9
INSTALLER
INSTALLER
11
PLACE OF INSTALLATION
R
7000 ACI PLUS
buffer tanks can be installed in any room
where there is no specific requirement for an electrical protec-
tion rating higher than IP X0D.
≥ 0,4 m
≥ 0,4 m
≥ 0,6 m
≥ 0,3 m
≥ 0,4 m
9
Respect the minimum specified installation distances to
ensure correct installation and access for maintenance.
12
INSTALLATION IN OLDER SYSTEMS AND SYSTEMS
REQUIRING MODERNISATION
When installing
R
7000 ACI PLUS
buffer tanks in old systems or
systems requiring modernisation, always perform the following
checks.
− Make sure that the system is fitted with safety and con-
trol devices in accordance with applicable legislation and
standards
− Make sure that the central heating circuit has been
flushed out to remove all sludge and lime scale, and has
been vented and seal tested
− Make sure that a suitable water treatment system is in-
stalled if the quality of the supply/recirculation water so
demands (refer to the reference values listed in the table
alongside).
REFERENCE VALUES
pH
6-8
Electrical conductivity
less than 200 μS/cm (25°C)
Chlorine ions
less than 50 ppm
Sulphuric acid ions
less than 50 ppm
Total iron
less than 0.3 ppm
Alkalinity M
less than 50 ppm
Total hardness
less than 35°F
Sulphur ions
none
Ammonia ions
none
Silicon ions
less than 30 ppm