Rinnai
22
Commercial Controller OM
DDSOLAR REGISTER
When setting up your controls monitoring interface it is necessary to know the registry information to select the
data you wish to monitor.
All parameters are READ-ONLY.
When using MODBUS protocol please note:
•
MODBUS Data is Big-Endian
•
Temperatures are provided in fixed point
•
MODBUS Coils and Discrete inputs are not used
When using BACNET protocol please note:
• The device object contains parameters such as
version info, serial number, etc
•
Temperatures are in floating point
Refer to the tables below for registers and data points.
INPUT REGISTER INFORMATION
Category
Input
Register Function
Size (16
bit words) Value
BACNET
Product
information
30002
Product Set
1
DDSTAT
Included elsewhere
30004
Major Version
1
Firmware Major version
In Device Info
30007
Serial Number
2
In Device Info
Temperatures
30011
Tank temperature
1
decidegrees (e.g. 260 = 26.0 deg C) Analog Input
30012
Collector thermistor temp.
1
decidegrees (e.g. 260 = 26.0 deg C) Analog Input
Pump Status
30021
Pump 1 Run Timer
2
Number of hours
Analog Input
30023
Pump 2 Run Timer
2
Number of hours
Analog Input
30031
Pump 1 state
1
on, off
Binary Output
30032
Pump 2 state
1
on, off
Binary Output
Fault Status
30041
Fault state
1
true, false
Binary Value
30042
Pump 1 condition
1
e.g. working or failed
Binary Value
30043
Pump 2 condition
1
e.g. working or failed
Binary Value
30044
Tank thermistor condition
1
e.g. working, open, short
Multi State Value
30045
Collector thermistor condition
1
e.g. working, open, short
Multi State Value
30049
No Solar Gain Fault
1
true, false
Binary Value
HOLDING REGISTER INFORMATION
Category
Holding
Register Function
Size (16
bit words) Value
BACNET
Product
information
40001
Product Set
1
DDSTAT
Multi State Value
Specific
Configuration
40011
BMS relay normally open
1
open, closed
Binary Value
40022
Pump swap period
1
12 hours, 24 hours, 0 if not alternating Analog Value
40023
Pumps alternating
1
true, false
Multi State Value
40024
Interrupt Mode
1
interrupting, not interrupting
Multi State Value
40025
Interrupt Stop Time Seconds
1
seconds
Analog Value
40026
Interrupt Run Time Minutes
1
minutes
Analog Value
40044
DDSOLAR Frost Mode enabled
1
true, false
Binary Value
Thermistor
Configuration
40031
Tank thermistor enabled
1
true, false
Binary Value
40032
Collector thermistor enabled
1
true, false
Binary Value
DDSOLAR OPERATION