
Installation & Servicing Instructions Rinnai E-Series
36
6.7.4
Recommended vent/air intake terminal position
Terminals should be positioned as to avoid products of combustion entering
openings into buildings or other vents.
Maintain 12” of clearance above the highest anticipated snow level or grade
or, whichever is greater. Please refer to your local codes for the snow level in
your area.
The termination shall be at least 4 feet (1,220 mm) for the US and 6 feet (1,830
mm) for Canada distance from electric meters, gas meters, regulators and
relief equipment. (for room air application only)
Horizontal vent systems should always be installed sloping towards the
boiler (min. 21 mm/m, 1/4 “/ feet), in order to avoid condensate retaining in
the vent system. With the condensate running back to the boiler the risk of
ice forming at the terminal is reduced.
The whole route of the vent system must be installed upwards, never
downwards, completely nor partly.
Place pipe supports every 4 feet (1219 mm) of horizontal run, beginning with
the support near the boiler to prevent movement in fittings and allow boiler
to be free from any strain or weight on boiler or fittings.
The terminal should be located where dispersal of combustion products is
not impeded and with due regard for the damage or discolouration that might
occur to building products in the vicinity (see fig 14 and 15).
In certain weather conditions condensation may also accumulate on the
outside of the air inlet pipe. Such conditions must be considered and where
necessary insulation of the inlet pipe may be required.
In cold and/or humid weather water vapor may condense on leaving the vent
terminal. The effect of such ‘water condensation’ must be considered.
The terminal must be located in a place not likely to cause a nuisance.
Use the Instructions of the Rinnai venting system for installation and service.
Cellular or Foam core PVC is not permitted for use with the boiler.
NOTICE
i
!
CAUTION
!
CAUTION
NOTICE
i
NOTICE
i
NOTICE
i
NOTICE
i
Approval codes for installation of venting system
table 7
Item Description
Flue Material
United States
PVC Schedule 40
ANSI/ASTM D1785
PVC - DWV
ANSI/ASTM D2665
CPVC Schedule 40 ANSI/ASTM F441
PVC
ANSI/ASTM D2564
CPVC
ANSI/ASTM F493
Item Description
Flue Material
Manufacturer
Approval code
US/CAN
Flue system
Stainless steel vent
systems
Stainless Steel
Ubbink
Rolux Condensing
Vent System
Plastic Vent System
PPS
Ubbink
Rolux Condensing
Vent System
Plastic Vent System
PVC/CPVC
IPEX
ULC S636
System 636
Stainless steel vent
systems
Stainless Steel
Simpson Dura-Vent
FastNSeal Flex
UL1738 Flexible liner
Saf-T Vent SC
Saf-T Vent EZ Seal
Stainless steel vent
systems
Stainless Steel
Heat Fab
concentric
UL1738 twin pipe
Approval Codes for Installation
Canada
Plastic Vent and/or air
pipes and fittings
ULC S636
Plastic Pipe cement and
primer
NOTICE
i
Summary of Contents for E110CN
Page 18: ...Installation Servicing Instructions Rinnai E Series 18 Boiler basic piping fig 5 ...
Page 45: ...Installation Servicing Instructions Rinnai E Series 45 electrical ladder diagram figure 21a ...
Page 99: ...Installation Servicing Instructions Rinnai E Series 99 ...
Page 119: ...Installation Servicing Instructions Rinnai E Series 119 ...
Page 120: ......