background image

37 

20075344

GB

Faults - Possible causes - Solutions

8

Faults - Possible causes - Solutions

WARNING

In the event the burner stops, in order to prevent
any damage to the installation, do not unblock the
burner  more  than  twice  in  a  row.  If  the  burner
locks  out  for  a  third  time,  contact  the  customer
service.

DANGER

In  the  event  there  are  further  lockouts  or  faults
with  the  burner,  the  maintenance  interventions
must only be carried out by qualified, authorised
personnel, in accordance with the contents of this
manual and in compliance with the standards and
regulations of current laws.

Signal

Problem

Possible cause

Recommended remedy

2 blinks

Once the pre-purging 
phase and safety time 
have passed, the burn-
er goes into lockout 
without the appearance 
of the flame

The operation solenoid lets little gas through.

Increase

One of the two solenoid valves does not open

Replace

Gas pressure too low

Increase pressure at governor

Ignition electrode incorrectly adjusted

Adjust it

Electrode grounded due to broken insulation

Replace

High voltage cable defective

Replace

High voltage cable deformed by high temperature Replace and protect

Ignition transformer defective

Replace

Incorrect valve or transformer electrical wiring

Check

Defective control box

Replace

A closed valve upline the gas train

Open

Air in pipework

Bleed air

Gas valves unconnected or with interrupted coil

Check connections or replace coil

3 blinks

The burner does not 
switch on, and the lock-
out appears

Air pressure switch in operating position

Adjust or replace

The burner switches on, 
but then stops in lockout

Air pressure switch does not switch owing to lack of air pressure:

Air pressure switch incorrectly adjusted

Adjust or replace

Pressure switch pressure test point pipe blocked

Clean

Poorly adjusted head

Adjust

High pressure in the furnace

Connect air pressure switch to fan 
suction line

Lockout during pre-
purging phase

Defective motor control contactor
(only three-phase version)

Replace

Defective electrical motor

Replace

Motor lockout (defective electrical motor)

Replace

4 blinks

The burner switches on, 
but then stops in lockout

Flame simulation 

Replace the control box

Lockout when burner 
stops

Permanent flame in the combustion head or flame 
simulation

Eliminate persistence of flame or 
replace control box

6 blinks

The burner switches on, 
but then stops in lockout

Defective or incorrectly adjusted servomotor

Adjust or replace

7 blinks

The burner goes into 
lockout immediately fol-
lowing the appearance 
of the flame

The operation solenoid lets little gas through

Increase

Ionisation probe incorrectly adjusted

Adjust

Insufficient ionisation (less than 5 A)

Check probe position

Earth probe

Withdraw or replace cable

Burner poorly earthed

Check earthing

Phase and neutral connections inverted

Invert them

Defective flame detection circuit

Replace the control box

Burner locks out when 
shifting from minimum 
to maximum output and 
vice versa

Too much air or too little gas

Adjust air and gas

Burner goes into lock-
out during operation

Probe or ionisation cable grounded

Replace worn parts

Summary of Contents for RS 310/M MZ

Page 1: ...uctions 20075344 4 01 2015 Forced draught gas burners Modulating operation CODE MODEL TYPE 20068343 20068351 20061373 RS 310 M MZ 1142T 20068356 20068361 20067141 RS 410 M MZ 1143T 20068027 RS 510 M M...

Page 2: ...Translation of the original instructions...

Page 3: ...trical panel description 14 4 13 Control box RMG88 15 4 14 Servomotor SQM40 16 4 15 Calibration of the thermal relay 17 5 Installation 18 5 1 Notes on safety for the installation 18 5 2 Handling 18 5...

Page 4: ...Operation 32 6 8 3 Ignition failure 32 6 8 4 Burner flame goes out during operation 32 6 9 Burner start up cycle diagnostics 33 6 9 1 Resetting of control box and diagnostics use 33 6 9 2 Control box...

Page 5: ...ed as follows CE 0085CP0166 RS 310 M MZ Class 2 EN 676 CE 0085CP0166 RS 410 M MZ Class 2 EN 676 CE 0085CP0166 RS 510 M MZ Class 2 EN 676 CE 0085CP0166 RS 610 M MZ Class 2 EN 676 The quality is guarant...

