recommended to use wire with lug for...

Page 7: ...roduct However organization has no control over the field conditions which influence product installation It is the user s responsibility to determine the suitability of the installation method in the user s field conditions Organization only obligations are those in organization standard Conditions of Sale for this product and in no case will organization be liable for any other incidental indire...

Reviews: