Riello RL 28/1 Installation, Use And Maintenance Manual Download Page 15

14

SIGNAL

FAULT

PROBABLE CAUSE

SUGGESTED REMEDY

No blink

The burner does not 
start

1

- No electrical power supply  . . . . . . . . . . . . . . . . . . . . . . . . . . . .  Close all switches - Check fuses

2

- A limit or safety control device is open  . . . . . . . . . . . . . . . . . . .  Adjust or replace

3

- Control box lock-out

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Reset control box (no sooner than 10 s after the 

lock-out)

4

- Pump is jammed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  Replace

5

- Erroneous electrical connections  . . . . . . . . . . . . . . . . . . . . . . .  Check connections

6

- Defective control box. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  Replace

7

- Defective electrical motor  . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  Replace

8

- Defective capacitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  Replace

4 x blinks

The burner starts and 
then goes into lock-out

9

- Photocell short-circuit  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  Replace photocell

10 - Light is entering or flame is simulated . . . . . . . . . . . . . . . . . . . .  Eliminate light or replace control box

2 x blinks

After pre-purge and the 
safety time, the burner 
goes to lock-out at the 
end of the safety time

11 - No fuel in tank; water on tank bottom . . . . . . . . . . . . . . . . . . . .  Top up fuel level or suck up water
12 - Inappropriate head and air damper adjustments  . . . . . . . . . . .  Adjust, see page 21 and 27
13 - Light oil solenoid valves fail to open (1st nozzle)  . . . . . . . . . . .  Check connections; replace coil
14 - 1st nozzle clogged, dirty, or deformed  . . . . . . . . . . . . . . . . . . .  Replace
15 - Dirty or poorly adjusted firing electrodes . . . . . . . . . . . . . . . . . .  Adjust or clean
16 - Grounded electrode due to broken insulation . . . . . . . . . . . . . .  Replace
17 - High voltage cable defective or grounded . . . . . . . . . . . . . . . . .  Replace
18 - High voltage cable deformed by high temperature . . . . . . . . . .  Replace and protect
19 - Ignition transformer defective  . . . . . . . . . . . . . . . . . . . . . . . . . .  Replace
20 - Erroneous valves or transformer electrical connections . . . . . .  Check
21 - Control box defective  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  Replace
22 - Pump unprimed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  Prime pump and see 

Pump unprimes

 

23 - Pump/motor coupling broken  . . . . . . . . . . . . . . . . . . . . . . . . . .  Replace
24 - Pump suction line connected to return line . . . . . . . . . . . . . . . .  Correct connection
25 - Valves up-line from pump closed  . . . . . . . . . . . . . . . . . . . . . . .  Open
26 - Filters dirty: line - pump - nozzle . . . . . . . . . . . . . . . . . . . . . . . .  Clean
27 - Defective photocell or control box . . . . . . . . . . . . . . . . . . . . . . .  Replace photocell or control box
28 - Dirty photocell . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  Clean

7 x blinks

Flame detachment

29 - Poorly adjusted head  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  Adjust, see page 6, fig. (F)
30 - Poorly adjusted or dirty firing electrodes . . . . . . . . . . . . . . . . . .  Adjust, see page 6, fig. (B)
31 - Poorly adjusted fan air gate:  too much air . . . . . . . . . . . . . . . .  Adjust
32 - 1st nozzle is too big (pulsation) . . . . . . . . . . . . . . . . . . . . . . . . .  Reduce 1st nozzle delivery
33 - 1st nozzle is too small (flame detachment) . . . . . . . . . . . . . . . .  Increase 1st nozzle delivery
34 - 1st nozzle dirty, or deformed . . . . . . . . . . . . . . . . . . . . . . . . . . .  Replace
35 - Inappropriate pump pressure  . . . . . . . . . . . . . . . . . . . . . . . . . .  Adjust

Uneven fuel supply

36 - Check if cause is in pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  Feed burner from tank 

or fuel supply system  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  located near burner

Internally rusted pump

37 - Water in tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  Suck water from tank bottom with separate 

pump

Noisy pump, unstable 
pressure

38 - Air has entered the suction line   . . . . . . . . . . . . . . . . . . . . . . . .  Tighten connectors

- Depression value too high (higher than  35 cm Hg):