Page 6: ...ed out correctly may cause damage to the ma chine and or injury to people DANGER DANGER LIVE COMPONENTS This symbol indicates operations which if not car ried out correctly lead to electric shocks wit...

Page 7: ...vent of damage to things or injury to people if such damage injury was due to any of the following causes incorrect installation start up use and maintenance of the burner improper incorrect or unreas...

Page 8: ...intenance Only those parts envisaged by the manufacturer can be replaced 3 2 Personnel training The user is the person body or company that has acquired the machine and intends to use it for the speci...

Page 9: ...atural gas Gas oil Gas oil Methane Adjustment Flame control system FS1 FS2 Standard 1 stop every 24 h Continuous working 1 stop every 72 h Electrical supply of the system 3 400 50 3 230 50 Voltage of...

Page 10: ...at max output 2 Gas G20 G25 mbar 33 2 49 5 41 7 62 48 9 73 64 6 96 4 Operation Intermittent Standard applications Boilers water steam diathermic oil Ambient temperature C 0 40 Combustion air temperat...

Page 11: ...d electrical power kW max 9 1 10 8 Protection level IP 54 STAR TRIANGLE START UP Model RS 310 M MZ RS 410 M MZ RS 510 M MZ RS 610 M MZ Code 20061373 20067141 20068027 20066706 Main electrical supply 3...

Page 12: ...ositions The l position is reference for the refractory thickness of the boiler door Maximum position for the extraction of the servomotor cover Tab G Model kg RS 310 M MZ 250 RS 410 M MZ 250 RS 510 M...

Page 13: ...diagram Tab H Model kW RS 310 M MZ 600 RS 410 M MZ 800 RS 510 M MZ 800 RS 610 M MZ 820 WARNING The firing rate value Fig 3 has been obtained considering an ambient temperature of 20 C an atmospheric...

Page 14: ...pecial test boilers accord ing to EN 676 regulations In Fig 4 you can see the diameter and length of the test combus tion chamber Example RS 610 M MZ Output 5000 kW diameter 100 cm length 5 m 4 10 Bur...

Page 15: ...ch 19 Combustion head air pressure test point 20 Maximum gas pressure switch with pressure test point 21 Flame sensor probe 22 Pressure test point for air pressure switch 23 Gas train adapter 24 Gas b...

Page 16: ...n contacts for signalling the burner is in lockout 11 Auxiliary circuits fuse includes a spare fuse 12 Timer for star triangle start up 13 Main terminal supply board 14 Supply cables and external conn...

Page 17: ...development of conden sate and humidity Otherwise before switching on again make sure that the entire control box is perfectly dry Static charges must be avoided since they can damage the control box...

Page 18: ...echnical data WARNING To avoid accidents material or environmen tal damage observe the following instruc tions Avoid opening modifying or forcing the ser vomotor Mains voltage 230 V 15 10 Mains freque...

Page 19: ...calibration 2 see the table in the wiring diagram To reset in case of an intervention of the thermal relay press the RESET button 1 of Fig 10 The red TEST button 3 opens the NC 95 96 contact and stop...

Page 20: ...ust be free from hazardous mixes e g chloride fluoride halo gen if present it is highly recommended to carry out cleaning and maintenance more frequently WARNING The handling operations for the burner...

Page 21: ...water cooled front piece a refractory lining 2 5 Fig 14 is not necessary unless expressly requested by the boiler manufacturer Tab I 5 6 Securing the burner to the boiler Fit the heat insulation suppl...

Page 22: ...elease the cables of the probe 5 and electrode 11 E Fully open the burner as in Fig 15 F Undo the screw 4 with pressure test point G Release the head by lifting it from its housing 3 then take out the...

Page 23: ...by turning the screw 1 clockwise Fig 18 Central air adjustment The factory setting is shown in Tab J Tab J In the event that the specific application requires a particular ad justment it is possible t...

Page 24: ...tion Below is a diagram Fig 20 that shows the recommended ad justment of the combustion head NOTE Depending on the specific application the adjustment can be modified Fig 20 20078016 No Setpoint air g...

