WIRELESS INDEPENDENT 

SMOKE DETECTOR

«Ladoga PD-RK-A»

Installation Guide

1 General Information

1.1 The wireless independent smoke Detector «Ladoga PD-RK-A» (hereinafter, 

the Detector) is intended for:

- detecting ignitions accompanied by smoke;
- sound announcement about the fire accident;
- «Fire» message generating and sending within the 433.05 to 434.79 MHz 

frequency range via two-way communication by the «Rielta-Сontaсt-R» exchange 
protocol. 

Operating principle of the Detector is based on the detection of the optical 

radiation reflected from smoke particles.

1.2 The Detector is designed for operation as a component of a system, 

that is operated by any control panel (hereinafter, CP) supporting the «Rielta-
Contact-R» wireless exchange protocol or in stand-alone mode without the CP.

1.3 After ignition detection, the Detector generates Fire alarm message and 

transmit’s it to the CP (in case of operation with the CP), switches on light state 

indication and sound announcement.

1.4 In case of operation in independent mode, Norm state restoration and 

sound announcement takes place after smoke content reducing lower the 
threshold.

1.5 In case of operation with a CP, Norm state restoration and sound 

announcement is executed after smoke content reducing lower the threshold 
and getting «RESET» command from the CP.

1.6 In case operation with a CP, the Detector provides possibility to switch 

ON announcement by the relevant command from the CP, as well as to inhibit 
announcement automatic switching ON when ignition is detected.

1.7 The Detector provides pulse and continues modes of sound announcement. 

Mode of operation is configured by means of the CP.

1.8 The Detector provides compensation of the optical smoke chamber dust 

content and controls it’s operability.

1.9 Radio signals exchange with the CP is fulfilled via the wireless two-way 

communication in 433.05 – 434.79 MHz frequency range. The Detector provides 
automatical switch to a backup operating frequency in case of radio-frequency 
interference at the main one.

1.10 Transmitter power does not exceed 10 mW.
1.11 The Detector comprises functionality testing module with speed of 

response not more than 5 s.

1.12 The Detector status is displayed by two built-in LED indicators.

1.13 The Detector controls it’s removal from the base.

1.14 The Detector is powered from two galvanic power supply batteries CR123A 

type with nominal voltage 3 V: the main and backup ones.

1.15 Ignition is detected if at least one battery is in working order.
1.16 During operation in independent mode in case of any battery failure, 

short sound signal is generated once in 40 s.

1.17 The Detector generates and transmits via wireless communication channel 

the following messages:

- «Norm» – normal state;
- «Fire alarm» – ignition is detected;
- «Optical smoke chamber dusting» – upon reaching the dust concentration 

threshold;

- «Failure» – circuit fault or sensitivity drop;
- «Main power-supply low-battery» – if power-supply voltage drops below 

2.4 V ± 0.2;

- «Backup power-supply low-battery» – if power-supply voltage drops below 

2.4 V ± 0.2;

- «Tamper» – in case of the Detector removal from the base.
1.18 The following rates of radio exchange may be assigned: 10 s,  

15 s, 30 s, 60 s, 2 min or 5 min by the command from the CP. Messages  about 
ignition and failures are transmitted immediately.

1.19 The Detector provides safe operation in a standby mode* being powered 

by:

- main power-supply battery: not less than 5 years;
- backup power-supply battery: not less than 2 months.
1.20 The Detector designed to operate  in closed areas  continuously  around 

the clock.

2 Features

Table1 

Parameter

Value

Threshold of sensitivity

0.16 ± 0.03 dB/m

Acoustic pressure level at 1 m distance from the 

Detector, not less than, not less than

85 dB

Generated sound alarm signals frequency

2 … 5 kHz

Consumption current in standby mode (without radio 

exchange), not more than

20 

μ

A

Consumption current in alarm mode  and sound 

announcement, not more than

100 mA

Operating temperature

minus 20 °C  +55 °C

Table 1, continuation

Parameter

Value

Permissible humidity (at a temperature 40 °C)

93 %

IP rating

IP30

Dimensions, not more than

 

Ø 

125 х 70 mm

Weight, not more

0.2 kg

Average service life

10 years

3 Scope of Delivery

Each Detector unit package contains the items listed in Table 2.

Table 2

Name

QNT

Wireless independent smoke Detector «Ladoga PD-RK-A»
Screw 3-3x30.016 
Wall plug NAT 5x25 SORMAT 
CR123A lithium power-supply battery 
Wireless independent smoke Detector «Ladoga PD-RK-A». Installation Guide

1 pc.

2 pcs.
2 pcs.
2 pcs.

1 copy

4 Design of the Detector

* under conditions of: radio sessions  interval of at least 30 s, 

 

radio-interference absence and normal climate parameters

The Detector outside view is shown in Figure 1. 
The Detector comprises:
- case with optical smoke chamber (1);
- base (2);
- two LED indicators (3);
- main power supply battery (8);
- backup power supply battery (6);
- operability control button «TEST» (4);
- pin contacts «RESET» (5);
- tamper (removal from the base control) (7).

5 LED Indication

The Detector displays it’s state in accordance with Table 3.

Table 3 

Detector Status

Indication

Notes

«Binding»

Green LED indicator blinks intermittentl

«Binding completed»

Single-shot (2 s) green LED lighting

«Fire»

Red LED indicator blinks intermittently at 

1 Hz frequency

«Norm» 

Green LED blinks once per 15 s

«Dusting»

Red LED blinks once per 15 s

Independent 

operation

«Power supply failure»

Red LED switching on once per  

15 s and sound signal – once per 

30 s

Operation with 

the CP

No communication with 

the CP

Red LED indicator blinks once per 

15 s

Operation with 

the CP

Communication quality 

appraisal «Excellent»

Three blinks of green LED

Operation with 

the CP

Communication quality 

appraisal «Good»

Two blinks of green LED

Operation with 

the CP

Communication quality 

appraisal «Communication 

established»

One blink of green LED

Operation with 

the CP

Communication quality 

appraisal 

«No communication»

Four  blinks of green LED

Operation with 

the CP

Figure 1

1

2

3

4

5

6

7

8

TEST

BACKUP

RESET

MAIN