background image

7.4 

Discharging the condensate from system with vacuum (Picture 10)

■ 

Downstream siphon prevents the suction of air from the atmosphere (H

Siphon

). 

■ 

The installation depth (H

Install

) enables the increase of the condensate column, which overcomes the vacuum.

■ 

The geodesic height (H

Geod

) and siphon height (H

Siphon

) are equal (H

Geod

 = H

Siphon

). They depend on the vacuum value and  

the required fl ow rate (quantity of condensate).

■ 

Per meter the pressure increases 0.1 bar because of the geodesic height (H

Geod

).

X

Condensate

Siphon

Air

H

Install

H

Geod

H

Siphon

Condensate 
column

Condensate

1064-N
1068-N

Gas +      Con-

densate

System with 

Vacuum

Picture 10

Conformity assessment

The pressure equipment is in accordance with the Pressure Vessel Directive 2014/68/EU, Article 4, subsection 3 and there-
fore bears no CE mark. A detailed declaration of conformity assessment according to PED is available as separate document. 
Please request if necessary, if not attached.