39 - Tank/burner height difference too great  . . . . . . . . . . . . . . . . . .  Feed burner with loop circuit
40 - Piping diameter too small  . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  Increase
41 - Suction filters clogged . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  Clean
42 - Suction valves closed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  Open
43 - Paraffin solidified due to low temperature . . . . . . . . . . . . . . . . .  Add additive to light oil

Pump unprimes after 
prolonged pause

44 - Return pipe not immersed in fuel  . . . . . . . . . . . . . . . . . . . . . . .  Bring to same height as suction pipe
45 - Air enters suction piping  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  Tighten connectors

Pump leaks light oil

46 - Leakage from sealing organ . . . . . . . . . . . . . . . . . . . . . . . . . . .  Replace

 

pump

Smoke in flame
- dark Bacharach

- yellow Bacharach

47 - Not enough air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  Adjust head and fan gate, see page 6 and 10
48 - Nozzle worn or dirty  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  Replace
49 - Nozzle filter clogged  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  Clean or replace
50 - Erroneous pump pressure. . . . . . . . . . . . . . . . . . . . . . . . . . . . .  Adjust to between 10 - 14 bar
51 - Flame stability spirat dirty, loose, or deformed . . . . . . . . . . . . .  Clean, tighten in place, or replace
52 - Boiler room air vents insufficient . . . . . . . . . . . . . . . . . . . . . . . .  Increase
53 - Too much air  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  Adjust head and fan gate, see page 6 and 10

Dirty combustion head

54 - Nozzle or filter dirty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  Replace
55 - Unsuitable nozzle delivery or angle  . . . . . . . . . . . . . . . . . . . . .  See recommended nozzles, page 5
56 - Loose nozzle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  Tighten
57 - Impurities on flame stability spiral . . . . . . . . . . . . . . . . . . . . . . .  Clean
58 - Erroneous head adjustment or not enough air  . . . . . . . . . . . . .  Adjust, see page 10; open gate valve
59 - Blast tube length unsuited to boiler . . . . . . . . . . . . . . . . . . . . . .  Contact boiler manufacturer

10 x blinks

60 - Connection or internal fault

Summary of Contents for RL 28/1

Page 1: ...nimiento Instruções de Instalação Funcionamento e Manutenção Bruciatori di gasolio Quemadores de gasóleo Queimadores a gasóleo One stage operation Funcionamiento a una llama Funcionamento a uma chama 2916092 0 CODE CÓDIGO MODEL MODELO TYPE TIPO 3472080 RL 28 1 657 T80 3472081 RL 28 1 657 T80 GB E P ...

Page 2: ...aintenance 12 Burner start up cycle diagnostics 13 Resetting the control box and using diagnostics 13 Fault Probable cause Suggested remedy 14 Status optional 15 N B Figures mentioned in the text are identified as follows 1 A part 1 of figure A same page as text 1 A p 3 part 1 of figure A page number 3 NOTE In conformity with Efficiency Directive 92 42 EEC the application of the burner on the boil...

Page 3: ...ing unit characteristics Burner delivery 80 kg h max Light oil pressure 0 7 bar max Ambient temperature 40 C max Light oil temperature 40 C max Attachment connectors 1 4 inch MODEL RL 28 1 TYPE 657 T80 OUTPUT 1 DELIVERY 1 kW 178 332 153 286 15 28 Mcal h kg h FUEL LIGHT OIL Net calorific value kWh kg Mcal kg 11 8 10 2 10200 kcal kg Density kg dm3 0 82 0 85 Viscosity at 20 C mm2 s max 6 1 5 E 6 cSt ...

Page 4: ... reset hold the pushbutton down for between 1 and 3 seconds PACKAGING WEIGHT B Approximate measurements The burner is shipped in cardboard boxe with the maximum dimensions shown in table B The weight of the burner complete with pack aging is indicated in table B MAX DIMENSIONS C Approximate measurements The maximum dimensions of the burner are giv en in C Bear in mind that inspection of the combus...

Page 5: ...TE area values have been ob tained considering a surrounding temperature of 20 C and an atmospheric pressure of 1000 mbar approx 100 m above sea level and with the combustion head adjusted as shown on page 6 TEST BOILER B The firing rate was set in relation to special test boilers in accordance with the methods defined in EN 267 standards Figure B indicates the diameter and length of the test comb...

