20162463
34
GB
Start-up, calibration and operation of the burner
6.11
Pressure switch adjustment
6.11.1 Air pressure switch
The air pressure switch is set after all other adjustments have
been made. Begin with the switch at the start of the scale. With
the burner operating, increase adjustment pressure by slowly
turning the relevant knob clockwise until the burner stops. Then
turn the knob anticlockwise by 0.1 kPa (1 mbar) and repeat
burner start-up to ensure it is operating regularly.
If the burner locks out again, turn the knob again anti-clockwise
by 0.5 mbar.
6.11.2 Maximum gas pressure switch
Adjust the maximum gas pressure switch (Fig. 35) after making
all other burner adjustments with the maximum gas pressure
switch set to the end of the scale.
To calibrate the maximum gas pressure switch, open the tap and
then connect a pressure gauge to its pressure test point.
The maximum gas pressure switch must be regulated to a value
no higher than 30% of the measurement read on the gauge when
the burner is working at maximum output.
After making the adjustment, remove the pressure gauge and
close the tap.
6.11.3 Minimum gas pressure switch
Adjust the minimum gas pressure switch after performing all the
other burner adjustments with the pressure switch set to the start
of the scale (Fig. 36).
With the burner operating at maximum output, increase
adjustment pressure by slowly turning the relative knob clockwise
until the burner stops.
Then turn the knob anticlockwise by 0.2 kPa (2 mbar) and repeat
burner start-up to ensure it is operating regularly.
If the burner locks out again, turn the knob anticlockwise again by
0.1 kPa (1 mbar).
ATTENTION
In conformity with the standard, the air pressure
switch must prevent the air pressure falling below
80% of the adjusted value and the CO in the flue
gases exceeding 1% (10,000 ppm).
To check this, insert a combustion analyser in the
flue, slowly reduce the burner air setting (for
example with a piece of cardboard) and verify that
the burner locks out before the CO value in the
flue gases exceeds 1%.
ATTENTION
1 kPa = 10 mbar
Fig. 34
D3854
PGM
PA
D3856
20181543
Fig. 35
Fig. 36
D3855
Summary of Contents for GI/EMME 1400
Page 2: ...Translation of the original instructions ...
Page 55: ...53 20162463 GB Appendix Electrical panel layout 0 0 0 1 0 2 0 0 0 0 0 0 0 30 3 3 0 0 1 0 ...
Page 56: ...20162463 54 GB Appendix Electrical panel layout 0 1 2 2 2 0 ...
Page 57: ...55 20162463 GB Appendix Electrical panel layout 0 1 2 2 2 0 ...
Page 60: ...20162463 58 GB Appendix Electrical panel layout 0 1 2 2 2 3 2 2 2 2 2 2 2 2 2 2 2 3 2 4 56 ...
Page 65: ...63 20162463 GB Appendix Electrical panel layout 011 234 1 5 6 732 0 1 31 8 2 0 9 9 ...
Page 66: ...20162463 64 GB Appendix Electrical panel layout 0 ...
Page 71: ...69 20162463 GB Appendix Electrical panel layout 0 0 0 1 0 2 0 0 0 0 0 0 0 30 3 3 0 0 1 0 ...
Page 72: ...20162463 70 GB Appendix Electrical panel layout 0 1 2 2 2 0 ...
Page 73: ...71 20162463 GB Appendix Electrical panel layout 0 0 0 1 0 2 0 0 0 0 0 0 0 0 0 0 1 0 ...
Page 75: ...73 20162463 GB Appendix Electrical panel layout 0 1 2 2 2 3 2 2 2 2 2 2 2 2 2 2 2 3 2 4 56 ...
Page 78: ......
Page 79: ......