5.5.13 Up/Down counter
Fashion:
Classic:
Short description
An input pulse increments or decrements an internal value, depending on the parameter setting. The
output is set or reset when a configured threshold is reached. The direction of count can be changed with
a signal at input Dir
Connection
Description
Input
R
You reset the output and the internal
counter value to zero with a signal at input
R (Reset).
Input
Cnt
This function counts the 0 to 1 transitions
at input Cnt. It does not count 1 to 0
transitions.
Input
Dir
Input Dir (Direction) determines the
direction of count:
Dir = 0: Up
Dir = 1: Down
Parameter
On:
On threshold
Value range: 0...99999999
Off:
Off threshold
Value range: 0...99999999
StartVal:
Initial value from which to begin
counting either down or up.
Retentivity
set (on) = the status is
retentive in memory.
Output
Q
Q is set and reset according to the actual
value at Cnt and the set thresholds.
Parameter
Summary of Contents for ELC-12AC-R-N
Page 1: ...Applied to ELC PR series Ver 3 0 Programmable Relay User s Manual Rievtech Electronic Co Ltd...
Page 27: ...27 PR 14 and PR 18 series 1 PR 18 CPU 2 PR E extension PR 24 series...
Page 31: ...31 AC type digital inputs Analog Inputs DC 0 10V Analog inputs current Inputs 0 20mA...
Page 40: ...40...
Page 120: ...120 C Analog input value of CPU and extensions D Analog output value of CPU and extensions...
Page 121: ...121 E F digital flag status F AF analog flag value...
Page 122: ...122 G M status H AM value...
Page 221: ...221 7 Click Install button to install Program is being installed...
Page 250: ...250...
Page 256: ...256 You can read the parameters from the PLC...
Page 258: ...258...
Page 267: ...267 TCP Sever 192 168 0 227 port 8004 is ok TCP Sever 192 168 0 227 port 8005 is ok...
Page 268: ...268 TCP Sever 192 168 0 227 port 8006 is ok TCP Sever 192 168 0 227 port 8007 is ok...
Page 269: ...269 TCP Sever 192 168 0 227 port 8008 is ok TCP Sever 192 168 0 227 port 8009 is ok...
Page 290: ...290 Slave1 IP 192 168 0 101 TCP server port 8001 Slave2 IP 192 168 0 102 TCP server port 8002...
Page 317: ...317 Network settings You can view the network parameters in such table...
Page 331: ...331 B005 Read the I1 IA status from the slave1 to the F11 F20 of the master Setting as follows...
Page 332: ...332 B006 Read the I1 IA status from the slave2 to the F21 F30 of the master Setting as follows...
Page 346: ...346 7 4 2 The scheme of xLogic The circuit diagram of industry gate...
Page 353: ...353 7 6 2 The scheme of xLogic Components K1 main contactor...
Page 357: ...357 4 cursors Cursor key Type 1x MODBUS code 02 C1 C4 256 259 BIT R...
Page 392: ...392...