Page 25: ...urners with maximum outputs over 1200 kW 9 Gasket for flanged versions only 10 Pressure adjuster 11 Train Burner adaptor supplied separately P2 Upline pressure of valves adjuster P3 Upstream pressure...

Page 26: ...er gas train combination manual 5 11 3 Gas train installation DANGER Disconnect the electrical power using the main switch Check that there are no gas leaks Pay attention when handling the train dang...

Page 27: ...tput value in the table Tab K for the burner in question read on the right column 1 the pressure at the test point P1 Fig 25 Add this value to the estimated pressure in the combustion chamber Example...

Page 28: ...s means it should compulsorily be stopped at least once every 24 hours to enable the control box to check its own efficiency at start up Normally the boiler s thermostat pressure switch ensures that t...

Page 29: ...ly valve Completes a rotation of 90 in 30 s After the adjustment made in the factory to its 6 cams to allow an initial ignition Check that they are as shown below In the event of a modification follow...

Page 30: ...r supply Release by pressing the button on thermal relay see section 4 15 on page 17 If ignition is still not achieved it may be that gas is not reaching the combustion head within the safety time per...

Page 31: ...e angle of cam III Fig 28 and by using the selector 2 Fig 29 To adjust the cam of the servo motor see Fig 32 A 6 6 3 Maximum output The MAX output must be set within the firing rate indicated in Fig 3...

Page 32: ...required Adjustment of gas delivery After adjusting the maximum and minimum output of the burner carry out air adjustment on higher intermediate positions of the servomotor The passage from one positi...

Page 33: ...anticlockwise until the burner locks out Turn the knob clockwise by 2 mbar and repeat the start up of the burner If the burner locks out again turn the knob clockwise again by 1 mbar 6 7 3 Minimum gas...

Page 34: ...x continues to check the presence of the flame and the correct position of the air and gas maximum pressure switches If the temperature or the pressure is low so the thermostat pressure switch TR is c...

Page 35: ...blinked The number of blinks indicates the reason for the malfunctioning refer to the coding in Tab U on page 38 6 9 4 Software diagnostics Gives an analysis of the life of the burner through optical...

Page 36: ...pulses of the LED constitute a signal spaced by approxi mately 3 seconds The number of pulses will measure the probe detection time since the opening of gas valves according to Tab R Tab R This is up...

Page 37: ...r to maintain all the original combustion characteristics in tact especially the flue gas temperature and combustion cham ber pressure Flame presence check The burner is fitted with an ionisation syst...

Page 38: ...G 25 11 5 9 5 8 8 100 170 G 30 14 0 11 6 10 7 100 230 G 31 13 7 11 4 10 5 100 230 WARNING The specified life cycles do not refer to the warran ty terms indicated in the delivery or payment con dition...

Page 39: ...h on and the lock out appears Air pressure switch in operating position Adjust or replace The burner switches on but then stops in lockout Air pressure switch does not switch owing to lack of air pres...

Page 40: ...ce The burner continues to repeat the start up cy cle without lockout The gas pressure in the gas mains lies very close to the value to which the gas pressure switch has been set The sudden drop in pr...

Page 41: ...regulator Code All models RWF 50 2 3 POINT OUTLET 20073595 All models RWF 55 5 COMPLETE WITH RS 485 INTERFACE 20074441 All models RWF 55 6 COMPLETE WITH RS 485 PROFIBUS INTERFACE 20074442 Burner Probe...

Page 42: ...ram RS 610 M MZ 400 V Star Triangle Start Up 4 Functional layout RS 310 410 M MZ 230 400 V Direct Start Up Functional layout RS 310 410 510 610 M MZ 400 V Star Triangle Start Up 5 Functional layout RM...

Page 43: ...K 5 K 5 K 5 1 T 0 AC K 1 K 0C A K O AE F T G C K F CO K U 50 K G G0 T A K GA 0 K AD K GAV0 A T AC C K A K AC5G K ACD O T 0 C K O D K 0 K O CGT A 0 C K CA 0G K CA 0G K CA 0G DT C DDC K C D K C D K C DD...

