16
|
Arriva/Evolve flue installation guide: 10726-I 09-21
Sideways flueing
The sideways flue installation can be run along the left or right hand side of an
internal wall behind the heater. When considering the location of the heater ensure
that the flue path is free from obstructions such as studs, noggins, wiring, joists etc.
Flue length
Total flue length can be 7.5 m—the elbow component of the ASPKIT03/EVOKIT03 is counted as
a 90° bend. If bends need to be included to offset a stud, noggin etc., the flue length can be up to
5.5 m and contain two 90° bends (two ESBEND kits).
Steps for creating sideways flueing
1. Lubricate all inner pipe o-rings with the silicone grease provided.
2. Join the flue transition and condensate together ensuring the condensate outlet points
upwards. Even though the condensate is not actually connected in this flue arrangement, the
condensate component serves as a transition piece between the transition casting and the
ESPIPE900. The transition component must not be connected directly to the ESPIPE900,
which is plastic, due to the heat of the flue gases.
3. Fit lengths of ESPIPE900 as required. Allow for a 2° continuous fall from the heater connection
point to the wall terminal to drain condensate.
4. Create the wall penetration. The minimum diameter is 80 mm to non-combustible surfaces
such as brick, and 100 mm to combustible surfaces such as plaster. Allow for a continuous 2°
fall from the fire to the wall terminal.
5. Create the wall terminal, refer p. 21.
6. Secure joints between flue components through the outer pipes with screws and secure the
entire flue system using the wall straps
supplied.
Remember to consider how the wall straps will be secured to the frame—additional packing will be
required depending on where the wall straps are positioned.
IMPORTANT
2° fall to terminal to
drain condensate
ASPKIT03/EVOKIT03
(DO NOT remove cap)
Additional packing
for wall straps
Condensate (should be
capped or sealed)
Air hose secured
with cable tie
Evolve model showing position of various flue components in a sideways flue installation