5.11
Combustion head adjustment
The air damper servomotor 4)(Fig. 4), beyond varying the air
output according to the output demand, through a leverage varies
the combustion head adjustment.
This system allows an optimum adjustment also at minimum
firing rate.
Similarly to servomotor rotation, it is possible to vary the opening
of the combustion head moving the tie-rod on the holes (5-6-7-8-
10)(Fig. 16).
The selection of the hole to be used is determined based on the
maximum output requested, as illustrated in Tab. J.
In the factory, the hole is adjusted for the maximum stroke (hole
10, Fig. 16).
Tab. J
Fig. 16
20062792
Leverage hole
Output (kW)
From
To
RLS 100
0/M
5
1200
3750
5
3750
6700
8
6700
8600
8
8600
10600
RLS 120
0/M
5
1500
5500
5
5500
7500
6
7500
9600
10
9600
11500
WARNING
The gas pipes leave the factory calibrated at
notch 1.
The adjustment shown in Fig. 17 allows the gas
pipes to be positioned in the best way for the
application on which the burner is installed (e.g.
boilers with flame inversion chamber).
Fig. 17
20077710
Summary of Contents for RLS 1000/M MX
Page 2: ...Translation of the original instructions ...
Page 54: ...20148180 52 GB Appendix Electrical panel layout 0 0 0 0 0 0 0 0 ...
Page 55: ...53 20148180 GB Appendix Electrical panel layout 0 0 0 1 0 2 0 0 0 0 0 0 0 30 3 3 0 0 1 0 ...
Page 57: ...55 20148180 GB Appendix Electrical panel layout 0 1 2 2 2 0 ...
Page 62: ...20148180 60 GB Appendix Electrical panel layout 0 12 3 4 5 4 5 6 7 6 8 9 8 9 7 7 0 0 0 ...
Page 66: ......
Page 67: ......