Programs for charging batteries
1. Universal program - UNI, Universal, used for unrecognized types of batteries
2. Standard Pb battery - STA, Standard, used for older types of Pb batteries
3. Pb Ca / Ca battery - CaCaWET is used for starting maintenance free batteries
4. Pb with acid swab - AGM, used for hermetic AGM batteries
5. Pb with GEL electrolyte -GEL, used for hermetic GEL batteries
6. Kristal Pb-LC, SIPBE, Lead Crystal, used to lead Si crystal battery
7. U-I, continuous charging current, U and I set
8. Pb Traction battery-TRA, Traction, used for fueling traction batteries
Operational Problems
Error
Cause
Solution
The charger is connected to the mains,
power switch is ON -LED is not
flashing, the screen does not work
-there is no mains voltage 230Vac
-
Ensure supply
voltage 230Vac
The battery is connected but the
charger is not charging, all LEDs
blinking indicates »no battery
connected«
- too low voltage on the battery (
battery is totally discharge)
-
Select from the
menu ‘BURST’
mode
Red LED illuminates and the is an
Error on LCD screen
-device has overheated due to high
ambient temperatures
-Hepatic fan (Error)
decrease temp. of
environment
-service intervention
-clean fan