20084880
48
GB
Faults - Possible causes - Solutions
Once the pre-purging
and the safety time has
elapsed the burner goes
into lockout without the
flame appearing
No fuel in the tank, or water on the bottom
Refill with fuel, or remove the water
Bad head and damper adjustments
Adjust
Faulty or grounded high voltage cable
Replace
High voltage cable deformed by high tempera-
ture
Replace and protect
Bad electrical wiring on valves or transformer Check
Pump unprimed
Prime it
Pump suction line connected to return line
Correct connection
Dirty filters (nozzle line)
Clean
The valves upstream from the pump are
closed
Open them
Opposite motor rotation
Change electrical wiring to the motor
Light oil solenoids do not open
Check connections and
solenoids
Nozzle clogged, soiled or deformed
Clean it or replace it
Defective control box
Replace
Ignition electrode incorrectly adjusted
Adjust it
Electrode grounded due to broken insulation
Replace
Motor/pump coupling broken
Replace
Faulty ignition transformer
Replace
The flame ignites regu-
larly but the burner goes
into lock out at the end of
the safety time
Control box defective
Replace flame sensor or control box
Dirty flame sensor
Clean
Insufficient detection current
Measure current, replace flame sensor
Smoke in flame
(dark Bacharach)
Little air
Adjust the fan head and damper
Incorrect pump pressure
Adjust
Nozzle filter clogged
Clean or replace
Insufficient boiler room ventilation openings
Increase
Dirty or worn nozzle
Replace
Flame disk soiled, loose or deformed
Clean it, tighten it or replace it
Smoke in flame
(yellow Bacharach)
Excessive air
Adjust head and air dampers
Ignition with pulses or
flame failure, delayed
ignition
Poorly adjusted head
Adjust
Incorrectly adjusted fan air damper: too much
air
Adjust
Nozzle not fit for burner or boiler
See the nozzle table
Faulty nozzle
Replace
Unsuitable pump pressure
Adjust
Ignition electrode not adjusted correctly or
soiled
Adjust it
Output during ionisation phase is too high
Reduce
Uneven fuel supply
Understand whether the cause lies in the
pump or the fuel supply system
Supply fuel to the burner from a tank posi-
tioned near the burner itself
Internally rusted pump
Water in the tank
Remove the water with a pump
Noisy pump, unstable
pressure
Air in the suction line
Block the couplings
Depression value too high (higher than 35 cm Hg)
Excessive difference of level between burner
and tank
Power the burner from a loop circuit
Piping diameter too small
Increase
Dirty suction line filters
Clean
Suction line valves closed
Open them
The paraffin solidifies due to the low tempera-
ture
Put additive in the light oil
LIGHT OIL OPERATION
Symbol
(1)
Problem
Possible cause
Recommended remedy
1
Summary of Contents for RLS 310/M MX
Page 2: ...Original instructions ...
Page 62: ...20084880 60 GB Appendix Electrical panel layout RLS 310 410 M MX 230 400V DSU ...
Page 63: ...61 20084880 GB Appendix Electrical panel layout RLS 310 410 510 610 M MX 400V ST ...
Page 66: ...20084880 64 GB Appendix Electrical panel layout 0 0 0 ALL MODELS ...
Page 67: ...65 20084880 GB Appendix Electrical panel layout 0 0 0 1 ALL MODELS ...
Page 68: ...20084880 66 GB Appendix Electrical panel layout 0 1 1 2 1 1 1 1 1 1 1 0 1 ALL MODELS ...