Before final connection of the water heater purge gas, hot water and 
cold water supply lines. Swarf in either the gas or water supplies may 
cause damage.

Turn on gas and cold water supplies.  

Test for water leaks and gas escapes near the unit.  

Isolate gas supply. Remove test point screw located on the gas inlet 
connection and attach pressure gauge.

Turn the power 'on' at the power point socket and turn on gas. 

Open all available hot water taps. (

CAUTION:

  Ensure building 

occupants do not have access to hot water outlets during this 
procedure.) 

Operate ALL other gas appliances at their maximum gas rate, in 
accordance with manufacturers instructions.

With all gas appliances in operation at maximum gas rate, check the 
inlet gas pressure. If the pressure is lower, the gas supply is inadequate 
and the appliance will not operate to specification. It is the Installers 
responsibility to check the gas meter, service regulator and pipe work 
for correct operation/sizing and rectify as required. 

Note

  that the gas 

regulator on the appliance is electronically controlled and factory pre-
set. Under normal circumstances it 

DOES NOT

 need adjustment during 

installation.

Close hot water taps including the shower.

Inspect and clean the strainer located on the cold water inlet 
connection. This procedure may need to be repeated to ensure the 
strainer remains clear, especially on new installations.

If Temperature Controllers are fitted, it is necessary to test their 
operation through the complete range of functions. (Refer to the 'How to 
use your Water Heater' booklet.)  

Confirm the hot water delivery temperature(s) using a thermometer. If 
controllers are fitted, ensure temperatures exceeding 50˚ C cannot be 
selected on bathroom or ensuite controllers.

After testing is completed, explain to the householder the functions and 
operation of the water heater and temperature controllers (if fitted).

TESTING AND COMMISSIONING

1. 

2.

3. 

4. 

5. 

6.

7. 

8.
 

9. 

10. 

11. 

12.

13.

AC weatherproof external earthed power point is required within 1500 mm 
of the appliance.

The appliance weighs approx. 

A

, depending on the wall on which it is to be 

mounted must be capable of supporting it and associated pipework. Ensure 
that suitable fixing screws or bolts are used to secure the appliance to the 
wall. Bracket and fixing hole locations are shown overleaf.

The top bracket has a keyhole slot so that the appliance can be positioned 
by  hanging it on one screw, then the other screws can be secured. After 
determining the most suitable position, fix the appliance to the wall.

Connect hot and cold water and gas pipes. Approved valves MUST BE 
FITTED to both the cold / hot water pipes and the gas inlet.
In areas where the water pressure is over 1000 kPa, a pressure limiting 
valve must also be fitted. the gas connection is 

B

, the cold water inlet and 

hot water outlet connections are 

C

. Locations are shown overleaf.

The appliance range can use up to 

D

 of gas.

IF THE GAS PIPE SIZE IS INSUFFICIENT, THE CUSTOMER WILL NOT 
GET THE FULL PERFORMANCE BENEFIT.

  An approved isolation valve 

MUST BE FITTED to the gas inlet. Connection size is 

B

. This is 

NOT

  an 

indication of the size of pipe required. Check the data plate for gas inlet.

This appliance is not suitable for use as a pool heater.

Never connect an earth wire to gas supply line.

This appliance is for 

OUTDOOR

 use.

INSTALLATION-GENERAL

REU-VRM2632WC / VRM3237WC

POSITIONING

This external model is an externally mounted, power flued appliance.

IT MUST ONLY BE FITTED OUTSIDE THE BUILDING.

When determining a suitable position for the appliance, the length of hot 
water pipe runs should be taken into consideration. In principle, the 
appliance should be as close as possible to the most often used taps, or in 
a central location between taps, showers etc.

See diagram overleaf for position of gas, water and power connections.

The location of the flue terminal must comply with the clearances shown in 
the following diagram.

Min. clearances 

(mm) 

Ref. 

Item 

Fan assisted 

Below eaves, balconies and other projections: 

·

Appliances over 50 MJ/h input 

300 

From the ground, above a balcony or other surface † 

300 

From a return wall or external corner † 

300 

From a gas meter (M)

1000 

From an electricity meter or fuse box (P) 

500 

From a drain pipe or soil pipe 

75 

Horizontally from any building structure † or obstruction facing a 
terminal  

500 

From any other flue terminal, cowl, or combustion air intake †

300 

Horizontally from an openable window, door, non-mechanical air inlet, or any other opening 
into a building with the exception of sub-floor ventilation: 

·

Appliances up to 200 MJ/h input 

300 

·

Appliances over 200 MJ/h input up to 250 MJ/h input †

500 

·

Appliances over 250 MJ/h input †

1500 

·

All fan-assisted flue appliances, in the direction of discharge 

1500 

From a mechanical air inlet, including a spa blower 

1000 

Vertically below an openable window, non-mechanical air inlet, or any other opening into a 
building with the exception of sub-floor ventilation: 

·

Space heaters up to 50 MJ/h input 

150 

·

Other appliances up to 50 MJ/h input 

500 

·

Appliances over 50 MJ/h input and up to 150 MJ/h input 

1000 

·

Appliances over 150 MJ/h input 

1500 

g

openable

window

door

M

P

g

T

b

d

d

e

e

See note 2

h

h

a

h

j

j

j

n

k

k

c

c

f

T = Flue terminal
I  = Mechanical air inlet

areas for flue terminals

T

T

I

 

Shading indicates prohibited

M = Gas meter
P = Electricity meter or fuse box

A

 (the appliance weights)

19kg

VRM2632WC

R3/4(20mm)

R3/4(20mm)

199MJ/h

29kg

VRM3237WC

R3/4(20mm)

R3/4(20mm)

250MJ/h

B

 (gas inlet)

C

 (cold / hot water pipes)

D

 (input)

1

† Unless appliance is certified for closer installation

note 1.  All distance are measured to the nearest part of the terminal.
note 2.  Prohibited Area below electricity meter or fuse box extends to
             ground level.

DIMENSIONS (VRM2632WC)

DIMENSIONS (VRM3237WC)

2