Page 44: ...5 T 5 K 5 K 5 K 5 1 T AC K 1 K C A K O AE F T G C K F CO K U 5 K G G T A K GA K AD K GAV A T AC C K A K AC5G K ACD O T C K O D K K O CGT A C K CA G K CA G K CA G DT C DDC K C D K C D K C DD GFT GA G C...

Page 45: ...K 5 K 5 K 5 1 T 0 AC K 1 K 0C A K O AE F T G C K F CO K U 50 K G G0 T A K GA 0 K AD K GAV0 A T AC C K A K AC5G K ACD O T 0 C K O D K 0 K O CGT A 0 C K CA 0G K CA 0G K CA 0G DT C DDC K C D K C D K C DD...

Page 46: ...5 T 5 K 5 K 5 K 5 1 T AC K 1 K C A K O AE F T G C K F CO K U 5 K G G T A K GA K AD K GAV A T AC C K A K AC5G K ACD O T C K O D K K O CGT A C K CA G K CA G K CA G DT C DDC K C D K C D K C DD GFT GA G...

Page 47: ...K L 4 5 7 T 27 K 27 K 2 7 K 2 7 1 T BD K 2 1 K DAB K O BE F T GA 22D K F 22DO K U 7 K G 2 G T B K GB K B6 K GBV B T BD D K B K BD7G K BD6 O T A D K O A6 K 2 K O A DGT B AD K DB G K DB G K DB G 6T AD2...

Page 48: ...L K L 4 5 7 T 27 K 27 K 2 7 K 2 7 1 T BD K 2 1 K DAB K O BE F T GA 22D K F 22DO K U 7 K G 2 G T B K GB K B6 K GBV B T BD D K B K BD7G K BD6 O T A D K O A6 K 2 K O A DGT B AD K DB G K DB G K DB G 6T A...

Page 49: ...L K L 4 5 7 T 27 K 27 K 2 7 K 2 7 1 T BD K 2 1 K DAB K O BE F T GA 22D K F 22DO K U 7 K G 2 G T B K GB K B6 K GBV B T BD D K B K BD7G K BD6 O T A D K O A6 K 2 K O A DGT B AD K DB G K DB G K DB G 6T AD...

Page 50: ...L K L 4 5 7 T 27 K 27 K 2 7 K 2 7 1 T BD K 2 1 K DAB K O BE F T GA 22D K F 22DO K U 7 K G 2 G T B K GB K B6 K GBV B T BD D K B K BD7G K BD6 O T A D K O A6 K 2 K O A DGT B AD K DB G K DB G K DB G 6T AD...

Page 51: ...47H2 A6 G B 2 C A6 H C I2896 C B6 3 B9 G J6 56 C B 669 C J6 C B K9 5 G C 65 C 8B6 C H7 G 3 294 C H7 6 C 3 294 C H6 BG 2 294 C 29B6 C 29B6 C 29B6 J G J 6 C J 6 C J 6 C J 6 BAG B B C B 6A C B C B 28 G...

Page 52: ...A1E6 A E6 4 H 4 A 4 7 A 4 7 A 4 3 4 H 7 A 4 35 A A 58I3 D7 H B 3 A D7 I A J3 7 A B7 4 B H 7 67 A B 77 A 7 A B K 6 H A 76 A B7 A I8 H 4 3 5 A I8 7 A 4 3 5 A I7 BH 3 3 5 A 3 B7 A 3 B7 A 3 B7 H 7 A 7 A 7...

Page 53: ...D 9 M 7C E D 9 E CB7 E 8N 7A G M 2B DDC E G DDCN E O E 2 D 2 M P 7 E 27 E P 71 E 27Q 7 M 7C C E 7 E 7C 2 E 7C1 N8 M B C E N8B1 E D E N B C2M 7 BC E C7 2 E C7 2 E C7 2 P1M PBCD 11C E PBCD 1 E PBCD 1 E...

Page 54: ...6 M 6B F 6B 9 F 6B9 F 6B 6 M 9CA F 6B 7 F A C F 7 N C 9 M D BBA F 9BBAN F O 9 F D9B6 D M 9C89 F DC99 F 9CE F DCP C8 M CA A F C98 F CA D9 F CAE N M 6 7A F N E9 F 6B 7 F N9 ADM C 7 A F AC D9 F AC D9 F...

Page 55: ...C9D E G 1 U A1 C A1 C A 1 C A 1 K U B0 C A K C 0 B C V B F U 3 AA0 C F AA0V C W 1 C 3 A 3 U 2 B C 3B C 2 B5 C 3BX B U B0 0 C B C B013 C B05 V U 0 C V 5 C A C V 03U B 0 C 0B 3 C 0B 3 C 0B 3 25U 2 0A 55...

Page 56: ...9 DKE6 G DKE 0 DKE 3 DKE 1 6 L 60 D 60 D 60 D 60 65 L 3 8B D 60 5 D 3B28 D M 8A F L C2 00B D F 00BM D N 3 D C 06 C3 L O 8 D C8 3 D O 8 D C8P3 8 L 8B B D 8 D 8B C D 8B M L 62 3 B D M 2 D 60 3 D M 2 BCL...

Page 57: ...J J J2 J J I I M C M C N 9C K 9C6 K 96C K 93C E N 6 8 K 934E K 8 K 4FD3 O6 N 3998 K O6998D K P3C 6 K 69 N Q6 56 K 66 K Q6 K G 5 N 8 8 K 65 K 8C 6 K 8 DF N 3 48 K DF 6 K 93 4 K D6 8 N 3 3 4 8 K 8 3 6...

Page 58: ...J 3 O A6 J PK6 A 56 86 J C 556 6 6 J 3 6 A6 J A6 A 5 6 8 A56 8G 1 83JUV 8 GX DDS 1 EJ CKG 7I 5 7I GX DDS 1 EJ CKG 5 I 6 6 6 I K56K 6 J A6 IK 6 I K 6 CK N 6 K 8K5 4 5 36 C 66 K 56 G 7I G 7I I A 5 K 3 6...

Page 59: ...K8 6K J 3 O A6 J PK6 A 56 86 J F 556 6 6 J 3 6 A6 J A6 A 5 6 8 A56 8 1 83JUV 8 7I 7I I 6 6 6 I K56K 6 J A6 IK 6 I K 6 FK N 6 K 8K5 4 5 36 F 66 K 56 7I I A 5 K 3 6 I 6 6 I5 36 I K56K IK 6 5 9 K 5 I5 I...

Page 60: ...H 6 L 6 K8 6K J 3 O A6 J PK6 A 56 86 J F 556 6 6 J 3 6 A6 J A6 A 5 6 8 A56 8 2 83JUV 8 7I 7I I 6 6 6 I K56K 6 J A6 IK 6 I K 6 FK N 6 K 8K5 4 5 36 F 66 K 56 7I I A 5 K 3 6 I 6 6 I5 36 I K56K IK 6 5 9...

Page 61: ...6 M 6 N O 6 M 6 N 7 R 7 S 7 S 7 S 7 6 7 R S 7 68 S S 8CO6 F B R 6 S B O S T6 S 7 R E 9 S S E S D 9 R S 9 S S OC R 7 6 8 S OC S 7 6 8 S O R 6 6 8 S 6 S 6 S 6 E R E S E S E S E BR S B S S 6 R 6 S S S 6...

Page 62: ...9 A 5BBBBB G9 AH A 4 Y6978 36 23DDBBZ G 4 4 G 5 5 CBBBB AX 5 AA 2 2 1 1 0 AYCZ AX 1 Y6978 36 23DDBBZ 4 G G AY Z D A A 1 0 4 7 H 7 H 7 H 7 9 6 H 7 1 H 960 H 1 2 8 G0 776 H 8 7762 H 9 H G 7 G9 H G 9 H...

Page 63: ...e starter triangle contactor KS1 Start triangle starter star contactor KSM Relay KST1 Star triangle starter timer K1 Clean contacts output relay burner operating K2 Clean contacts output relay burner...

Page 64: ...Subject to modifications RIELLO S p A I 37045 Legnago VR Tel 39 0442 630111 http www riello it http www riello com...

Reviews: