background image

WIRELESS FLOOD 

DETECTOR

«

STZ-RK

»

Installation Guide

1 Product Overview

1.1 Wireless flood detector «STZ-RK» (hereinafter, the Detector) is intended 

for detecting leaks of water, water solutions, other  current-conducting 
non-aggressive liquids and generating an alarm message via a two-way 
communication by the «Rielta-Contact-R» protocol. The Detector is intended to 
operate as a component of any control panel (hereinafter, CP) supporting the 
wireless exchange protocol «Rielta-Contact-R».

1.2 The Detector comprises a Signal Processing Module (SPM) and flood sensors 

«DZ-3V» (FS). The SPM has two connecting blocks for FS hooking up: «Loop 1» 
and «Loop 2». Not more than two FSs can be hooked up in parallel to each loop.

1.3 The Detector is able to operate in two-loop or single-loop mode. The last 

mode presumes the «Loop 2» status is ignored. The operation mode choosing 
is available during the detector logging in the CP.

1.4 Radio signals are exchanged within the 433.05 to 434.79 MHz frequency 

range. The transmitter output power does not exceed 10 mW.

1.5 Two operating frequencies: main and reserve are used for the wireless data 

exchange. The Detector switches over reserve operating frequency automatically.

1.6 Radio exchange sessions are initiated by the Detector at a preset 

frequency. The frequency settings are 10, 15, 30 sec, 1, 5, 10 min, chosen in 
the process of the the binding procedure. The SPM transmits alarm messages 
to the CP immediately.

1.7 Independent power supply of the Detector is provided by power supply 

batteries placed inside it’s case: the main one (CR123A) and the backup one 

(CR2032). If the main power supply battery is low, the Detector switches over 
to the backup power supply source automatically.

1.8 The Detector generates and transmits the following messages:
- «Norm in Loop 1» – under the absence of liquid between the FS contacts 

plugged to «Loop 1»;

- «Norm in Loop 2» – under the absence of liquid between the FS contacts 

plugged to «Loop 2»;

- «Alarm in Loop 1» – under the presence of liquid between the FS contacts 

plugged to «Loop 1»;

- «Alarm in Loop 2» – under the presence of liquid between the FS contacts 

plugged to «Loop 2»;

- «Tamper» – under the case tampering or SPM removal from the installation 

surface;

- «Failure in Loop 1» under the break of communication bus SPM – FS, 

hooked to «Loop 1»;

- «Failure in Loop 2» under the break of communication bus SPM – FS, 

hooked to «Loop 2»;

- «Main Power Supply Low Battery» – under the main power supply battery 

voltage drop over 2.8

-0.4

 V;

- «Backup Power Supply Low Battery» – under the backup power supply 

battery voltage drop over 2.8

-0.4

 V.

1.9 The Detector is designed to operate continuously, around the clock.
1.10 The Detector provides immunity to electromagnetic interference.
1.11 The level of industrial interference generated by the Detector does not 

exceed the norms established for the technical equipment operated in residential 
buildings or connected to power mains of residential buildings.

2 Features 

Table 1

Features

Value

Assumed number of FSs in an alarm loop circuit, max

2 pcs.

Length of each alarm loop between the FS and the 

SPM, max

5 m

Weight:

- SPM, max

- FS, max

0.1 kg

0.03 kg

Operating temperature

minus 20 … +50 °C

Case dimensions:

SPM, max

FS, max

112 x 41 x 32 mm

65 x 22 x 16 mm

IP rating:

- SPM 

- FS

IP30

IP67

Average service life

8 years

Battery life under normal climate conditions and speci-

fied broadcast period not more

 

than 60 sec, not less:

- main power supply battery

- backup power supply battery 

60 months

2 months

Figure 2 – Flood Sensor «DZ-3V»

5 Sound and LED Indication

The Detector has the following indication modes:
- «Binding» procedure LED indication (procedure of logging in the CP);
- LED indication of the mode «Identification» – lights up by sending relevant 

command from CP and remains active during 15 min or until the case is opened;

- LED indication of the Detector state – lights up and remains unchanged for 

15 min after the case is closed under conditions:

- other LED indication types (except the sound alarm) absence;
- alarm «Tamper» message is not generated during this time period;
- the Detector state indication is ON upon the receipt of relevant command 

from the CP.

LED indicator modes are listed in the Тable 3.
Тable 3

The Detector Mode

Indication

Note

Binding procedure 

finished

LED lighting red for 2 – 3 sec

«Binding» mode

LED blinking green with 

0.25 sec period 

The Detector 

logging in the CP 

in single-channel 

mode 

LED blinking green with 1 sec

period

The Detector 

logging in the CP 

in double-channel 

mode 

«Identification»

Alternate LED red and green 

alternate blinking

on command from 

the CP

«Alarm in Channel 1»

«Alarm in Channel 2» 

Single-shot LED lights up red 

for 4 sec *

State indication 

is on and 

«Identification» 

indication is off

Generation

«Alarm in Channel 1» 

«Alarm in Channel 2» 

Sound alarm dual switching **

State sound 

indication is on

Fallback recovery

«Alarm in Channel 1» 

«Alarm in Channel 2»

Single-shot sound alarm 

switching **

3 Scope of Delivery

Each Detector unit package contains the items Table 2.
Table 2

Name

Qty

Signal processing module «STZ-RK SPM»
Flood sensor «DZ-3V»

CR123A lithium power supply battery

CR2032 lithium power supply battery
Set of accessories:
Screw 3-3x30.016

Nylon wall plug NAT 5x25 SORMAT

Wireless flood detector «STZ-RK». Installation Guide

1 pc.

2 pcs.

1 pc.
1 pc.

6 pcs.
6 pcs.

1 copy

4 Design of the Detector

The external appearance of the SPM is shown in Figure 1.
The SPM comprises a base, a cover and a printed circuit board (PCB). 
The front side of PCB (1) comprises: tamper (2), LED indicator (3), connecting 

blocks (4) for connecting the FSs, main power supply battery holder (5), «RESET» 
contacts (7), sounder (8), antenna (9). The backup power supply battery holder 
and the tamper are located on the reverse side of the PCB. The PCB is fixed in 
the base of the case by a latch (6) and grips on the reverse side of the base.

The case of the FS is watertight, it is 

provided with sensing contacts and a 

 

1.5 m cable for connecting to the SPM. 
The FS is designed to be fastened to both 
horizontal and vertical surfaces.

Figure 1 – The Base with the PCB

The «DZ-3V» layout is shown in Figure 2.

Red

Black

WA1

XP2

HL1

GB1

+

XP1

1

2

3

4

9

6

5

7

8

«DZ-3V»

RESET

+ Line №2-    -Line №1 +