Installation
5.13
Light oil supply
5.13.1 Double-pipe circuit
The burner is equipped with a self-priming pump which is capable
of feeding itself within the limits listed in Tab. M.
Tank higher than burner A
Distance "P" must not exceed 10 meters in order to avoid strain-
ing the pump's seal; distance "V" must not exceed 4 meters in or-
der to allow pump self-priming even when the tank is almost
empty.
Tank lower than burner B
Pump depression values higher than 0.45 bar (35 cm Hg) must
not be exceeded. Because at higher levels gas is released from
the fuel, the pump starts making noise and its working life-span
decreases. It is good practice to ensure that the return and suc-
tion lines enter the burner from the same height; in this way it will
be less probable that the suction line fails to prime or stops prim-
ing.
5.13.2 The loop circuit
A loop circuit consists of a loop of piping departing from and re-
turning to the tank with an auxiliary pump that circulates the fuel
under pressure.
A branch connection from the loop feeds the burner.
This circuit is extremely useful whenever the burner pump does
not succeed in self-priming because the tank distance and/or
height difference are higher than the values listed in Tab. M.
5.13.3 Hydraulic connections
The pumps are equipped with a by-pass that connects return line
with suction line.
They are installed on the burner with the by-pass closed by screw
6)().
It is necessary to connect both flexible hoses to the pump
(Fig. 29). The pump will break down immediately if it is run with
the return line closed and the by-pass screw inserted.
Remove the plugs from the suction and return connections of the
pump.
Key to layout (Fig. 28)
H = Pump/Foot valve height difference
L = Piping length
Ø = Inside pipe diameter
1 = Burner
2 = Pump
3 = Filter
4 = Manual on/off valve
5 = Suction line
6 = Foot valve
7 = Quick closing manual valve with remote control (Italy only)
8 = On/off solenoid valve (Italy only).
9 = Return line
10 = Check valve (only Italy)
Tab. M
Explosion danger due to fuel leaks in the pres-
ence of a flammable source.
Precautions: avoid knocking, attrition, sparks and
heat.
Make sure that the fuel interception tap is closed
before performing any operation on the burner.
WARNING
WARNING
The fuel supply line must be installed by qualified
personnel, in compliance with current standards
and laws.
WARNING
WARNING
Follow the instructions below:
Tighten the flexible hoses with the supplied
gaskets.
Take care that the hoses are not stretched or
twisted during installation.
Place the pipes so that they are not crushed
or are in contact with hot parts of the boiler
and so it is possible to open the burner.
Finally, connect the other end of the flexible
hoses to the suction and return pipes.
+/- H
L [m]
m
Ø 12 mm
Ø 14 mm
Ø 16 mm
+ 4
+ 3
+ 2
+ 1
+ 0.5
71
62
53
44
40
138
122
106
90
82
150
150
150
150
150
0
36
74
137
- 0.5
- 1
- 2
- 3
- 4
32
28
19
10
-
66
58
42
26
10
123
109
81
53
25
A
B
3
5
9
1
2
7
10
9
5
7
6
6
8
4
10 c
m
V
P
- H
+
H
Fig. 28
20058642
Fig. 29
D10531
Summary of Contents for RLS 120/E FGR
Page 2: ...Translation of the original instructions ...
Page 51: ...49 20168262 GB Appendix Electrical panel layout 01 2 3 4506 7 891 01 ...
Page 52: ...20168262 50 GB Appendix Electrical panel layout 0 1 2 2 2 0 ...
Page 54: ...20168262 52 GB Appendix Electrical panel layout 0 0 0 12 3456 7 12 3456 7 ...
Page 57: ...55 20168262 GB Appendix Electrical panel layout 0 0 1 2 3 4 5 667 8 667 2 9 63 8 63 63 3 5 ...