Indication of operation :

In normal operation, the various statues are
indicated in the form of colour codes according
to the  table below.
The interface diagnosis (with adapter) can be
activated by pressing the lock-out button for
> 3 seconds.

Diagnosis of fault causes :

After lock-out has occurred, the red signal lamp is steady on. In this status, the visual fault diagnosis
according to the error code table can be activated by pressing the lock-out reset button for > 3 seconds.
The interface diagnosis (with adapter) can be activated by pressing again the lock-out button for > 3
seconds.

The blinkers of red LED are a signal with this sequence :

(e.g. signal with n

°

 3 blinks – faulty air pressure monitor)

Lock-out

If the 1st stage flame does not light within the safety limit (3s max.)
the burner locks-out.
When flame-failure occurs during working, shut down takes place
within one second.

START UP CYCLE

Correct operation

0s           The burner begins

the ignition cycle

0s-2s      Safety time
2s-42s   Pre-purge with

opened air damper

42s-45s  Ignition 1st stage
52s         Ignition 2nd stage.

TR

M

V1

2 s max.

Ignition

transformer

40 s

1

Lock-out

Normal

3 s max.

Lock-out due to ignition failure

2

V2

10 s

time (s)

time (s)

3 s max.

2 s max.

40 s

Error code table

Possible cause of fault

No establishment of flame at the end of safety time :  - faulty or soiled fuel valves

- faulty or soiled flame detector
- poor adjustment of burner, no fuel
- faulty ignition equipment

Faulty air pressure monitor

Simulation of flame on burner start up

Loss of flame during operation : - faulty or soiled fuel valves

- faulty or soiled flame detector
- poor adjustment of burner

Wiring error or internal fault

Blink code

Color code table

Operation statues

Stand-by

Pre-purging

Ignition phase

Flame OK

Poor flame

Undervoltage, built-in fuse

Fault, alarm

Extraneous light

Color code table

LED off

LED off

3 sec.

3 sec.

3 sec.

9

Summary of Contents for GS10D

Page 1: ...e high quality level guarantees safe working In developing these burners special attention was paid to reducing noise to the ease of installation and adjustment to obtaining the smallest size possible...

Page 2: ...V type kW kW IP kW A A IP type V1 V2 I1 I2 dB A W mg kWh mg kWh Heat output Since the Company is constantly engaged in the production improvement the aesthetic and dimensional features the technical d...

Page 3: ...5 kW 25 0 5 10 15 20 1 1 5 2 2 5 40 20 60 80 100 120 140 3 30 20 40 60 80 100 120 Test conditions conforming to EN 676 standards Temperature 20 C Pressure 1013 5 mbar Altitude 100 m a s l Useful work...

Page 4: ...120 145 W mm 46 46 55 With 1 2 3 4 reduction nipple supplied 5 9 6 7 8 1 2 3 4 P2 10 11 12 P1 Y Z X W The dimensions of the gas trains vary depending on their construction features The following table...

Page 5: ...3970537 Plug and socket Output kW 80 With natural gas P combustion head gas train combustion head Pressure loss kcal h X 1000 kW 0 29 mbar M B Z R D L E 4 0 7 G20 G25 kW 106 10 50 70 90 110 30 40 50 6...

Page 6: ...e conversion coefficient Once the equivalent output has been determined on the delivery scale shown at the top of the diagram move vertically downwards until you cross the line that represents the pip...

Page 7: ...e adapted to the burner output VENTILATION Air suction The different ventilation circuits always ensure low noise levels with high performance of pressure and air delivery inspite of their compact siz...

Page 8: ...for the supervision during intermittent operation For helping the commissioning and maintenance work there are two main elements The lock out reset button is the central operating element for resetti...

Page 9: ...working shut down takes place within one second START UP CYCLE Correct operation 0s The burner begins the ignition cycle 0s 2s Safety time 2s 42s Pre purge with opened air damper 42s 45s Ignition 1st...

Page 10: ...rmostat between clamps T6 and T8 removing the bridge Electrical wiring with gas leak control device DUNGS VPS 504 P PG V11 V10 V12 P TS FUSE P PG V10 V11 VPS B5 N L1 T6 T8 T7 V12 GS10D GS20D XP4 4 pol...

Page 11: ...S20D 160 170 185 170 155 130 200 Q R GS10D GS20D 11 A D F E I N V M E H BURNER BOILER MOUNTING FLANGE Z 485 525 473 525 17 22 320 365 Model GS10D GS20D X Y kg The emission data have been measured in t...

Page 12: ...tput of the boiler Head setting is easy and aided by a graduated scale a test point allows reading the air pressure in the combustion head The air damper position can be adjusted without removing the...

Page 13: ...Standard head burners can be transformed into extended head versions by using the special kit Below the KITS available for the various burners are listed showing the original and the extended lengths...

Page 14: ...e burner requires continuous ventilation in the stages without flame a special kit is available as given in the following table Kit code 3010094 GS10D GS20D Burner Continuous ventilation kit for RMG c...

Page 15: ...train Fuel supply line in the Multibloc configuration fitted with Filter Pressure stabiliser Minimum gas pressure switch Safety valve Two stage working valve with ignition gas output regulator Approva...

Page 16: ...s can be changed This document contains confidential and proprietary information of RIELLO S p A Unless authorised this information shall not be divulged nor duplicated in whole or in part Lineagrafic...

Reviews: