background image

Summary of Contents for RS 50/EV

Page 1: ...20040438 5 05 2013 Installation use and maintenance instructions Forced draught gas burner Progressive two stage or modulating operation Code Model 20039989 RS 50 EV GB...

Page 2: ......

Page 3: ...11 Control box for the air fuel ratio LMV37 4 13 3 12 Actuators SQM33 5 16 4 Installation 17 4 1 Notes on safety for the installation 17 4 2 Handling 17 4 3 Preliminary checks 17 4 4 Boiler plate 17 4...

Page 4: ...rner working 27 6 Maintenance 28 6 1 Notes on safety for the maintenance 28 6 2 Opening the burner 29 6 2 1 To open the burner 29 6 2 2 To close the burner 29 A Appendix Spare parts 30 B Appendix Acce...

Page 5: ...nerator is to be installed The instruction manual shows the serial number of the burner the address and telephone number of the nearest Assis tance Centre The system supplier carefully informs the use...

Page 6: ...manual 1 2 1 Owner s responsibility Please pay attention to the Safety Warnings contained within this instruction manual Keep this manual for your records and provide it to your quali fi ed service a...

Page 7: ...the burner components is not allowed apart from the parts requiring maintenance Only those parts envisaged by the manufacturer can be replaced 2 2 Personnel training The user is the person body or co...

Page 8: ...eration Low high low or modulating Standard application Boilers water steam thermal oil Ambient temperature F 32 104 0 40 C Combustion air temperature F max 140 60 C Electrical protection NEMA 1 Noise...

Page 9: ...er supply 10 V Ph Hz 575 3 60 Fan motor rpm W HP V A 3450 0 75 575 1 3 Ignition transformer V1 V2 I1 I2 120 V 1 x 8 kV 1 6 A 20 mA Electrical power consumption W 950 Electrical control circuit cons W...

Page 10: ...h OFF ON 29 Signal Power ON 30 Lamp Signal Call for Heat 31 Signal Ignition ON 32 Signal Fuel ON 33 Burner terminal board X1 34 RWF40 modulator with analog output 4 20 mA 35 Lifting rings 36 Relay K2...

Page 11: ...ires the burner to be opened and the rear part withdrawn on the slide bars The maximum dimension of the burner when open without casing is give in measurement H Tab F 1 Blast tube short long obtainabl...

Page 12: ...are based only on altitude variation reference temper ature 68 F 20 C To get the combined correction in case of different air temper ature a compensation of 1000 ft each 20 F 305 m each 11 C is appli...

Page 13: ...908 2 875 8 843 5 811 85 779 8 747 8 Average barometric pressure 68 F w c 399 394 385 371 358 345 332 320 307 294 CORRECTED BURNER AIR PRESSURE ACCORDING TO ALTITUDE Altitude Rated Pressure m a s l 0...

Page 14: ...e best results are obtained in terms of low NOx emissions The maximum thickness of the boiler s front door must not ex ceed 8 see Fig 5 3 10 Minimum furnace dimensions The firing rates were set in rel...

Page 15: ...s via which it is possible to easily identify any causes of malfunctioning Mechanical design The following system components are integrated in the LMV37 4 basic unit Burner control with gas valve prov...

Page 16: ...oltage Nominal current Power factor AC 120 V 50 60 Hz 1 6 A pilot duty load declaration to UL372 cos 0 4 Alarm output Nominal voltage Nominal current Power factor AC 120 V 50 60 Hz 1 A cos 0 4 Ignitio...

Page 17: ...T P 10 Shutdown Operation Startup Valve proving OUTPUTS INPUTS Phase number Fuel Actuator 2 Air Actuator 1 Actuators Safety limit thermostat STB Control thermostat or pressurestat R Flame signal FS Ai...

Page 18: ...s can be seen on the dis play of the Operator Panel Index 0 for fuel actuator index 1 for air actuator Installation notes Always run the high voltage ignition cables separate from the unit and other c...

Page 19: ...he burner must be carried out by qualified personnel as indicated in this manual and in compliance with the standards and regulations of the laws in force WARNING The handling operations for the burne...

Page 20: ...ompromise the extraction of the blast tube For boilers having a water cooled front the insulation 4 5 Fig 11 is not required unless it is required by the boiler man ufacturer 4 6 Securing the burner t...

Page 21: ...ts are done on notch 3 as in Fig 13 In this case the pressure load loss of the combustion head is given by column A Tab I page 21 Diagram Fig 14 shows the ideal settings for the ring 2 Fig 13 If the g...

Page 22: ...e extract the inner part of the combustion head 12 4 9 Gas piping The main gas train must be connected to the gas attachment 1 Fig 17 using flange 2 gasket 3 and screws 4 supplied with the burner The...

Page 23: ...of the burner as fol lows subtract the combustion chamber pressure from the gas pres sure measured at test point 1 Fig 19 find the nearest pressure value to your result in column A or B Tab I for the...

Page 24: ...the electri cal layouts Check that the electrical supply of the burner corresponds to that shown on the identification label and in this manual Do not invert the neutral with the phase in the electric...

Page 25: ...e earthed with a large area It is desirable to earth the screen of the cable by clamping the cable to the earth plate The screen must be earthed on both side of the cable take care for good earthing s...

Page 26: ...4 15 Speed sensor adjustment WARNING The measurement of speed sensor 1 Fig 25 must be respected WARNING It is important that the disc 2 is installed on the burner as shown in the Fig 26 5 64 Fig 25 D...

Page 27: ...tions of maximum safe ty i e with gas delivery at the minimum 5 3 Burner firing Having completed the checks indicated in the previous heading the pilot of the burner should fire If the motor starts bu...

Page 28: ...int and start up the burner again to ensure the set point is correct If the burner locks out again turn the knob counter clockwise a little bit more DANGER Make sure that the lamps or testers connecte...

Page 29: ...ction manual The value during the operation must be higher than 24 If at the burner start up the value is higher or equal of 18 the burner locks out due to the extraneous light The display Fig 32 show...

Page 30: ...ings and correctly positioned Flame inspection window Clean the flame inspection window Fig 33 UV scanner Clean the glass cover from any dust that may have accumulated In order to reach the UV scanner...

Page 31: ...ustion head 12 Fig 36 6 2 2 To close the burner To close the burner proceed as follows push the burner 13 Fig 36 at approximately 4 from the elec trical board 14 insert the ignition electrode cables a...

Page 32: ...rts A Appendix Spare parts 13 12 1 10 11 6 25 26 14 64 24 57 58 8 9 18 8 19 60 61 21 5 7 20 61 59 63 62 22 44 2 4 3 22 43 48 42 65 41 55 45 37 56 27 16 28 53 59 52 49 51 47 46 50 35 36 34 33 32 31 30...

Page 33: ...IGNAL 19 20027020 LIGHT SIGNAL 20 3012956 TRANSFORMER B 21 20027021 SWITCH C 22 20018135 SERVOMOTOR B 23 3012994 MOTOR C 24 20027028 SCREW 25 3003891 CONNECTOR C 26 3012948 AIR PRESSURE SWITCH A 27 30...

Page 34: ...6 SHUTTER C 50 3003811 END CONE C 51 3003803 SQUARE B 52 3003893 TEST POINT 53 3006211 FUSE 54 20026791 SUPPORT 55 20027033 MANIFOLD 56 3003396 UV PROBE A 57 3005483 SEAL C 58 3013004 FLANGE AND ELBOW...

Page 35: ...on LPG Gas train according to UL Standards B Appendix Accessories Burner Standard length Length obtainable with kit Code RS 50 EV 8 1 2 13 13 16 3010258 Burner MBtu hr Code RS 50 EV 549 1986 3010272...

Page 36: ...Fire High Fire Control Power Supply CO Low Fire High Fire Burner Firing Rate NOX Low Fire High Fire Manifold Pressure Net Stack Temp Low Fire High Fire Pilot Flame Signal Comb Efficiency Low Fire High...

Page 37: ......

Page 38: ......

Page 39: ......

Page 40: ...ond Park Road 1 800 4 RIELLO 2165 Meadowpine Blvd Hingham Massachusetts 1 800 474 3556 Mississauga Ontario U S A 02043 Canada L5N 6H6 http www riello burners com RIELLO S p A I 37045 Legnago VR Tel 39...

Reviews: