20184179
8
GB
Technical description of the burner
5.1
Technical data
Tab. A
(1)
Reference conditions: Room temperature 20°C - Barometric pressure 1000 mbar – Altitude 100 m above sea level.
5.2
Electrical data
Tab. B
5
Technical description of the burner
MODEL
PRESS 140 P/N
Output
(1)
kW
855 ÷ 5130 kW
Delivery
(1)
kg/h
75 ÷ 450 kg/h (see the following tables)
Fuel
Heavy oil
- max viscosity at 50 °C
mm
2
/s
50 (7°E) up to 500 (65°E) with kit
Operation
• Intermittent (min. 1 stop every 24 hours).
Nozzle
number 1 (nozzle with return line)
Standard applications
Boilers: water, steam, diathermic oil
Ambient temperature
°C
0 - 40
Combustion air temperature
°C max
60
Pump flow rate
pressure range
kg/h
bar
60
Weight of the burner (complete with
packaging)
kg
690
25
MODEL
PRESS 450P/N
Electrical power supply
V
Hz
3 ~ 400 ± 10%
50
Electrical motor
rpm
kW
V
A
2915
15
400/690
26.8-15.5
Heater
kW
19.6
Ignition transformer
Primary: 2.3A - Secondary: 2x6 kV - 35 mA
Absorbed electrical power
kW max
36.7
Protection level
IP
40
Summary of Contents for PRESS 450 T/N
Page 2: ...Translation of the original instructions ...
Page 35: ...33 20170392 GB Appendix Electrical panel layout 0 1 1 1 ...
Page 36: ...20170392 34 GB Appendix Electrical panel layout ...
Page 37: ...35 20170392 GB Appendix Electrical panel layout 0 1 0 2 3 2 3 ...
Page 38: ...20170392 36 GB Appendix Electrical panel layout 0 0 ...
Page 41: ......
Page 42: ......
Page 43: ......