![Riello MCM 10 Technical Specifications Download Page 29](http://html1.mh-extra.com/html/riello/mcm-10/mcm-10_technical-specifications_1460115029.webp)
MULTI SENTRY
SPTMSTD2T16EREN
27
11.
OPTIONS
>11.1 COMMUNICATION
PowerNETGuard
is a centralised UPS management and control software package using the SNMP
communications protocol. It is the ideal UPS management tool for IT/EDP managers running Datacentre and
medium-to-large-sized networks.
The main features of the software include:
Various display levels by geographical areas, building plans, maps.
Multi-user accesses with various security levels.
Compatible with RFC 1628 standard SNMP agents.
Graphical representation and file backup of operating measurements
Notification of alarms via email and SMS.
Integrated Wap Server for display of alarms.
Suitable for operation with Windows operating systems: (98, ME, NT, 2000, 2003, and Xp), Linux, Mac OS
X, Solaris 8 and 9.
Hardware
Two slots are available in which to house one or two of the following options:
a)
NetMan 204:
the NetMan network agent allows UPS management across a LAN using any of the
main network communication protocols - TCP/IP, HTTP, HTTPS and network interface (SNMP).
NetMan enabled UPS integrate easily into medium and large sized networks and provide reliable
communications between the UPS and management system employed.
b)
MultiCOM 302:
a Modbus/Jbus protocol converter through an RS232 or RS485 output for monitoring
the UPS, for example, from a BMS (Building Management System). It also provides a second
independent RS232 serial line that can be used by other devices such as a NetMan or PC.
c)
MultiCOM 352:
it is a serial duplexer that allows two devices to be connected to a single serial port
on a UPS. It can be used where numerous serial connections and multiple UPS polling are required,
and is ideal for LAN networks with a firewall.
d)
MultiCOM 382:
it provides a set of relay contacts to provide UPS alarm and status indication. The
contacts are connected through terminal connections. Signal contacts include Emergency Power
Off (EPO), Remote Shut Down (RSD), On Battery, On Bypass, Alarm and Low battery. The contacts
are change over or normally open.
e)
MultiCOM 401:
it is an external accessory with which you can connect a UPS to a Profibus DP
network.
f)
Multi I/O:
Multi I/O has configurable input and output signal contacts to allow UPS integration with
control systems. It can be used to connect two devices to a single UPS serial communication port.
It can also communicate using the MODBUS/JBUS protocol on RS485 lines.
g)
MultiCOM 372:
MultiCOM 372 provides a UPS with an additional RS232 serial interface port. The
card has Emergency Power Off (EPO) and Remote Shut Down (RSD) inputs with terminal
connections.