17
20148124
GB
Installation
5.7
Securing the burner to the boiler
Prepare a suitable lifting system using rings 3)(Fig. 12).
Fit the heat insulation supplied onto the blast tube 4)
(Fig. 12).
Fit the entire burner onto the boiler hole prepared previously,
as in Fig. 11, and fasten with the screws supplied.
5.8
Access to head internal part
In order to reach inside the combustion head (Fig. 13) proceed as
follows:
disconnect the electrical wiring related to oil pump/
servomotor, air servomotor and gas pressure switch;
disconnect the leverages related to air damper and head
movement;
undo the 4 fixing screws 1);
disconnect the electrode cable 2);
disconnect the light oil pipes unscrewing the two pipe fittings
3).
Release the ignition pilot retainer;
remove the gas pressure screw/test point 6) of the head;
disconnect the lower part of the elbow until it is released
from its housing;
remove the internal part of the head 5).
5.9
Electrode position
ATTENTION
The seal between burner and boiler must be
airtight.
5
2
1
1
3
3
8
7
4
D8364
Fig. 12
ATTENTION
Be careful as some drops of fuel may leak out
during this phase.
1
1
3
4
5
2
6
D9337
Fig. 13
ATTENTION
Position the electrode on ignition pilot according to
the dimensions shown in Fig. 14.
18.5
0
- 2
71.5
± 1
Diffuser
Electrode
D9218
Fig. 14
Summary of Contents for RLS 800/M MX
Page 2: ...Translation of the original instructions ...
Page 52: ...20148124 50 GB Appendix Electrical panel layout ...
Page 53: ...51 20148124 GB Appendix Electrical panel layout 0 1 1 1 ...
Page 55: ...53 20148124 GB Appendix Electrical panel layout 0 1 2 2 2 0 ...
Page 56: ...20148124 54 GB Appendix Electrical panel layout 0 1 1 1 2 3 45678 9 55 ...
Page 62: ......
Page 63: ......