Page 6: ...ed after having protected the thread with antiscruffing products high tempera ture grease compounds graphite The burner boiler seal must be airtight CHOICE OF NOZZLES Choose the couple of nozzles among those giv en in table C Use nozzles with a 60 spray angle at the recom mended pressure of 12 bar When the burner fires only the first nozzle works Its delivery is higher than that of the second noz ...

Page 7: ... necessary to change a nozzle with the burner already fitted to the boiler proceed as outlined below Retract the burner on its slide bars as shown in fig B p 5 Remove the nuts 1 D and the disk 2 Use spanner 3 D to change the nozzles COMBUSTION HEAD SETTING The setting of the combustion head depends ex clusively on the delivery of the burner in other words the combined delivery of the two nozzles s...

Page 8: ...pipe diameter 1 Burner 2 Pump 3 Filter 4 Manual on off valve 5 Suction line 6 Foot valve 7 Rapid closing manual valve remote con trolled only Italy 8 On off solenoid valve only Italy 9 Return line 10 Check valve only Italy HYDRAULIC CONNECTIONS B The pumps are equipped with a by pass that connects return line with suction line The pumps are installed on the burner with the by pass closed by screw ...

Page 9: ...9 Control deviceTL LAYOUT C RL 28 1 burner electrical connection Cable section not indicated 1 5 mm2 Key to layout C h1 Hourcounter IN Manual burner stop switch S Remote lock out signal TL Limit control device system this shuts down the burner when the boiler tempera ture or pressure exceeds the setpoint value TS Safety control device system this oper ates when TL is faulty X7 7 pole plug NOTE The...

Page 10: ...p can be considered to be primed when the light oil starts coming out of the screw 3 Stop immediately the burner and tighten the screw 3 The time required for this operation depends upon the diameter and length of the suction tub ing If the pump fails to prime at the first starting of the burner and the burner locks out wait ap prox 15 seconds reset the burner and then re peat the starting operati...

Page 11: ... not be altered unless the delivery of the burner is changed Pump pressure 12 bar This is the pressure calibrated in the fac tory which is usually sufficient for most purposes Sometimes this pressure must be adjusted to 10 bar in order to reduce fuel delivery This ad justment is possible only if the surrounding tem perature remains above 0 C 14 bar in order to increase fuel delivery or to en sure ...

Page 12: ... it comes into contact with the spark This is the ignition flame 29 s The ignition transformer switches off 36 s The solenoid valve 11 opens the fuel passes through the piping 13 and filter 14 and is then sprayed out through the 2nd noz zle This is the operating flame The starting cycle comes to an end STEADY STATE OPERATION When the boiler temperature or pressure increases until control device TL...

Page 13: ...ies are observed inside the pump use a separate pump to lift any water and other impurities that may have deposited on the bottom of the tank Then clean the insides of the pump and the cov er sealing surface Fan Check to make sure that no dust has accumulat ed inside the fan or on its blades as this condi tion will cause a reduction in the air flow rate and provoke polluting combustion Combustion ...

Page 14: ...the malfunction according to the coding system indicated in the table on page 14 SOFTWARE DIAGNOSTICS Reports burner life by means of an optical link with the PC indicating hours of operation number and type of lock outs serial number of control box etc To view diagnostics proceed as follows Hold the button down for more than 3 seconds once the red LED burner lock out remains steadily lit A yellow...

Page 15: ...sted head Adjust see page 6 fig F 30 Poorly adjusted or dirty firing electrodes Adjust see page 6 fig B 31 Poorly adjusted fan air gate too much air Adjust 32 1st nozzle is too big pulsation Reduce 1st nozzle delivery 33 1st nozzle is too small flame detachment Increase 1st nozzle delivery 34 1st nozzle dirty or deformed Replace 35 Inappropriate pump pressure Adjust Uneven fuel supply 36 Check if ...

Page 16: ...seconds after stage 5 the code I I I I will appear on the read out this indicates that the starting phase is terminated WITH CONTROL DEVICE TR OPEN 1 Burner off TL open 2 Control device TL closed 3 Motor start seconds count starts on read out V 4 Ignition valve energized 7 30 seconds after stage 4 seconds count stops on read out V 8 10 seconds after stage 7 the code I I I I will appear on the read...

Reviews: