62 

 

A

LARMS AND INDICATORS

 

UPS ACOUSTIC SIGNAL TABLES

 

Signal 

Cause 

Solution 

1 beep every 4 
seconds 

The UPS is operating in 
battery mode 

Check the input voltage 

The battery is discharging 

Save your work and switch off the equipment 

1 beep per  
second 

Overload in output 

Check the charge level indicator and remove some loads 

Continuous 
beep 

The UPS has a fault 

Check the indicators table and contact the reseller if 
necessary 

 UPS ALARMS TABLE 

Problem 

Cause 

Solution 

The power cable is not 
connected correctly 

Check the power cable connection 

The wall socket may be 
faulty 

Please contact a trustworthy electrician  

The UPS output may have 
short-circuited or be 
overloaded 

1.  Disconnect all the loads and ensure that there is nothing 

short-circuiting the output  

2.  Ensure that the loads are not isolated or short-circuited 

internally 

The UPS does 
not start up 
when “ON” is 
pressed 

An internal fuse may have 
blown 

Please contact the reseller 

There may be no output 
voltage in the socket used 

Check the output fuse (if present) 

The UPS is not 
powering the 
loads 

There is no output voltage 
on the sockets 

1.  Check the connection cable 
2.  Ensure that the load does not exceed the UPS’s 

maximum capacity 

The battery is not charged 

Recharge the battery for at least 4 hours 

The battery has 
reduced its 
back-up time 

It may not be possible to 
fully recharge the battery. 

1.  Recharge the battery for at least 8 hours 
2.  Replace the battery 

The UPS fault 

indicator 

  is 

on 

 The UPS has a fault 

Save your work and stop the equipment. See the LCD 
INDICATOR PANEL for details. 

The battery fault 

indicator 

  is 

on 

The battery is faulty 

1.  Check the battery connection 
2.  Please contact the reseller to order a new battery to 

replace the faulty battery. 

The UPS may be 
overloaded 

Check the load status 

The equipment 
connected to the 
UPS switch off 

The UPS may be faulty 

Please contact the reseller 

The UPS emits 
a continuous  
beep 

The UPS is in a fault state 

Check the UPS acoustic signals table 

The buttons do 
not work 

The button is broken 

Please contact the reseller 

 

Summary of Contents for DVD 150

Page 1: ...1...

Page 2: ...36 GB USER MANUAL GB...

Page 3: ...LLATION OF THE DVD MODELS WITH BATTERY BOX 48 POSITIONING THE FRONT PANEL LCD FOR DVD MODELS 49 INSTALLING DVR AND DVD MODELS IN A RACK CABINET 51 CONNECTION 52 CONNECTION TO THE NET TEL PROTECTION DE...

Page 4: ...RT 62 COMMUNICATION SOCKET 62 SOFTWARE 63 MONITORING AND CONTROL SOFTWARE 63 CONFIGURATION SOFTWARE 63 ALARMS AND INDICATORS 64 REPLACING THE BATTERY 65 DIALOG VISION TOWER 65 DIALOG VISION RACK 66 DI...

Page 5: ...tailed instructions on how to use and install the UPS For information on using and getting the best performance from your UPS this manual should be kept safely near the UPS and CONSULTED BEFORE TAKING...

Page 6: ...able CHARACTERISTICS Sinusoidal output voltage Front panel LCD Microprocessor control for high reliability High frequency technology Automatic correction of input voltage fluctuations by the built in...

Page 7: ...minal power VA 500 800 1100 1500 2000 500 800 1100 1500 2200 3000 Nominal power W 350 540 740 1050 1350 350 540 740 1050 1540 2100 Nominal output voltage Vac 200 208 220 230 240 Dimensions LxHxD mm 11...

Page 8: ...42 PRESENTATION REAR VIEW DVT 50 80 110 DVT 150 200 DVR 50 80 110 DVD 150...

Page 9: ...Cooling fan 3 Net Tel protection 4 Input thermal protection 5 IEC network input plug 6 IEC output plug max 10A 7 Expansion slots for interface cards 8 Battery expansion connector 9 IEC output plug max...

Page 10: ...kaging should contain the following UPS IEC 10A power cable IEC 16A for DVD models 220 300 only 2 IEC 10 A connection cables USB cable Plastic supports DVD model only Guides for rack installation hand...

Page 11: ...CHECKING THE CONTENTS After opening the packaging check the contents The packaging should contain the following Battery Box UPS Battery Box connection cable Guides for rack installation handles kit U...

