Step 3: Set the O2 at Minimum Input
1.
While still in service mode (as described in the previous step), use the scroll wheel to adjust to
0%
.
2.
Press
OK
.
3.
The boiler is now at minimum input.
4.
After the boiler has run for approximately one minute, the O2 value displayed on the
combustion analyzer should read a value as shown in the
Nominal O2 Percentages
table (see
section
Step 2: Set the O2 at Maximum Input
).
Example: If maximum input value is 4.8% on natural gas, then minimum input value should be
between 5.2% and 6.4%.
If the values do not match, adjust the parameters by following the steps in the
Adjust O2
Percentages
section.
5.
When adjustments are complete, place the plug back into the flue gas test port.
6.
On the controller, press and hold the
Back
button until the Home screen appears in the
window.
This section is required only if it is necessary to adjust O2 percentages.
Rotate the screw on the gas valve assembly slowly. Allow the boiler to operate for approximately
one minute for the O2 value to stabilize. Repeat until you reach the levels shown in the
Nominal
O2 Percentages
table (see section
Step 2: Set the O2 at Maximum Input
).
•
Rotate counter
-
clockwise to decrease the O2 percentage
•
Rotate clockwise to increase the O2 percentage
Adjust O2 Percentages
INCREASE O2
DECREASE O2
Counter
-
Clockwise
Clockwise
THIS SECTION IS INTENDED FOR THE INSTALLER
Summary of Contents for M Series
Page 96: ...96 Rinnai M Series Condensing Boiler Combi Manual Heat Exchanger ...
Page 98: ...98 Rinnai M Series Condensing Boiler Combi Manual Hydraulic Parts Pipes ...
Page 101: ...Rinnai M Series Condensing Boiler Combi Manual 101 Electrical Components Solo Only ...
Page 113: ...Rinnai M Series Condensing Boiler Combi Manual 113 ...
Page 114: ...114 Rinnai M Series Condensing Boiler Combi Manual ...
Page 122: ...122 Rinnai M Series Condensing Boiler Combi Manual 800000063 03 6 2019 ...