Start-up, calibration and operation of the burner
8.1
Notes on safety for the first start-up
8.2
Combustion adjustment
In conformity with EN 267, the application of the burner on the
boiler, adjustment and testing must be carried out observing the
instruction manual of the boiler, including verification of the CO
and CO
2
concentration in the flue gases, their temperatures and
the average temperature of the water in the boiler.
Settings carried out in factory
The values in Tab. H refer to 12.5% of CO
2
, at sea level and with
an ambient and the light oil temperature of 20 °C.
Tab. H
8.3
Nozzles installation
The burner complies with the emission requirements of the
EN 267 standard.
In order to guarantee that emissions do not vary, recommended
and/or alternative nozzles specified by the manufacturer in the In-
struction and warning booklet should be used.
8.3.1
Nozzles recommended
Danfoss type S.
8.4
Pump pressure
The pump leaves the factory set for kerosene working.
10 bar:
maximum pressure for kerosene.
8
Start-up, calibration and operation of the burner
WARNING
The first start-up of the burner must be carried out
by qualified personnel, as indicated in this manual
and in compliance with the standards and regula-
tions of the laws in force.
WARNING
Check the correct working of the adjustment, com-
mand and safety devices.
WARNING
The combustion air is sucked from outside, there-
fore, there can be sensitive temperature varia-
tions that can influence the percentage value of
the CO
2
. It is advisable to adjust the CO
2
accord-
ing to the indicated diagram.
e.g. with a combustion air temperature of 20°C,
adjust the CO
2
to 12.5% (± 0.2%).
-10
-5
0
5
10
15
20
25
30
35
40
45
10.5
10.0
11.0
11.5
12.0
12.5
13.0
13.5
14.0
CO
๙>@
S9763
Combustion air temperature (°C)
Fig. 17
Burner
Nozzle
Pump
pressure
Burner
output
Combustion
head
adjustment
Air damper
adjustment
Model
GPH
Angle
bar
kg/h ± 4%
Set-point
Set-point
RDB 3.2 BT 58/70
DANFOSS
1.75
45° S
8
4.9
1
6.7
WARNING
It is advisable to replace nozzles every year dur-
ing regular maintenance operations.
CAUTION
The use of nozzles other than those specified by
the manufacturer and inadequate regular
maintenance may result into emission limits non-
conforming to the values set forth by the
regulations in force, and in extremely serious
cases, into potential hazards to people and
objects.
The manufacturing company shall not be liable for
any such damage arising from non-observance of
the requirements contained in this manual.