Page 12: ...nsation Warning A long period of use in an environment with a temperature over 25 C will shorten battery life The UPS should be placed at least 20 cm away from a monitor in order to avoid interference...

Page 13: ...DELS WITH BATTERY BOX 1 Assemble the supports and the extension as shown in the figure 2 Put the UPS and the battery box in a vertical position and place the two supports close to them 3 Carefully ins...

Page 14: ...r tower The information below explains how to rotate the display A From Rack to Tower 1 Place the UPS flat and press the key shown 2 Rotate the LCD display 90 3 Reinsert the display in its housing B F...

Page 15: ...n be installed in a 19 rack cabinet The installation procedure is described below 1 Align and screw the handles onto the sides of the UPS 2 Secure the guides onto the rack cabinet supports with the sc...

Page 16: ...one modem network card etc is inserted in the connector marked OUT N B This protection device limits the effects of an overvoltage but does not guarantee absolute protection POWERSHARE All the models...

Page 17: ...MS Imax 20mA between Pin 1 and 2 of the terminal using an unshielded wire of diameter 18 22 AWG 0 75 mm2 0 3mm2 5 Reconnect the terminal to the EPO input 6 Ensure that the switch connected to the EPO...

Page 18: ...current automatically increases to 6 A START UP SHUTDOWN To start up and shut down the UPS press the ON and OFF switch for at least three seconds Starting up for the first time after about 30 seconds...

Page 19: ...53 SYSTEM DESCRIPTION FRONT PANEL The front panel consists of a display and ON OFF and SELECT keys LCD SELECT button LCD Front panel ON button OFF button Part A Part B Part D Part C...

Page 20: ...voltage unit Volt BATTERY estimated back up time as a percentage of the battery charge BATTERY MIN estimated battery back up time unit Minutes Note The estimated back up time in minutes is also provid...

Page 21: ...at regular 4 second intervals Flashing When operating in battery mode the UPS signals that it is about to switch off due to end of discharge In this state it beeps at regular 1 second intervals Steady...

Page 22: ...d intervals Once the load has been reduced to within the 100 threshold the UPS will return to normal operating mode Warning If the overload is too high the protection device will be activated and the...

Page 23: ...ller UPS internal error Contact the reseller SETTING THE VALUES ON THE FRONT PANEL LCD The LCD has two parts left Part A and right Part B The left side displays the following parameters Input voltage...

Page 24: ...play Part A and Capacity as a percentage of the battery on the right side Part B Configuration example Press SELECT for 3 seconds Press SELECT to change the field Press ON to confirm the field Press S...

Page 25: ...t Intermittent 1s on 1s off t 1 2 3 4 5 6 0 1 7 8 9 10 g The UPS is performing the battery test Intermittent for 3 times 0 5s on 0 5s off t 1 2 3 4 5 6 0 1 7 8 9 10 h If none of the events in the prev...

Page 26: ...PS Failure Alarm contact closed in the event of failure or signalling of alarms by the UPS maximum values 25mA 35Vdc Vce sat max 1 5V 25mA e Input programmable via RS232 5 15 Vdc USB PORT The USB port...

Page 27: ...cable provided Insert the CD Rom and select the operating system required Follow the installation instructions For more detailed information on installing and using the software refer to the software...

Page 28: ...tact the reseller There may be no output voltage in the socket used Check the output fuse if present The UPS is not powering the loads There is no output voltage on the sockets 1 Check the connection...

Page 29: ...s of leakage contact the reseller immediately Recycle the used batteries Never throw batteries into a fire as they may explode Do not open or damage the batteries The electrolyte contents are harmful...

Page 30: ...ands 2 Disconnect the UPS battery cable 3 Undo the screws securing the support to the UPS and remove the plate securing the batteries 4 Remove the batteries on a flat surface 5 Insert the new batterie...

Page 31: ...both hands 2 Undo the screws securing the support to the UPS and remove the plate securing the batteries 3 Disconnect the cable 4 Remove the batteries on a flat surface 5 Insert the new batteries in t...

Page 32: ...cycles 110 alarm and failure after 30 seconds OVERLOAD From battery power 120 failure after 5 cycles TRANSFER TIME Typical 4 msec 6 msec max Nominal battery voltage 12V 24V 24V 48V 48V BATTERY Recharg...

Page 33: ...cles TRANSFER TIME Typical 4 msec typical 6 msec max Nominal battery voltage 12V 18V 24V 48V 96V 96V BATTERY Recharge time Less than 6 hours at 90 Dimensions LxHxD mm 438X44 3X460 19 x1Ux460 438X87 9X...

Page 34: ...165...

Reviews: