Canadian Air Handler Installation and Operation Manual
11
Values shown in following tables may vary depending on the static pressure of the duct system.
Coil Entering
Water
Temperature
(°F)
Flow Rate
(GPM)
Heat Fan Ratio (Air Flow)
Coil Pressure
Drop (PSI)
50%
(800CFM)
Temperature
Differential (°F)
75%
(1200 CFM)
Temperature
Differential (°F)
100%
(1600 CFM)
Temperature
Differential (°F)
120
2
23,100
27
27,500
21
35,400
21
1.42
3
26,000
30
33,600
26
40,300
23
2.36
4
28,000
32
37,500
29
43,900
25
4.38
140
2
33,700
39
42,000
32
47,500
28
1.41
3
37,300
43
48,300
37
56,500
33
2.34
4
38,400
44
54,000
42
62,700
36
4.38
160
2
43,100
50
54,800
42
62,600
36
1.41
3
48,000
56
62,100
48
73,100
42
2.34
4
51,200
59
66,200
51
80,000
46
4.38
Engine
Entering Water
Temperature (°F)
50%
(800CFM)
75%
(1200 CFM)
100%
(1600 CFM)
SENSEI
120
26,600
34,700
41,400
I
-
Series
28,500
38,400
44,600
SENSEI
140
37,500
49,100
57,400
I
-
Series
39,100
54,900
64,100
SENSEI
160
47,600
61,600
72,400
I
-
Series
52,000
67,500
81,700
Maximum Equivalent Piping
Distance (ft)
Flow (GPM)
Sensei
I
-
Series
2
200 ft
200 ft
3
150 ft
150 ft
With 20ft or less equivalent piping