11 The Detector Switching on and Checking
For mounting height 5 m set up DIP-switch «1» to ON position (5 m). If
the ceiling hight of the room is less than 3 m, it is recommended to set up
DIP-switch «1» to OFF position (2.5 m). Thus, the higher sensitivity level is
provided. It is recommended to use the Detector in this mode in small rooms
with severe interference conditions.
After enegizing the Detector executes self-testing (checking of power supply,
environment temperature as well as amplification path testing), the LED blinks
red (independently from DIP-switch «3» position), output contacts are opened.
During self-testing procedure it is necessary to exclude any movement in the
detection zone, asi can result in failure message generation.
12 Functional Check
Upon expity «Warm-up Time», the Detector changes to standby mode and is
able to generate an alarm message.
High filled density of the Detection zone provides to detect intruder moving
in any direction. Testing and sensitivity adjustment is fulfilled so as to determine
the detection zone borders.
Testing mode
DIP-switches position: «3» – ON, «2» – ON.
This mode ensures determination of each detection zone beam position. After
each beam crossing, the indicator switches for 0.25 sec. Optimal movement
speed at maximal distance is 0.5 m/sec.
Note
– In this mode there is no LED indication of аlarm message.
Under absence of movement inside the detection zone, the indicator should
not light. The testing mode is performed during 5 min, whereafter the Detector
changes over to «Norm» mode.
Sensitivity Check
DIP switches position: «3» – ON, «2» – OFF. This mode is intended for the
Detector sensitivity appraisal (the distance inside the detection zone, which is
covered before alarm message generation). Alarm message is generated after
2 – 5 steps inside the detection zone (depending on mounting height and
direction of movement) during 3 sec.
After each alarm message generation, stop and make a pause till the LED is off,
after it wait for 8 – 10 sec before proceeding movement inside the detection zone.
Note
– In the temperature range near 36 °С, temperature compensation is
switched on, providing maintainance of detection ability of the Detector.
13 LED Indicator Disabling
For the Detector operation masking, LED indicator disabling mode is provided.
DIP-switch «3» is in OFF position. In this mode LED is functioning only in first
minute of operation after the Detector energizing, as well as in modes «Alarm
memory» and «Failure».
14 Alarm memory
DIP-switch «4» is ON. The LED is lighting green in 5 min after alarm
message generation. LED indication duration is 15 min. Change-over of
DIP-switch «4» from ON to OFF position results in the «Alarm memory» indication
reset.
15 Self-testing and Failure Indication
The Detector fulfills self-testing automatically, thereby the following parameters
are checked:
- availability of the receiver and signal amplifier;
- power supply voltage;
- environment temperature.
The Detector generates «Failure» message with 15 min period under the
following conditions:
- power supply voltage drop lower than 9.0
-1
V – by the relay contacts opening,
duplicated by perionical single LED indicator blinking green;
- maximal permissible temperature value exceedance – by the relay contacts
opening, duplicated by perionical twofold LED indicator blinking green;
- negative result of the receiver with signal amplifier testing – by the relay
contacts opening, duplicated by perionical threefold LED indicator blinking green.
After removal of the failure cause, the Detector turnes over to the «Standby»
mode automatically in 15 min. Premature reset of «Failure» LED indication can
be fulfilled by changing DIP-switch «2» position from ON to OFF (or vice versa).
ATTENTION!
The Detector must be checked at least annually in order to
test it’s performance.
16 Storage and Transportation
16.1 The Detectors in their original packing may be shipped by any transport
means in covered vehicles (in railway, cars, trucks, sealed heated compartments
of aircraft, ship cargo holds, etc). The storage room should be free from
current-conducting dust, acid vapors, alkali and gases that cause corrosion
and destroy insulation.
16.2 The Detectors in their original packing may be stored not more than 3
months. During this period the Detector package should not have bloodshot
spots and impurities.
16.3 Upon the expiry of 3 months, the Detector should be released from
the package.
17 Manufacturer’s Guarantees
The Manufacturer guarantees conformity of the Detector to it’s Technical
Specifications if conditions of transportation, storage, assembling and operation
are observed. The guaranteed storage period is 63 months since the date of
manufacturing the Detector.
The guaranteed period of operation is 60 months since the date of
commissioning within the storage period guaranteed.
The Detectors that are found to non-conforming to it’s Technical Requirements
shall be repaired by the Manufacturer, provided the installation and operation
rules have been complied with.
18 Acceptance and Packing Certificate
Passive infrared detector «Foton-21»,
serial number ____________,
has been manufactured in compliance with the active technical documentation
and classified as fit for operation and packed by «RIELTA» JSC.
Person in charge of acceptance and packing
QC representative_________________ __________________.