background image

«RIELTA», JSC  www.rielta.ru
Chapaeva Str. 17, Saint Petersburg 197101, Russian Federation,
E-mail: [email protected]

Tel/fax: +7 (812) 233-0302, 703-1360,
Technical support, tel. +7 (812) 233-29-53, 703-13-57, [email protected]

Wall mounting of the 

swivel

Ceiling mounting of the 

swivel

For wall    

mounting

Rear housing latch access 

For corner mounting

Blind flanges for the 
wiring openings

For  mounting  rear           

housing on a 

s

wivel

Sensor rear housing 

Сircuit board latch

Swivel

Buushing

Sphere

Screw

Details of the swivel bracket

Figure 2 – Sensor rear housing  and swivel bracket

5.3 For the best quality video image production, it is recommended to 

take into account the following requirements:

- avoid direct flash exposurers of TV-camera lens;
-  prevent the installation of sourses of light sources alongside of the 

Detector in order to avoid hot spots on the lens;   

- under operation at a night-time, it is necessary to apply additional  

light sources. 

5.4 In case of installation of the Detector without swivel bracket, the 

recommended installation height is 2.3 m from the floor. Therewith, the 
PIR-channel detection range is not less than 12 m. 

ATTENTION!

  In this variant of installation the sabotage protection zone 

of PIR-channel is not caught on TV-camera. When TV-camera monitoring 
of sabotage protection zone is required it is recommended to incline the 
Detector down over 300 with respect to norm position. For this purpose, the 

Detector should be installed on the swivel bracket. Note that this method 

of installation reduces the detection zone as little as 4 m.

5.5 Fulfill the Detector installation in the following sequence:
- Preliminarily choose the place of installation (taking into account 

specification described in Cls.5.3, 5.4);

- Using flat tip screwdriver put off the cover by pressing the latch of 

the cover throuh the opening located on the case bottom; (See Figure 2);

- Put off the PCB by unfastening the PCB fixing arm;
- Set up the DIP switches in accordance with chosen operation algorithm 

(See Cl.6.1);

- Drill holes in the base for the Detector wiring and fastening the base;
- Choose the place of installation, mark the places for mounting holes 

with regard to the openings on the detector base(swivel bracket), drill 
holes in the wall;

- Pass the wires through the wiring holes in the base, leaving several 

centimeters of the wires for connecting them inside the case;

- Fasten the base (swivel bracket) on the chosen place. In case of 

installation on the swivel bracket, move the screw upwards and remove it 
from the sphere, align the squere bulge on the sphere wirh correspondent 
recess in the top of the base. Insert a screw into the opening of the base 
top, locate the base in the required position, tighten the screw;  

- Set up the DIP-switches in accordance with chosen operation algorithm 

(See Cl.6.1);

- Install the PCB on its place.
5.6 Connection of the Detector
5.6.1 Terminals for connection of alarm loop, video system and additional 

lighting control unit, as well as voltage application terminals are located 
on the PCB top.

5.6.2 Fulfill connections in accordance with the pattern, shown in Figure 2.
5.7 Place an announcement at the place ensuring possibility to acquaint 

everybody of the audience at the secured object about video control 
presence.

6 Preparation for Operation

6.1 DIP-Switches Settings

 

6.1.1 In order to prepare the Detector for particular exploitation conditions 

it is nesessary to set up «1», «2», «3», «4», «5»  DIP-switches in relevant  
positions in accordance with the Table 2.

Table 2

Mode

DIP-

switch

DIP-switch position

ON 

OFF

Sensitivity

«1»

Normal

High

Testing

«2»

Sensivity (sensitivity check)

Detection zone (DZ check)

Indicator

«3»

ON

OFF

TV-camera 

mode

«4», «5»

See table 3

6.1.2 DIP-switches «4» and  «5» position correspondence to the TV-

camera mode is listed in Table 3.

Table 3

«4»

«5»

TV-camera operation mode

ON

OFF

5 s after alarm

OFF

ON

30 s after alarm

ON

ON

120 s after alarm

OFF

OFF

TV-camera adjustment – periodical TV-camera switching on for 

(600±20) s

6.1.3 Testing modes
Upon the warm-up time expiry, the Detector entirely  assumes its 

functionality. For the Detector checking two testing modes both with 5 
min run time are provided.

Detection Zone (DZ) Check Mode

DIP-switches porition: «2» – OFF, «3» – ON. This mode is intended for 

each DZ beam position determination. Upon each DZ beam crossing, the 
indicator is switched on for 0.25 s. Optimal movement speed at maximal 
distance is 0.5 m/s.

Sensitivity Check Mode

DIP-switches position: «2» – ON,  «3» – OFF. This mode is intended for 

estimation of the Detector sensitivity  (the distance covered within the DZ 
till the moment of an Alarm message generation). LED indicator switches 
for 0.25 s upon each DZ beam crossing, and the LED is lighting for 5 s 
displaying an Alarm message transmission.

High sensitivity

  –  DIP-switch position: «1» – OFF. Main operation 

mode. An Alarm message is generated after 2 – 4 steps within the DZ 
(after LED indicator single switching for 0.25 s).

Normal sensitivity

 – DIP-switch position: «1» – ON. This sensitivity 

mode is recommended for usage inside the premises with advanced 
interference. An Alarm message is generated after 4 – 5 steps within the 
DZ (after LED indicator double switching for 0.25 s). After every Alarm 
message generation stop moving and male a pouse till the LED is switched 
off, after what wait for 8 – 10 s before resuming movement inside the DZ.

NOTE :

  If the detector fails to detect moving objects in the detection 

zone, its position on its swivel bracket should be changed (In case of wall 
mounting the rotation angle of the Detector in horizontal plane is ±45° and 
its tilt degree in vertical plane is not less than 20°)

Under the movement absence in the secured zone, the LED indicator 

should not light. After 5 min operation in any of both testing modes the 
Detector turns to normal operation mode automatically (in case of «3» 

jamper is ON, the alarm message generation is displayed by LED indicator 

lighting for 3 s period).

The DZ location can be estimated at-a-glance by transforming TV-

camera to continuous operation mode and by monitoring movements on 
video-system control unit.

6.1.4 LED indicator disabling
For the detector operation masking, the LED indication disabling mode 

is provided. DIP-switch «3» is OFF. In this mode the LED indicator is 
operative only at a first minute after energizing, as well as during «Failure» 
message generation.

6.2 To prepare the Detector to operation act as follows:

- check correctness of the Detector installation;
- set up the DIP-switches to the required mode (set up DIP-switches 

«4» and «5» to OFF position for adjustment of TV-channel detection zone, 
choose sensitivity mode by means of DIP-switch «1»);

-  energize the Detector. During 60 s after energizing the LED indicator 

should blink at a frequency  of 1 Hz, informing about its turning to normal 
operation;

- fulfill a simulation of the intruder movement through the DZ at a speed 

0.3 m/s, and then 3 m/s monitoring the Detector response by its LED 
indicator switching on. It is advisable to repeat such passages at minimal 
as well as at maximal distanses to the Detector. Make sure that at the 
video-system control unit (hereinafter, VCU) your video image is visible. 
Verify that in case of optional lighting circuit control (LCC) it was switched 

ON during passages.

- in case of the Detector response failure or your video image absence, 

it is necessary to make corrections in the DZ location. In the lack of 
illumination, install sufficient illumination devices or additional optional 
lighting, controlled by the LCC;

- after adjustment finishing set up the DIP-switches to the operating 

mode.

Reviews: