7
INSTALLATION
BOILER PLATE (A)
Drill the combustion chamber locking plate as
shown in (A). The position of the threaded holes
can be marked using the thermal screen sup-
plied with the burner.
SECURING THE BURNER TO THE
BOILER (B)
Protective fettling in refractory material 8) must
be inserted between the boiler's fettling 9) and
the blast tube 7).
This protective fettling must not compromise the
extraction of the blast tube.
- Remove the screws 2) from the two slide
bars 3).
- Remove the screw 1) fixing the burner 4) to the
flange 5).
- Withdraw the combustion head 10) from the
burner 4).
Secure flange 5) to the boiler plate interposing
the supplied gasket 6). Use the 4 screws provid-
ed after having protected the thread with an-
tiscruffing products (high-temperature grease,
compounds, graphite). The burner-boiler seal
must be airtight.
CHOICE OF NOZZLE (C)
The burner complies with the emission require-
ments of the EN 267 standard.
In order to guarantee that emissions do not vary,
recommended and/or alternative nozzles speci-
fied by the manufacturing company in the In-
struction and warning booklet should be used.
Warning:
It is advisable to replace nozzles
every year during regular maintenance op-
erations.
Caution:
The use of nozzles other than
those specified by the manufacturing
company and inadequate regular maintenance
may result into emission limits non-conforming
to the values set forth by the regulations in
force, and in extremely serious cases, into
potential hazards to people and objects.
The manufacturing company shall not be liable
for any such damage arising from nonobser-
vance of the requirements contained in this
manual.
The nozzle must be chosen from among those
listed in table (C).
The deliveries of the 1st and 2nd stages must be
contained within the value range indicated on
page 7.
IMPORTANT
Use nozzles with a 60° hollow
or semi-
solid spray angle
.
In case of moisture due to narrow combus-
tion chamber, it is possible to use nozzles
providing 45° full-cone spray angle.
(A)
(C)
(1)
light oil: density 0,84 kg/dm
3
- viscosity 4,2 cSt/20 °C - temperature 10 °C
GPH
Kg/h
(1)
8 bar
11 bar
14 bar
17 bar
20 bar
22 bar
2,25
2,50
3,00
3,50
4,00
4,50
5,00
5,50
6,00
6,50
7,4
8,2
9,9
11,5
13,2
14,8
16,5
18,1
19,8
21,4
8,8
9,8
11,8
13,7
15,7
17,6
19,6
21,5
23,5
25,5
10,0
11,2
13,4
15,6
17,8
20,1
22,3
24,5
26,8
29,0
11,1
12,4
14,8
17,3
19,8
22,2
24,7
27,2
29,7
32,0
11,9
13,4
16,1
18,8
21,5
24,0
26,8
29,5
32,2
34,5
12,4
14,0
16,8
19,8
22,6
25,1
28,1
30,9
33,7
36,0
(B)
D587