4 How to Use
4-5. How to wire
- 27 -
GD-D58 Series
<Specifications of Terminal Plate>
Specifications of terminal plate
Rated voltage: 250 VAC
Rated
current:
12
A
However, it depends on the cables to be used.
Connection conditions
Cables: 0.25 - 2.5 mm
2
Bare wire length: 8 - 9 mm
Connecting tool: Dedicated handling lever (accessory) or driver (edge 3.5 x 0.5 mm)
Compatible bar terminal
For a bar terminal, the following items are available.
Bar terminal (ferrule): Model 216 Series (manufactured by WAGO)
Crimping tool: Model VarioCrimp 4 (206-204) (manufactured by WAGO)
<How to Connect to Terminal Plate>
When cables are connected to the connectors, use the dedicated lever or a flathead screwdriver to do it
as shown below.
CAUTION
The specified bare wire length must be observed when the wire insulation is peeled off.
Improper clamping of the wire due to a shorter bare wire length may cause defective electric
conduction or heating.
Catching the wire insulation due to a shorter bare wire length may cause defective electric
conduction or heating.
Exposing the wire due to a longer bare wire length may cause defective insulation or a short
circuit.
Be careful not to break up the wire. If the wire is broken up when inserted to the terminal, this
may cause defective insulation or heating.
CAUTION
A bar terminal of the specified model must be used. Using other bar terminals invalidates the
warranty of the performance.
CAUTION
The appropriate tools must be used.
In principle, one wire can be connected to one wiring hole.
When the wire is inserted into the driver slot by mistake, it does not contact the conductive part.
This may cause defective electric conduction or heating. When the wire is inserted under the
spring by mistake, it does not contact the conductive part. This may cause defective electric
conduction or heating.
8 - 9 mm