Figure 22:
Circulating Pump 115V Troubleshooting - Flow Sensor (FS) Configuration
FINISH
YES
NO
CHECK
FOR LOOSE OR BROKEN
WIRES
CHECK
VOLTS ACROSS 'PUMP'
CONNECTIONS ON PCB
VAC =
115V +/-
NO
YES
PROBLEM(S) WITH 24V TO PCB
-
GO TO
24V
TROUBLESHOOTING CHART
PUMP AMP
DRAW NORMAL
NO
CHECK CAPACITOR;
IF
DEFECTIVE
REPLACE
COMPONENT
AND RE-CHECK
AMP DRAW
YES
RETURN TO
START
NO
PUMP AMP
DRAW NORMAL
CHECK PUMP
MOTOR;
IF
DEFECTIVE
REPLACE
COMPONENT
AND RE-CHECK
AMP DRAW
NO
CONNECT PUMP DIRECTLY TO
115 VAC POWER SUPPLY
PUMP MOTOR
ENERGIZED
(1) RECTIFY
WIRING PROBLEM(S)
(2) CHECK MOTOR AND
CAPACITOR;
IF DEFECTIVE,
REPLACE
FAULTY COMPONENT(S)
RETURN TO
START
NO
YES
YES
YES
CONTACT
TECH.
SUPPORT
RECONNECT WIRES
AND
CONFIRM THAT WIRING IS AS
PER WIRING DIAGRAMS
SYSTEM
WORKING
SYSTEM
WORKING
ADJUST THERMOSTAT
SET
TEMPERATURE HIGHER THAN
ROOM TEMPERATURE
PUMP
ENERGIZED
YES
NO
CHECK CAPACITOR;
IF
DEFECTIVE,
REPLACE
COMPONENT
AND RE-CHECK
AMP DRAW
PUMP AMP
DRAW NORMAL
YES
NO
REPLACE
PUMP
MOTOR
AND
RETURN TO
START
WITH DOOR SWITCH CLOSED
(SET SYSTEM IN HEATING MODE
-CALL FOR HEAT)
START
IS 'LED' ON
RAPID 'LED' FLASH
GO TO
RFH START-UP &
'LED' TROUBLESHOOTING
STEADY 'LED' FLASH
YES
YES
NO
PUMP
ENERGIZED
YES
NO
PUMP AMP
DRAW NORMAL
YES
NO