Heat Exchanger Overheat
Overheat switch is tripped.
Measure the resistance of the Overheat
Switch.*
Check the heat exchanger surface for hot
spots which may indicate blockage due
to scale buildup.
Ensure the boiler pump is not locked up.
Ensure that all of the valves in the CH
circuit are open.
Ensure the boiler and CH circuit does not
have a freezing condition.
The surface of the heat exchanger may
turn to a black color as stainless steel is
tempered even in normal conditions.
This does not indicate an abnormal
condition.
Check for damage on the exhaust, seal,
and venting.
Venturi Control
Venturi operation error.
Ensure the venturi motor is operating
correctly.*
Replace the gas valve assembly.
High Outgoing Temperature
Safety shutdown because DHW outgoing
temperature is too hot.
Check sensor wiring for damage of
outgoing thermistor.
Measure resistance of outgoing
thermistor.*
Ensure the gas valve has no damage and
the orifice is installed correctly.
Replace the gas valve assembly.
Venturi Blockage
Check the venturi and silencer for
blockage.
Before resetting this error, check if the
condensate drain is block and if the
venting is connected properly.
Electrical Grounding
Secondary circuit ground fault.
Check all electrical components for
electrical short.
Condensate Pump (Accessory)
Boiler will operate for 60 seconds.
Confirm wire connections and
harnesses are good.
Ensure the condensate reservoir is
empty and condensate pump is
operational.
Inlet Thermistor
Check sensor wiring for damage.
Measure the resistance of the sensor.
Replace if necessary.
Supply Thermistor
Check sensor wiring for damage.
Clean the surface of the sensor.
Measure the resistance of the sensor.
Check the return thermistor.
Replace if necessary.
Outgoing Thermistor
Check sensor wiring for damage.
Clean sensor of any scale buildup
present.
Measure the resistance of the sensor.
Replace if necessary.
Heat Exchanger Thermistor
Check sensor wiring for damage.
Measure the resistance of the sensor.
Replace if necessary.
Freeze Protection Thermistor
Check sensor wiring for damage.
Measure the resistance of the sensor.
Replace if necessary.
Exhaust Thermistor
Check sensor wiring for damage.
Clean the surface of the sensor.
Measure the resistance of the sensor.
Check the return thermistor.
Replace if necessary.
Return Thermistor
Check sensor wiring for damage.
Measure the resistance of the sensor.
Replace if necessary.
Outdoor Thermistor
Ensure that DIP switch 1 is set to the
appropriate position.
Check sensor wiring for damage.
Measure the resistance of the sensor.
Replace if necessary.
Pressure Sensor
Check sensor wiring for damage.
Measure the voltage of the sensor.
Replace if necessary.
* See “Electrical Diagnostics” on Technical Data Sheet located on inside front cover of boiler.
Summary of Contents for COMBI i060C
Page 124: ...124 Rinnai I Series Condensing Boiler Combi Manual ...
Page 125: ...Rinnai I Series Condensing Boiler Combi Manual 125 ...
Page 134: ...134 Rinnai I Series Condensing Boiler Combi Manual ...
Page 135: ...Rinnai I Series Condensing Boiler Combi Manual 135 ...
Page 136: ...136 Rinnai I Series Condensing Boiler Combi Manual 800000111 3 2019 ...