20020804
14
Installation
4.6
Choice of nozzle
Nozzles with no fuel shutoff needle must be fitted on the nozzle
holder.
To set the delivery range within which the nozzle must work,
nozzle return line fuel pressure must be adjusted according to
the table (Tab. 5-Tab. 6).
Tab. 5
Tab. 6
Recommended nozzle
• BERGONZO, type B5 45°;
• FLUIDICS, type N4 45°.
Intermediate flow rates may be obtained by choosing the nozzle
with a nominal flow rate slightly higher than that actually re-
quired.
Complete range of nozzles:
Bergonzo type B5 45° (Tab. 5):
350 - 375 - 400 - 425 - 450 - 475 - 500 - 525 - 550 - 575 - 600 -
650 - 700 - 750. We normally recommend 45° angles of pulver-
isation.
Fluidics type N4 45° (Tab. 6):
375 - 400 - 450 - 500 - 550 - 600 - 650 - 700 - 750. We normally
recommend 45° angles of pulverisation.
Fit the nozzle with the box spanner, fitting the spanner through
the central hole in the flame stability disk.
Do not use any sealing products such as gaskets, sealing com-
pound, or tape. Be careful to avoid damaging the nozzle sealing
seat. The nozzles must be screwed into place tightly but not to
the maximum torque value provided by the wrench.
4.7
Electrode positioning
Place the electrode on the ignition pilot observing the
dimensions specified in Fig. 13.
kg/h
Delivery
pressure
PSI
Return
pressure
PSI
kg/h
GPH
375
290
166.8
147
45.7
Low fire
290
246.5
295
78
High fire
550
290
145
170
52.8
Low fire
290
246.5
421
130.7
High fire
650
290
116
180
56
Low fire
290
239.3
565
175.6
High fire
700
290
87
160
49.7
Low fire
290
232
630
195.7
High fire
750
290
108
180
55.9
Low fire
290
230
660
205
High fire
kg/h
Delivery
pressure
PSI
Return
pressure
PSI
kg/h
GPH
375
290
174
147
45.7
Low fire
290
268.3
295
78
High fire
550
290
101.5
170
52.8
Low fire
290
232
421
130.7
High fire
650
290
87
180
56
Low fire
290
246.5
565
175.6
High fire
WARNING
2 " 1 3 / 1 6
1 1 / 1 6 "
Diffuser
Electrode
D10019
Fig. 13