Maintenance
Fan
Check to make sure that no dust has accumulated inside the fan
or on its impellers, as this condition will cause a reduction in the
air flow rate and provoke polluting combustion.
Boiler
Clean the boiler as indicated in its accompanying instructions in
order to maintain all the original combustion characteristics
intact, especially: the flue gas temperature and combustion
chamber pressure.
Flame presence check
Check the level of the flame detection signal with the “Check
Mode” function from the flame control: LEDs from 2 to 6 indicate
the flame signal level, respectively.
see “Description of LED lamps” on page 41
Check Mode
With burner flame on:
hold the reset button on the flame control pressed for at
least 3 sec.;
the button colour will change from green to yellow;
each operating status signalling LED will be compared to
20% of the maximum brightness;
press the reset button again (<0.5sec) to reset the standard
operation of the signalling LEDs.
7.2.4
Safety components
The safety components should be replaced at the end of their life
cycle indicated in the following table.
The specified life cycles do not refer to the warranty terms
indicated in the delivery or payment conditions.
Tab. N
Safety component
Life cycle
Flame control
10 years or 250.000
operation cycles
Flame sensor
10 years or 250.000
operation cycles
Gas valves (solenoid)
10 years or 250.000
operation cycles
Pressure switches
10 years or 250.000
operation cycles
Pressure adjuster
15 years
Servomotor (electronic cam)
10 years or 250.000
operation cycles
Oil valve (solenoid)
10 years or 250.000
operation cycles
Oil regulator
10 years or 250.000
operation cycles
Pipes/ oil fittings (metallic)
10 years
Flexible hoses (if present)
5 years or 30.000 pressurised
cycles
Fan impeller
10 years or 500.000 start-ups